background image

P5417054 

3

 

A room: Properly insulate any refrigerant tubing run inside a room to prevent “sweating” that can 

cause dripping and water damage to wall and floors.

 

Damp or uneven areas: Use a raised concrete pad or concrete blocks to provide a solid, level 

foundation for the unit to prevent water damage and abnormal vibration.

 

An area with high winds: Securely anchor the outdoor unit down with bolts and a metal frame. 

Provide a suitable air baffle.

 

A snowy area: Install the outdoor unit on a raised platform that is higher than drifting snow. Provide 

snow vents.

 

Do not install the unit in the following places. Doing so can result in an explosion, fire, deformation, 

corrosion, or product failure.

 

▫ Explosive or flammable atmosphere

 

▫ Where a fire, oil, steam or powder can directly enter the unit, such as nearby or above a kitchen 

stove.

 

Where oil (including machinery oil) may be present.

 

▫ Where corrosive gases such as chlorine, bromine, or sulfide can accumulate, such as near a hot 

tub or a hot spring.

 

▫ Where dense, salt-laden airflow is heavy, such as in coastal regions.

 

Where the air quality is of high acidity.

 

Where harmful gases can be generated from decomposition.

 

Do not install the decorative panel with motion sensor and radiation sensor (P-AP160NAE1) in the 

following places.  It may cause failure or deterioration of the sensor.

 

Ambient temperature changes drastically.

 

Where excessive force or vibration is applied to the sensor.

 

Where static electricity or electromagnetic waves may generate.

 

Where interference of infrared light such as glasses or mist is in the detecting area.

 

Where the lens for sensor is exposed in high temperature and humidity for a long time.

 

W

here fluid and corrosive gas exist.

 

Where direct lights such as sunlight or headlight affect the sensor.

 

Where hot air from a heater, etc. affects directly to the sensor.

 

W

here the air flow returns to the sensor by hitting obstacles such as shelf, locker, etc.

 

W

here the blower devices such as ceiling fan, ventilating fan, etc. affect the air flow from the 

indoor unit.

 

Where weather affects directly the surface of the sensor.

 

Where the lens surface may smudge or be damaged such as a dusty environment.
Detecting function will decrease if the lens for sensor smudges. 

In this case, wipe off smudges using a cotton swab soaked with alcohol (Isopropyl alcohol is 

recommended.) or a soft cloth. (When wiping off smudges on the lens for sensor, do not apply 

excessive force.  If excessive force is applied, the resin lens may be damaged and this may cause 

malfunctions such as misdetection or undetectable of the motion.)

 

Do not position the condensate pipe for the indoor unit near any sanitary sewers where corrosive 

gases may be present. If you do, toxic gases can seep into breathable air spaces and can cause 

respiratory injuries. If the condensate pipe is installed incorrectly, water leakage and damage to the 

ceiling, floor, furniture, or other possessions may result. If the condensate pipe becomes clogged, 

water may drip from the indoor unit. Do not install the indoor unit where such dripping can cause 

moisture damage or uneven locations: Use a raised concrete pad or concrete blocks to provide a 

solid, level foundation for the unit to prevent water damage and abnormal vibration.

 

Before performing any brazing work, be sure that there are no flammable materials or open flames 

nearby.

 

Perform a test run to ensure normal operation. Safety guards, shields, barriers, covers, and protective 

devices must be in place while the compressor/unit is operating. During the test run, keep fingers and 

clothing away from any moving parts. 

 

Clean up the site when finished, remembering to check that no metal scraps or bits of wiring have 

been left inside the unit being installed.

After installation work for the system has been completed, explain the “Safety Precautions,” the proper use 

and maintenance of this unit to the customer according to the information in all manuals that came with the 

system. All manuals and warranty information must be given to the user or left near the Indoor Unit.

Summary of Contents for HIC4008B21S

Page 1: ...TIONERS Type Model 4 Way Cassette H Y C IC4008B21S H Y C IC4012B21S H Y C IC4015B21S H Y C IC4018B21S H Y C IC4024B21S H Y C IC4030B21S H Y C IC4036B21S H Y C IC4048B21S IMPORTANT READ AND UNDERSTAND...

Page 2: ...to verify that your product model numbers have the same version of software Access the main printed circuit board in each product Locate a white sticker with a P XXXX number or Connect a service check...

Page 3: ...been designed for a specific temperature range For optimum performance and long life operate this unit within the range limits according to the table below This manual should be considered as a perma...

Page 4: ...General Check 21 8 2 Electrical Wiring Capacity 21 8 2 1 Field Minimum Wire Sizes for Power Supply 21 8 2 2 Details of Electrical Wiring Connection 22 8 3 Position of Electrical Wiring Connection 23...

Page 5: ...d are attached to the unit Refer back to these safety instructions as needed This system should be installed by personnel certified by Johnson Controls Inc Personnel must be qualified according to loc...

Page 6: ...a hospital or other facility where electromagnetic waves are generated from nearby medical and or electronic devices be prepared for noise and electronic interference Electromagnetic Interference EMI...

Page 7: ...tc Where the blower devices such as ceiling fan ventilating fan etc affect the air flow from the indoor unit Where weather affects directly the surface of the sensor Where the lens surface may smudge...

Page 8: ...mpressor activates with the stop valve opened the refrigerant cycle will become subjected to extremely high pressure which can cause an explosion or fire Tighten the flare nut with a torque wrench in...

Page 9: ...door or outdoor units without turning OFF the main power supply After stopping operation be sure to wait at least five minutes before turning off the main power switch Otherwise water leakage or elect...

Page 10: ...ceiling surfaces Any variance or inclination can cause moisture to back up into the condensate pan overflow and seepage onto ceiling or wall surfaces and cause damage to carpeted surfaces or furniture...

Page 11: ...essive force is applied as a result of mishandling of the unit during installation 3 Before Installation 3 3 Factory Supplied Accessories 1 Check to ensure that the following accessories are packed wi...

Page 12: ...objects inside the indoor unit and verify that no foreign objects remain inside in the indoor unit before the installation and Test Run Failure to do this can result in equipment failure and damage t...

Page 13: ...d condensation 8 If installing the indoor unit to a high ceiling the warmed air will remain near the ceiling during heating operation Thus a parallel installation of a circulator is recommended 9 Do n...

Page 14: ...16 Dimension of Opening 33 1 16 Unit Size 29 15 16 Dimension of Suspension Bolts Piping Connection Side Condensate Piping Connection Side Unit inch 4 Positions of Suspension Bolts M10 or W3 8 4 1 2 x...

Page 15: ...allation comes with a scale printed on a portion of the outer packaging Detach this area with the printed scale to use in sizing and checking the opening Refer to the procedure shown in Item 6 2 Mount...

Page 16: ...oor Unit Nut Field Supplied Surface of Ceiling Approx 1 15 16 inches Washer Accessory Washer with Insulation Accessory 4 Mounting Nuts and Washers Mount nuts and washers onto the suspension bolts befo...

Page 17: ...h 5 0 mm The pattern board template for the installation and the checking scale are printed on the packing Cut off the checking scale for dimension of opening from packing to adjust the position of th...

Page 18: ...e scale of the pattern board template while maintaining the vertical alignment of the indoor unit 2 See that the secured screws for the panel are tightened Tighten the securing screws for the panel un...

Page 19: ...the cutting operation After the cut is made blow out each pipe with dry compressed air or nitrogen to remove this residue before making pipe connections 6 1 Piping Materials 1 Tolerances of refrigeran...

Page 20: ...or the outdoor unit 10 If temperature and humidity inside the ceiling exceed 80 6 F 27 C RH80 condensation occurs on the surface of the accessory insulation Wrap additional insulation approximately 3...

Page 21: ...ose Accessory Twisted Incompletely Insertion Check to ensure that the condensate pipe discharges moisture properly If connected incorrectly it can cause structural damage to indoor wall and ceiling su...

Page 22: ...nd spillover into the room after unit operation has stopped Hose Clamp Accessory Tightening Torque 2 2 2 6 ft lbs Condensate Pipe Connection Condensate Hose Accessory Max 11 13 16 inches 1 1 8 inches...

Page 23: ...d at the pipe end and that no moisture leakage occurs If the end of the condensate pipe cannot be checked visually pour another 50 to 67oz 1 5 to 2 liters of water to the condensate pan If the water o...

Page 24: ...he condensate pan The heat exchanger is heated since a slight amount of refrigerant circulates inside the indoor unit during periods of stoppage As a result moisture in the condensate pan evaporates c...

Page 25: ...that the indoor fan and the outdoor fan have stopped before attempting any electrical wiring work or for any scheduled electrical work that is being performed Tighten screws according to the followin...

Page 26: ...lect the wiring size GFCI in accordance with the regulations for each region the Installation and Maintenance Manual and the dedicated electrical circuit that must be used Outside of the indoor unit i...

Page 27: ...unication line Terminals A B 1 and 2 of TB2 If connected the printed circuit board PCB will be destroyed 7 Tightly clamp the power supply wiring and communication cables using the cable band inside th...

Page 28: ...ll be seriously damaged and will not recover L1 R L2 AC 208V 230V Incorrect Wiring Reconnect wirings correctly 5V A B 1 2 S L1 R L2 AC 208V 230V 5V A B 1 2 S ON OFF DSW7 Set No 1 Pin at ON side PCB 1...

Page 29: ...e wired controller Remote ON OFF function settings No 1 2 and 3 External Input Output Function Power supply ON OFF functions No 1 and 2 Function Selection Prohibiting the wired controller after manual...

Page 30: ...vailable with two wired controllers 3 The individual louver function is not designed for blocking the air outlet If the air outlets are required to be blocked a three way outlet parts set shall be use...

Page 31: ...I U with Motion Sensor The communication cable for the wired controller I U with Motion Sensor I U with Motion Sensor I U with Motion Sensor Wired Controller Wired Controller Main Setting is Available...

Page 32: ...S G F C I G F C I R L1 S L2 Mp N R L1 S L2 Mp N R L1 S L2 Mp N R L1 S L2 Mp N R L1 S L2 Mp N R L1 S L2 Mp N Where ambient temperature changes drastically Where excessive force or vibration is applied...

Page 33: ...appropriately and firmly fastened to guarantee against electrical short sparks and flame Piping Cover Cable Band Wiring Support Plate Electrical Box Cover Wiring Opening Electrical Box PCB Screw for E...

Page 34: ...F 1 2 3 4 5 6 ON OFF 1 2 3 4 5 6 ON OFF 1 2 3 4 5 6 ON OFF 5 Unit Model Code Setting DSW4 No setting is required It is for setting the model code of the indoor unit 8 6 DIP Switch Settings 1 Turn OFF...

Page 35: ...P Switch adjustments otherwise the settings will not take effect NOTES The solid square symbol signifies the ON and OFF positions for DIP switches The diagrams show original settings before shipment W...

Page 36: ...e indoor units are running Thermo OFF The outdoor unit and some indoor units stay on but don t run 8 9 Individual Louver Settings Number of Louver Outlets This setting is available only for the indoor...

Page 37: ...OK is pressed the screen will return to Item 5 Regarding the Individual Louver Setting the louver selected at Item 5 will be set as Number 1 and the other louver numbers will be changed automatically...

Page 38: ...he controller is 1 one In this case 4 is displayed Press All to select all the indoor units connected to the wired controller OK Test Run Menu Input Output Thermistor Selection Function Selection 01 0...

Page 39: ...2 Not Available Available Control of Dew Condensation Prevention K8 Not Available Available Automatic COOL HEAT Operation b8 Not Available Available Dual Setpoint R1 Not Available Available A Cooling...

Page 40: ...tback function can be selected on the wired controller Refer to Section 8 11 Function Selection by Wired Controller of the manual for details OK Test Run Menu Input Output Thermistor Selection Functio...

Page 41: ...ions 3 Check to ensure that the main power supply has been turned ON for more than 12 hours to warm up the compressor oil by the crankcase heater 4 Verify that all DIP Switch settings are correct Refe...

Page 42: ...ON and the operation starts At this time a two hour OFF timer will be set automatically c Press or select LOUV and select auto swing by pressing or The auto swing operation will start Check the opera...

Page 43: ...q6 is neither 0 nor 100 If the value displayed is 0 or 100 repeat the procedure from Item 1 If the same value reappears it may be a malfunction of the motion sensor NOTE Refer to the operator s manual...

Page 44: ...ed controller a loose or severed connection In this case verify Section 9 3 Alarm Code and perform the appropriate troubleshooting measures Consult with an authorized service engineer if the problem c...

Page 45: ...insufficient total indoor unit capacity code 32 Incorrect setting of other indoor unit number Problem with a different Indoor Unit in the same refrigerant cycle Failure at the power supply defective P...

Page 46: ...2017 Johnson Controls Inc Code No LIT 12012613 Issued November 2017 P5417054...

Reviews: