Table 2: Physical and electrical data
Outdoor unit model
HMCG22B241S HMCG22B361S HMCG22B481S HMCG22B601S
Compressor type
Twin rotary
Twin rotary
Twin rotary
Twin rotary
Compressor rated load
11.0
16.1
26.0
26.5
Compressor locked rotor
n/a
n/a
n/a
n/a
Crankcase heater
No
No
No
No
Factory external discharge
muffler
No
No
No
No
HS kit required with TXV
No
No
No
No
HS kit part number
(S1-2SA067*****)
n/a
n/a
n/a
n/a
Fan diameter (in.)
20
22
20
20
Fan motor type
ECM
ECM
ECM
ECM
Fan motor rated HP
1/12
1/7
1/6
1/6
Fan motor rated load (A)
n/a
n/a
n/a
n/a
Fan motor nominal RPM
880
880
810
850
Fan motor nominal CFM
1825
2235
3525
3615
Coil face area (sq ft)
6.10
7.49
14.03
14.03
Coil rows deep
2
2
2
2
Coil fins per inch
18
17
17
17
Liquid refrigeration piping
outdoor unit (field-installed)
3/8
3/8
3/8
3/8
Vapor refrigeration piping
outdoor unit (field-installed)
5/8
5/8
7/8
7/8
Unit charge (lb-oz)
4-8
6-3
8-13
9-9
Charge (oz/ft)
0.38
0.38
0.38
0.38
Operating weight (lb)
99
117
206
207
Physical and electrical data notes
1. The normal voltage range is rated in accordance with AHRI Standard 110-2012, utilization
range A.
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. The unit charge provided is equal to 25 ft refrigeration piping. Select the appropriate indoor
section and refrigeration piping length charge additions to calculate additional charge
required and total system charge.
5. For applications with non-standard vapor line sizes, see
.
YORK Technical Guide: HMCG2 Series - 16 SEER2 Horizontal Discharge Modulating Air Conditioner
8
Johnson Controls Ducted Systems