GUIDE SPECIFICATION

Furnish and install YORK Sunline air-cooled condensing 
units or equivalent, suitable for ground or roof mounting. 
Units shall have capacities and efficiencies as outlined in the 
schedules shown on the plans and shall be installed in accor-
dance with all applicable national and local codes.

I. General

a.

Units shall be manufactured in a facility registered under 
the ISO 9002 manufacturing quality standard.

b.

Units shall be CSA approved.

c.

Unit shall be packaged to allow outdoor storage.

d.

Hermetic compressors shall be covered by a five year 
limited warranty.

e.

All other unit parts shall be covered by a full year limited 
warranty.

II. Unit Cabinet

a.

Cabinet shall be constructed of 18 gauge, zinc-coated 
steel, finished with a powder paint process capable of 
withstanding a minimum of 500 salt spray hours accord-
ing to ASTM B117.

b.

Cabinet screws shall comply with the ASTM B117 salt 
spray test for a minimum of 750 hours.

c.

Panels shall be removable for easy access to all internal 
components during maintenance and service.

d.

Cabinet shall feature a separate access panel for the 
controls so that unit airflow need not be disturbed during 
servicing.

e.

Permanently attached base rails shall have 3-way fork lift 
access and lifting holes for ease of installation.

III. Compressor

a.

Compressor shall be scroll compressors with integral 
motor overload protection.

b.

Compressors for HCE090, 120 have crankcase heaters 
to keep refrigerant from diluting the compressor oil in the 
sump. Crankcase heater shall be field replaceable with-
out removal of the charge.

c.

Compressor shall be mounted on isolators to limit the 
transmission of sound and vibration.

IV. Condenser and Fans

a.

Fan motors shall be single phase, direct-drive with pro-
peller-type condenser fans which discharge air vertically 
upward.

b.

Units with more than one condenser fan motor shall be 
wired to distribute the single phase motor loads across 
the 3 phase power supply, thus minimizing phase imbal-
ance on multiple unit installations.

c.

Fan motors shall be totally enclosed with permanently 
lubricated ball-bearings for longer wear during start and 
stop cycles.

d.

Fan motors shall have inherent overload protection.

e.

Coil shall be constructed of rifled copper tubing mechan-
ically expanded and bonded to louvered aluminum fins. 
Coil shall include an integral subcooler.

V. Refrigeration Components

a.

Refrigeration system contains both high and low pres-
sure cut-outs.

b.

Service valves to ease installation and recovery of refrig-
erant.

c.

External ports to accommodate gauge lines, allowing for 
easy servicing of the unit.

d.

Each unit ships with a filter drier for field installation.

e.

Holding charge of R-22.

VI. Controls

a.

Each unit is equipped with 24 volt control circuit with ter-
minal blocks.

b.

Color-coded wiring for easy service and trouble shoot-
ing.

c.

Independent line break thermal protection for the con-
denser fans.

d.

5 minute anti-short cycle timer to protect the compressor 
from frequent cycling.

e.

Unit safety lockouts which automatically reset from the 
thermostat once the anti-short cycle timer is satisfied. 
Safety lockouts will also generate a 24 volt signal to the "X" 
terminal, allowing notification to the user via the thermostat 
fault light (if present). These safety lockouts shall include:

• High refrigerant pressure.

• Low refrigerant pressure (low refrigerant pressure shall be 

bypassed for the first 90 seconds of operation to eliminate 
nuisance trips).

• Compressor motor protection to automatically shutdown 

the unit in the event of motor overcurrent or excessive tem-
perature conditions. Unit shall automatically restart after 
the line break protector cools.

• Low ambient operation down to 45°F (7°C) without a low 

ambient kit. (Operation down to 0°F with the optional low 
ambient kit.)

VII. Electrical 

a.

Units shall be ______ volts, 3 phase, with a single power 
point connection.

b.

Unit control circuit shall have a 24 volt transformer, sized 
sufficiently to operate the indoor fan.

c.

All condenser fan motors and the secondary of each   
transformer shall be grounded.

Summary of Contents for H5CE090

Page 1: ...ranty A complete line of Evaporator Blower units is also offered to meet your precise capacity and air handling requirements Refer to Form 036 21300 001 for more information on this air side equipment...

Page 2: ...ATA 3 4 ELECTRICAL DATA 4 5 UNIT COOLING CAPACITIES AND POWER REQUIREMENTS 4 6 SYSTEM COOLING CAPACITIES AND POWER REQUIREMENTS 5 7 NOMINAL EVAPORATOR DATA FOR G2FD090S35 W HCE090 10 H 4 C E 2 5 9 A P...

Page 3: ...own to 0 F These units can operate at a maximum ambient temperature of 120 F providing the wet bulb temperature of the air entering the evaporator coil does not exceed 67 F Note Refer to Form 035 1540...

Page 4: ...LING CAPACITIES AND POWER REQUIREMENTS Model HCE Suction Press Corresponding Temp Saturation Temperature of Air on Condenser Coil F 65 75 85 95 105 115 PSIG F MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW...

Page 5: ...69 43 133 12 4 94 68 42 129 13 6 93 67 41 67 126 11 1 112 93 67 40 120 12 3 109 91 64 38 114 13 4 105 88 62 36 62 113 10 7 113 111 84 58 109 12 0 109 108 82 55 106 13 2 106 106 79 53 57 113 10 7 113 1...

Page 6: ...ockout The system controller SC has a lockout cir cuit to prevent compressor short cycling on a safety control with automatic reset If the high or low refrigerant pressure switches HP or LP open the S...

Page 7: ...stat 2HT04701424 if the blower unit is equipped with a 2 stage electric heat accessory Use thermostat 2TH07701024 if the blower unit is equipped with a hot water coil a steam coil or a 1 stage electri...

Page 8: ...ts Group FIELD INSTALLED ACCESSORIES 0 FLOW AMBIENT KITS An auto transformer and tempera ture control maintain stable system operation by reducing the speed of the condenser fan motor FIGURE 3 TYPICAL...

Page 9: ...16 1 2 AIR OUT AIR IN 4 25 3 4 10 1 8 2 1 2 4 1 2 GUAGE LINE ACCESS 1 1 8 OD SUCTION LINE 1 2 OD LIQUID LINE COMPRESSOR AND CONDENSER FAN MOTOR ACCESS 7 8 KNOCKOUT ACCESSORY WIRING ENTRY 1 3 8 DIA PO...

Page 10: ...036 21083 007 A 0404 10 Unitary Products Group TABLE 7 NOMINAL EVAPORATOR DATA FOR G2FD090S35 W HCE090...

Page 11: ...phase motor loads across the 3 phase power supply thus minimizing phase imbal ance on multiple unit installations c Fan motors shall be totally enclosed with permanently lubricated ball bearings for l...

Page 12: ...a Head Pressure Control Shall include an auto trans former to slow the speed of the condenser fan at low ambient temperatures allowing operation of the con densing unit down to 0 F b Coil Guard Field...

Reviews: