i
IMPORTANT NOTICE
● The company pursues a policy of continuous improvement in design and performance of products. The
right is therefore reserved to vary specifications without notice.
● The company cannot anticipate every possible circumstance that might involve a potential hazard.
● This heat pump air conditioner is designed for standard air conditioning only. Do not use this heat pump
air conditioner for other purposes such as drying clothes, refrigerating foods or for any other cooling or
heating process.
● Do not install the unit in the following places. It may cause a fire, deformation, corrosion or failure:
* Places where oil (including machinery oil).
* Places where a lot of sulfide gas drifts such as in hot spring.
* Places where inflammable gas may generate or flow.
* Places where strong salty wind blows or with an atmosphere of acidity or alkalinity such as coastal
regions.
● Do not install the unit in the place where silicon gas drifts. If the silicon gas attaches to the surface of
heat exchanger, the fin surface repels water. As a result, drain water splashes outside the drain pan and
splashed water runs into electrical box. In the end, water leakage or electrical devices failure may occur.
● Pay attention to the following points when the unit is installed in a hospital or other facilities where
electromagnetic wave generates from medical equipment.
* Do not install the unit in the place where the electromagnetic wave is directly radiated to the electrical
box, wired controller cable or switch.
* Install the unit at least 3 meters away from electromagnetic wave such as a radio.
● Do not install the unit in the place where the breeze directly blows to the animals and plants. It could
adversely affect the animals and plants.
● The installation and service engineering should be in accordance with the local laws and regulations.
● If you have any questions, contact your distributor or dealer.
● The installation of this air conditioner can only be carried out by dealers or specialists. If the user installs
the air conditioner by himself, it may cause leakage, electric shock or fire.
● This manual gives a common description and information for this heat pump air conditioner and also for
other models.
● To protect the environment, do not discard the product at will, the company can provide recycling services
as per the relevant provisions of the country, and provide replaceable components as per national
standards.
● This manual should be considered as a permanent part of the unit and should remain with it.
● No part of this manual may be reproduced without written permission.
● It is assumed that this heat pump air conditioner will be operated and serviced by English speaking
people. If this is not the case, the customer should be added safety, caution and operating signs in the
native language.
● This heat pump air conditioner has been designed for the following temperatures. Operate the heat pump
air conditioner within this range.
Temperature
(ºC)
Range
Maximum
Minimum
Cooling
operation
Indoor
23 WB
15 WB
Outdoor
52 DB*
-5 DB
Heating
operation
Indoor
27 DB
15 DB
Outdoor
15 WB
-20 WB
DB: Dry Bulb, WB: Wet Bulb
NOTE:
*-5ºC~48ºC DB is stabilized operation range, 48ºC~52ºC DB is for interval operation