036-21137-003 Rev. A (1102)

                            

6

Unitary Products Group

- = Not applicable.

COOLING CAPACITY - With Air Handler Coils

UNIT MODEL

AIR HANDLER

COIL

1

MODEL

COOLING

MODEL

ELECTRIC

2

HEAT KW

W

RATED 

CFM

NET MBH

SEER

W/O TXV

SEER

WITH TXV

3

EER

TOTAL

SENS.

1 PH 12 SEER AC WITH N1AH / G2FD

H2RC018S06

N1AHB0806

2,5,8,10

17

G2FD024(S,H)17

600

19.6

13.2

12.50

12.50

11.60

H2RC024S06

N1AHB0806

2,5,8,10

17

G2FD024(S,H)17

750

23.6

16.9

12.00

12.00

11.00

N1AHB0806

2,5,8,10

17

G2FD030(S,H)17

750

24.0

17.3

12.00

12.00

11.10

H2RC030S06

N1AHB1206

2,5,8,10

17

G2FD030(S,H)17

1000

30.0

21.3

12.00

12.00

11.00

N1AHB1206

2,5,8,10

17

G2FD036(S,H)17

1000

30.6

21.8

12.25

12.25

11.20

H2RC036S06

N1AHB1206

5,8,10,15,19

17

G2FD036(S,H)17

1200

33.8

23.6

11.50

11.50

10.70

N1AHB1206

5,8,10,15,19

17

G2FD046(S,H)17

1200

35.0

24.4

12.00

12.00

10.90

H2RC042S06

N1AHC1606

5,8,10,15,20

21

G2FD042(S,H)21

1400

41.0

29.3

12.00

-

10.50

N1AHC1606

5,8,10,15,20

21

G2FD048(S,H)24

1400

42.5

30.6

12.00

-

10.75

H2RC048S06

N1AHC1606

5,8,10,15,20

21

G2FD048(S,H)24

1575

46.5

36.0

12.20

12.20

10.90

N1AHD2006

8,10,15,20,25,30

24

G2FD060(S,H)24

1575

48.0

36.4

12.50

12.50

11.10

N1AHD2006

8,10,15,20,25,30

24

G2FD061H24

1575

48.5

34.5

12.50

12.50

11.20

H3RC060S06

N1AHD2006

8,10,15,20,25,30

24

G2FD060(S,H)24

1800

57.5

42.6

-

12.00

10.40

N1AHD2006

8,10,15,20,25,30

24

G2FD061H24

1850

58.0

43.2

-

12.00

10.45

3 PH 12 SEER AC WITH N1AH / G2FD

H1RC036S(25,46)

N1AHB1246

5,8,10,15,18

17

G2FD036(S,H)17

1255

33.6

24.9

--

12.00

10.65

N1AHB1246

5,8,10,15,18

17

G2FD046(S,H)17

1250

34.8

25.8

--

12.00

10.95

N1AHC1646

5,8,10,15,18

21

G2FD048(S,H)21

1600

45.5

33.7

--

12.20

11.20

H1RC048S(25,46)

N1AHD2046

8,10,15,20,25,30

24

G2FD060(S,H)24

1620

47.0

34.8

--

12.50

11.45

N1AHD2046

8,10,15,20,25,30

24

G2FD061H24

1600

47.5

35.2

--

12.50

11.50

H1RC060S(25,46)

