background image

550.38-N1Y

Unitary Products Group

3

® 

LOCATION

Before starting the installation, select and check the suitability
of the location for both the indoor and outdoor unit. Observe
all limitations and clearance requirements.

The outdoor unit must have sufficient clearance for air
entrance to the condenser coil, for air discharge and for ser-
vice access. See Figure  1.

If the unit is to be installed on a hot sun exposed roof or a
black-topped ground area, the unit should be raised suffi-
ciently above the roof or ground to avoid taking the accumu-
lated layer of hot air into the outdoor unit.

Provide an adequate structural support.

GROUND INSTALLATION

The unit may be installed at ground level on a solid base that
will not shift or settle, causing strain on the refrigerant lines
and possible leaks. Maintain the clearances shown in Figure

1 and install the unit in a level position. Isolate the base from

the structure to avoid noise or vibration transmission.

Isolate the unit from rain gutters to avoid any possible wash
out of the foundation.

Normal operating sound levels may be objectionable if the
unit is placed directly under windows of certain rooms (bed-
rooms, study, etc.).

ROOF INSTALLATION

When installing units on a roof, the structure must be capable
of supporting the total weight of the unit, including a pad, lin-
tels, rails, etc., which should be used to minimize the trans-
mission of sound or vibration into the conditioned space.

UNIT PLACEMENT

1.

Provide a base in the pre-determined location.

2.

Remove the shipping carton and inspect for possible
damage.

3.

Compressor tie-down bolts should remain tightened.

4.

Position the unit on the base provided.

5.

Sit unit on the (4) rubber elevating grommets if provided.
Use grommet kit 1SG0601 if not provided. These should
be positioned as shown in Figure  2 to reduce noise and
allow for proper drainage.

6.

Make a hole(s) in the structure wall large enough to
accommodate the insulated vapor line, the liquid line and
the wiring.

 FIGURE 1:  TYPICAL INSTALLATION

THERMOSTAT

TO
BLOWER
MOTOR
RELAY

TO POWER 
SUPPLY

NEC CLASS 1 
WIRING

NEC CLASS 2 
WIRING

TO 
COIL

NOTE: ALL OUTDOOR WIRING 
MUST BE WEATHERPROOF

SEAL OPENING(S) WITH PERMAGUM OR EQUIVALENT

24” SERVICE
ACCESS CLEARANCE 
REQUIRED

WEATHERPROOF 
DISCONNECT 
SWITCH

48” OVERHEAD 
CLEARANCE 
REQUIRED

12” REAR
AND SIDES
CLEARANCE
REQUIRED

Sit unit on
rubber
elevator
grommets
to reduce
noise and
allow for
proper
drainage.

Summary of Contents for H*DB012 - 76

Page 1: ...8 FIELD CONNECTIONS POWER WIRING 8 FIELD CONNECTIONS CONTROL WIRING 8 SYSTEM CHARGE 8 MEASUREMENT METHOD 9 SUPERHEAT CHARGING METHOD 9 SYSTEM START UP 9 ENERGIZE CRANKCASE HEATER 9 SYSTEM CONTROLLER H...

Page 2: ...ler or furnace and other accessories Read all instructions before installing the unit Installer should pay particular attention to the words NOTE CAUTION and WARNING NOTES are intended to clarify or m...

Page 3: ...t is placed directly under windows of certain rooms bed rooms study etc ROOF INSTALLATION When installing units on a roof the structure must be capable of supporting the total weight of the unit inclu...

Page 4: ...ates from entering the coil If the orifice cannot be replaced and the coil resealed within 2 minutes then it should be temporarily closed to air using masking tape short term delay or plugging cap pin...

Page 5: ...rtical bulb installations the bulb should be positioned with the bulb tail at the top so that the bulb acts as a reservoir c Bulb should be insulated using thermal insulation provided to protect it fr...

Page 6: ...be taken to prevent heat damage to angle valve by wrapping a wet rag around it as shown in Fig ure 6 Also protect all painted surfaces and insulation during brazing After brazing cool joint with wet...

Page 7: ...unger cap and with an allen wrench back out counter clockwise until valve stem just touches retaining ring Release the refrigerant charge into the system See PRECAUTIONS DURING BRAZING ANGLE VALVE on...

Page 8: ...cal box cover 3 All field wiring to be in accordance with national electrical codes NEC and or local city codes NOTE A Start Assist Kit is available and recommended for long line set applications or i...

Page 9: ...er and the outdoor dry bulb DB temperature using a thermometer 3 Measure and record the suction pressure at the suction service valve port 4 Using Table 1 on page 12 note the superheat value cor respo...

Page 10: ...S T B E W E A T H E R P R O O F 2 4 V O L T C O N T R O L W I R I N G M i n i m u m 1 8 G A W i r e N E C C l a s s 2 GROUND LUG C Y R G W W G R Y C O N T A C T O R T E R M I N A L S F U R N A C E O...

Page 11: ...6 0 R E D G R O U N D S C R E W A L L F I E L D W I R I N G T O B E I N A C C O R D A N C E W I T H N A T I O N A L E L E C T R I C A L C O D E N E C A N D O R L O C A L C O D E S L 1 L 2 L 3 A L L O...

Page 12: ...1 63 63 67 69 71 73 75 77 76 0 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 79 2 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 82 4 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81...

Page 13: ...t the migration of refrigerant to the compressor during the OFF cycle The heater is energized only when the unit is not running If the main switch is disconnected for long periods of shut down do not...

Page 14: ...550 38 N1Y 14 Unitary Products Group NOTES...

Page 15: ...550 38 N1Y Unitary Products Group 15 NOTES...

Page 16: ...nditioning Unitary Products Group 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright by Unitary Products Group 1999 All rights reserved Supersedes 550 38...

Reviews: