036-21083-007-A-0404
Unitary Products Group
5
TABLE 6: SYSTEM COOLING CAPACITIES AND POWER REQUIREMENTS
Air On Cool-
ing Coil
Temperature of Air on Condenser
95
°
F
105
°
F
115
°
F
Total
Cap.,
MBH
Power
Input,
KW
Sensible Capacity, MBH
Total
Cap.
MBH
Power
Input,
KW
Sensible Capacity, MBH
Total
Cap.,
MBH
Power
Input,
KW
Sensible Capacity, MBH
CFM
WB
°
F
Entering Dry Bulb,
°
F
Entering Dry Bulb,
°
F
Entering Dry Bulb,
°
F
86
80
74
68
86
80
74
68
86
80
74
68
H5CE090/K4EU090
3600
72
100
8.5
75
53
32
-
96
9.5
73
52
31
-
93
10.4
72
50
29
-
67
93
8.3
92
70
49
27
89
9.3
88
68
47
26
85
10.2
85
67
45
24
62
82
8.0
82
82
61
39
81
9.0
81
81
60
38
80
10.0
80
80
58
37
57
91
8.1
91
88
67
45
89
9.0
89
84
63
41
87
9.9
87
80
58
37
3000
72
97
8.5
66
49
31
-
93
9.5
65
48
30
-
88
10.5
64
47
29
-
67
91
8.2
82
64
47
29
86
9.2
80
63
45
28
81
10.2
79
62
44
27
62
80
8.0
80
78
61
43
78
9.0
78
76
59
41
76
10.1
76
74
57
39
57
89
8.0
89
81
63
46
86
9.0
86
77
60
42
83
9.9
83
74
56
39
2400
72
91
8.4
57
43
30
-
88
9.3
56
42
28
-
85
10.3
54
41
27
-
67
86
8.1
71
57
43
30
82
9.1
69
55
42
28
78
10.0
67
54
40
26
62
75
7.9
75
69
56
42
74
8.9
74
67
53
40
73
9.9
73
65
51
38
57
84
7.9
84
72
58
44
82
8.8
81
68
54
41
80
9.7
78
64
51
37
H5CE090/K3EU120
4200
72
104
8.5
84
59
34
-
97
9.5
82
57
32
-
90
10.4
80
55
30
-
67
97
8.3
97
80
55
30
92
9.2
92
77
52
27
86
10.2
86
75
50
25
62
91
8.2
91
91
65
40
84
9.1
84
84
59
34
78
10.0
78
78
53
28
57
91
8.2
91
91
66
41
86
9.1
86
86
61
36
81
10.0
81
81
56
31
3500
72
102
8.4
75
54
34
-
96
9.4
73
53
32
-
91
10.3
71
51
31
-
67
95
8.2
94
74
53
33
91
9.1
91
72
51
31
87
10.1
87
70
49
29
62
89
8.1
89
88
68
48
84
9.0
84
85
64
44
79
9.9
79
81
60
40
57
89
8.1
89
89
69
48
85
9.0
85
85
65
44
81
9.9
81
81
61
41
2800
72
97
8.4
63
47
31
-
91
9.3
62
46
30
-
85
10.2
60
44
28
-
67
91
8.2
80
64
48
32
86
9.1
78
62
47
31
81
10.0
77
61
45
29
62
85
8.0
85
77
61
45
79
8.9
79
74
58
42
74
9.9
74
70
54
38
57
86
8.1
86
78
62
46
81
8.9
81
74
58
52
76
9.8
76
71
55
39
H3CE120/K3EU120
4400
72
137
11.1
95
69
43
-
133
12.4
94
68
42
-
129
13.6
93
67
41
-
67
126
11.1
112
93
67
40
120
12.3
109
91
64
38
114
13.4
105
88
62
36
62
113
10.7
113
111
84
58
109
12.0
109
108
82
55
106
13.2
106
106
79
53
57
113
10.7
113
113
87
60
109
12.0
109
109
83
57
106
13.2
106
106
80
53
4000
72
134
11.3
90
66
43
20
130
12.5
89
66
42
19
125
13.6
88
65
42
18
67
123
11.3
110
89
66
42
117
12.3
106
87
64
41
111
13.4
102
86
62
39
62
110
10.9
110
106
83
59
106
12.0
106
104
81
57
103
13.2
103
102
78
55
57
110
10.9
110
110
87
64
106
12.0
106
106
83
60
103
13.2
103
102
79
56
3000
72
114
11.1
70
53
35
18
112
12.3
69
52
35
18
110
13.6
69
52
35
18
67
104
11.0
88
70
53
36
101
12.2
87
70
52
35
98
13.4
86
69
52
34
62
94
10.7
94
84
67
50
92
11.9
92
83
66
49
90
13.2
90
82
64
47
57
94
10.7
94
87
70
53
92
11.9
92
85
68
50
90
13.2
90
82
65
48
H3CE120/K3EU180
4700
72
140
11.7
101
74
46
19
135
12.8
100
72
45
17
129
13.9
98
71
43
16
67
129
11.4
119
95
67
40
124
12.5
115
94
67
39
119
13.6
110
93
66
38
62
120
11.2
120
115
87
60
115
12.3
115
113
85
58
112
13.4
112
112
83
56
57
120
11.2
120
119
91
64
115
12.3
115
115
88
61
112
13.4
112
112
85
57
HCE150/K3EU180
6250
72
163
13.7
135
99
63
-
156
15.1
132
96
60
149
16.8
129
94
58
-
67
157
13.5
157
130
94
57
151
15.0
151
127
91
55
145
16.7
145
124
89
52
62
157
13.5
157
147
125
89
151
15.0
151
141
122
87
144
16.7
144
135
119
84
57
156
13.5
156
147
137
119
150
15.0
150
141
132
116
144
16.7
144
135
126
113
5000
72
160
13.6
121
90
60
-
153
15.0
118
88
57
-
145
16.7
115
85
55
-
67
150
13.3
144
117
87
56
144
14.8
141
114
84
53
138
16.5
138
111
81
51
62
149
13.3
149
139
113
83
143
14.8
143
134
110
80
137
16.5
137
129
107
77
57
148
13.3
148
139
131
108
143
14.8
143
134
125
105
137
16.5
137
129
120
102
All Sensible Capacity
Nominal Rating
Note: These capacities are gross ratings. For net capacities, determine
the KW requirement of the supply air blower motor per the published
BLOWER PERFORMANCE data. Convert KW to MBH per the following
equation and deduct this equivalent heat from the gross cooling ratings.
Blower Motor KW x
3.415 MBH
= Blower Motor (MBH)
KW
The KW input ratings listed above include the compressor and condenser fan motor(s).