N1AHD2046

8,10,15,20,25,30

24

G2FD060(S,H)24

1800

57.5

42.6

--

12.00

10.40

N1AHD2046

8,10,15,20,25,30

24

G2FD061H24

1850

58.0

43.2

--

12.00

10.45

1 PH 12 SEER / N1VS - VARIABLE SPEED

H2RC018S06

N1VSB12

10,15,18

17

G2FD024(S,H)17

650

20.2

13.2

13.75

13.75

12.80

H2RC024S06

N1VSB12

10,15,18

17

G2FD024(S,H)17

725

24.2

16.9

13.35

13.35

12.15

N1VSB12

10,15,18

17

G2FD036(S,H)17

775

25.2

17.8

13.50

13.50

12.50

H2RC030S06

N1VSB12

10,15,18

17

G2FD036(S,H)17

1000

31.0

21.9

13.25

13.25

12.15

N1VSB12

10,15,18

17

G2FD046(S,H)17

1000

32.0

22.3

13.75

13.75

12.55

N1VSB12

10,15,18

17

G2FD046(S,H)17

1000

32.0

22.3

13.75

13.75

12.55

H2RC036S06

N1VSB12

10,15,18

17

G2FD036(S,H)17

1200

34.8

23.6

12.40

12.40

11.35

N1VSB12

10,15,18

17

G2FD046(S,H)17

1210

35.8

24.4

13.00

13.00

11.65

N1VSC16

10,15,18

21

G2FD048(S,H)21

1155

36.8

25.1

13.40

13.40

12.20

H2RC042S06

N1VSC16

10,15,18

21

G2FD048(S,H)21

1400

43.0

30.6

13.00

-

11.55

N1VSC16

10,15,18

21

G2FD048(S,H)21

1590

47.0

30.6

12.80

-

11.40

H2RC048S06

N1VSC16

10,15,18

21

G2FD048(S,H)21

1590

47.0

34.9

12.80

12.80

11.40

N1VSD20

10,15,18,30

24

G2FD060(S,H)24

1560

48.5

36.0

13.25

13.25

11.75

N1VSD20

10,15,18,30

24

G2FD061H24

1560

49.0

36.4

13.30

13.30

11.90

H3RC060S06

N1VSD20

10,15,18,30

24

G2FD060(S,H)24

1780

57.5

42.6

-

12.25

10.65

N1VSD20

10,15,18,30

24

G2FD061H24

1780

58.0

43.2

-

12.40

10.80

1 PH 12 SEER AC / F2RP / RC / FC

4

,

5

H2RC018S06

F2RC/F2FC024

5,8,10

18

-

600

20.0

13.2

12.50

12.50

11.70

F2RP/F2FP024

5,8,10

18

-

600

20.0

13.2

12.50

12.50

11.70

H2RC024S06

F2RC/F2FC024

5,8,10

18

-

750

23.4

17.5

11.50

11.50

10.85

F2RC/F2FC030

5,8,10,15

18

-

750

23.4

17.5

11.50

11.50

10.85

F2RP/F2FP024

5,8,10

18

-

750

23.6

17.5

12.00

12.00

10.90

F2RP/F2FP030

5,8,10,15

18

-

750

24.0

17.9

12.00

12.00

11.10

H2RC030S06

F2RC/F2FC030

5,8,10,15

18

-

1000

29.8

21.5

12.00

12.00

11.00

F2RC/F2FC036

5,8,10,15

21

-

1000

31.0

22.4

12.25

12.25

11.30

F2RP/F2FP030

5,8,10,15

18

-

1000

30.2

22.9

12.00

12.00

11.15

F2RP/F2FP036

5,8,10,15,19

21

-

1000

30.2

23.5

12.00

12.00

11.15

H2RC036S06

F2RC/F2FC036

5,8,10,15

21

-

1200

34.6

26.2

12.00

12.00

10.85

F2RP/F2FP036

5,8,10,15,19

21

-

1200

34.6

26.2

12.00

12.00

10.85

F2RP/F2FP042

5,8,10,15

21

-

1200

34.8

26.3

11.60

11.60

10.70

F2FP048

5,8,10,15,20,25

24

-

1200

35.4

26.7

12.00

12.00

10.90

H2RC042S06

F2RP/F2FP042

5,8,10,15

21

-

1400

40.5

28.9

11.80

-

10.35

F2FP048

5,8,10,15,20,25

24

-

1400

42.5

30.5

12.00

-

10.55

H2RC048S06

F2FP048

5,8,10,15,20,25

24

-

1565

46.5

34.9

11.40

11.40

10.75

F2FP060

5,8,10,15,20,25

24

-

1575

48.0

35.9

11.50

11.50

10.70

F2FV060

8,10,15,20,25

24

-

1560

48.5

35.9

13.20

13.20

11.70

H3RC060S06

F2FP060

5,8,10,15,20,25

24

-

1600

56.5

37.5

-

12.00

10.25

F2FV060

8,10,15,20,25

24

-

1780

57.5

42.6

-

12.30

10.60

Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210. 
Cooling MBH based on 8

0

°F entering air temperature, 50% RH, and rated air flow.

EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at a 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power 
input in watt-hours during the same period.

1. G2FD coils available with a factory installed horizontal drain pan. See price pages for specific model number.

2. Single phase units require single phase 2HK heaters. Three phase units require three phase 2HK heaters.

3. TXV = Thermal Expansion Valve kit required. Use 1TV700 series kit.
4. To meet R=4.2 insulation requirements, substitute F2FP for F2RP, and F2FC for F2RC

models. All ratings remain the same.

5. FG8, FG9, and FL8 furnaces and F2RP / F2RC air handlers have B.O.D (Blower on Delay) standard.

Summary of Contents for H*RC018 THRU 060

Page 1: ...is is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protects the compressor if undesirable operating condi tions occur A liquid line filter dr...

Page 2: ...ed indoor coil and 15 feet of refrigerant tubing For tubing lengths other than 15 feet add or sub tract the amount of refrigerant using the difference in length multiplied by the per foot value PHYSIC...

Page 3: ...2 12 702 0 703 0 G2FD048S H 21 24 84 73 16 78 10 87 11 702 16 702 10 703 11 G2FD060S H 24 90 87 15 703 15 703 20 G2FD061H24 90 87 19 703 19 703 25 G1HD024 59 53 5 59 4 701 5 701 4 G1HD036 69 59 13 63...

Page 4: ...F048SOF 78 78 21 87 6 702 21 703 6 G1NF060SOF 87 87 18 703 18 703 0 F2RP024N06 61 53 4 59 4 701 4 701 4 F2RP030N06 65 59 6 63 4 701 6 701 4 F2RP036N06 75 63 4 73 8 701 4 702 8 F2RP042N06 78 73 13 78 0...

Page 5: ...changed verify the evaporator nameplate has been marked with the correct orifice size Additional R 22 Charge Orifice Size for Various Matched Systems 3 Phase Outdoor Unit H1RC036S H1RC048S H1RC060S U...

Page 6: ...18 21 G2FD048 S H 21 1400 43 0 30 6 13 00 11 55 N1VSC16 10 15 18 21 G2FD048 S H 21 1590 47 0 30 6 12 80 11 40 H2RC048S06 N1VSC16 10 15 18 21 G2FD048 S H 21 1590 47 0 34 9 12 80 12 80 11 40 N1VSD20 10...

Page 7: ...11 00 17 G1FA048S17 1000 31 2 22 3 12 50 12 50 11 45 21 G1FA048S21 1000 31 2 22 3 12 50 12 50 11 35 G1HD036 1000 30 8 21 9 12 75 12 75 11 25 17 G1NA030S17K 1000 30 2 21 4 12 00 12 00 11 05 21 G1NA030S...

Page 8: ...1FA048S21 1575 46 5 34 9 12 00 12 00 11 00 21 24 G1FA060S21 24 1575 48 0 36 0 12 50 12 50 11 10 G1HD048 1575 46 0 34 5 12 00 12 00 10 80 G1HD060 1575 47 5 35 6 12 40 12 40 11 05 21 G1NA048S21D 1575 46...

Page 9: ...0 11 15 P1DUB16V G2FD036 S H 17 17 1200 34 4 24 2 12 25 11 40 P1DUC20V G1FA036S21 21 1200 33 6 23 6 12 00 11 30 P1DUC20V G2FD036 S H 21 21 1200 34 8 24 4 13 00 11 60 P1XDB12V G2FD036 S H 17 17 1130 34...

Page 10: ...s for specific model number 2 TXV Use 1TV700 Series Kit 3 Variable speed furnaces have B O D Blower on Delay standard COOLING PERFORMANCE MODEL SUCT T P COMPR AIR TEMP ON CONDENSER MODEL SUCT T P COMP...

Page 11: ...Stage only manual mechanical thermostat Add sub base for 1H 1C 1H 1C manual change over electronic non programmable thermostat 1H 1C auto manual changeover electronic programmable deluxe 7 day thermo...

Page 12: ...30 1 60 CONTACTOR TERMINALS COIL GND LUG C Y R G W Y R G W POWER WIRING CONTROL WIRING FACTORY WIRING 24 VOLT CONTROL WIRING MINIMUM 18 GA WIRE NEC CLASS 2 FURNACE OR AIR HANDLER TERMINAL BLOCK ROOM T...

Page 13: ...14 2 13 6 KW 1 47 1 45 1 43 1 48 1 47 1 45 1 49 1 48 1 46 105 T C 18 1 16 3 14 2 18 7 17 1 15 0 19 4 17 8 15 8 S C 11 3 10 6 9 7 13 0 12 2 11 3 14 7 13 8 12 9 KW 1 58 1 55 1 52 1 59 1 57 2 53 1 61 1 5...

Page 14: ...6 2 07 2 02 1 98 2 09 2 04 2 00 115 T C 21 3 18 6 16 2 22 0 19 5 17 0 22 8 20 5 17 7 S C 14 0 12 9 12 0 16 3 15 3 14 2 18 6 17 8 16 4 KW 2 19 2 13 2 08 2 22 2 16 2 10 2 25 2 18 2 12 125 T C 19 8 16 4...

Page 15: ...3 19 5 KW 2 70 2 61 2 55 2 74 2 64 2 57 2 77 2 68 2 59 125 T C 24 0 20 4 17 0 26 7 21 7 16 8 29 4 23 2 16 7 S C 17 1 15 6 14 1 20 2 17 9 16 0 23 3 20 5 17 8 KW 2 88 2 76 2 70 2 94 2 79 2 70 3 00 2 84...

Page 16: ...2 22 6 28 4 25 5 22 9 S C 21 4 20 0 19 0 23 8 22 3 21 1 26 2 24 6 23 2 KW 3 36 3 29 3 19 3 38 3 31 3 23 3 39 3 33 3 26 NOTE ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH 10...

Page 17: ...33 4 30 8 27 2 33 6 31 3 27 7 S C 23 7 22 5 20 7 24 5 23 6 21 9 25 4 24 6 23 0 KW 4 01 3 88 3 75 4 02 3 91 3 77 4 03 3 93 3 78 125 T C 31 0 27 6 23 5 31 1 28 1 24 1 31 3 28 5 24 4 S C 23 1 21 3 19 6 2...

Page 18: ...37 4 43 9 41 5 38 1 44 2 42 0 38 9 S C 28 4 27 6 25 9 30 0 29 7 28 2 31 6 31 8 30 5 KW 3 39 3 38 3 36 3 39 3 38 3 36 3 40 3 39 3 37 115 T C 41 2 38 1 34 1 41 6 38 7 34 9 42 0 39 3 35 7 S C 27 8 26 7...

Page 19: ...2 6 41 9 37 2 33 1 S C 30 5 28 3 26 3 33 1 30 5 28 4 35 7 32 8 30 5 KW 4 28 4 15 4 02 4 32 4 17 4 05 4 35 4 19 4 08 125 T C 36 3 31 3 28 5 36 9 31 9 28 8 37 6 32 5 29 1 S C 29 2 26 8 24 8 31 8 28 9 26...

Page 20: ...6 2 42 5 39 3 36 2 S C 30 5 30 6 29 5 30 9 32 6 32 8 31 5 32 8 34 1 34 2 32 7 34 5 KW 4 67 4 45 4 25 4 03 4 72 4 49 4 30 4 09 4 74 7 53 4 34 4 18 115 T C 41 8 38 3 35 3 31 7 42 3 38 8 35 8 33 0 42 5 3...

Page 21: ...38 8 43 1 42 6 41 6 KW 5 24 5 10 5 06 5 25 5 11 5 07 5 26 5 12 5 08 105 T C 58 1 54 6 50 0 58 9 55 7 51 3 59 7 56 8 52 7 S C 36 9 36 0 34 4 39 8 39 0 37 3 42 7 41 9 40 2 KW 5 86 5 72 5 63 5 87 5 74 5...

Page 22: ...LOW HORIZONTAL AND DOWNFLOW Available with factory installed horizontal drain pan ADD ON COILS FOR FURNACE APPLICATIONS G1NA UNCASED UPFLOW G1FA FULL CASED UPFLOW AIR HANDLERS FOR NON FURNACE APPLICAT...

Page 23: ...036 21137 003 Rev A 1102 Unitary Products Group 23 NOTES...

Page 24: ...nge without notice Printed in U S A 036 21137 003 Rev A 1102 Copyright by York International Corp 2002 All rights reserved Supersedes 036 21137 002 Rev C 0602 Unitary 5005 Norman Products York OK Grou...

Reviews: