by johnson controls
12
Technical specifications
Model
EUKC
Sizes
12
18
24
36
42
60
Capacities
Cooling
kW
3.5
5.0
7.0
10.0
12.0
16.0
Heating
kW
3.6
5.7
8.0
11.0
14.0
18.5
Power Supply
V.ph.Hz
230.1.50
230.1.50
380.3.50
380.3.50
Consumption
Cooling / Heating
kW
1.2 / 1.1
2.1 / 1.8
2.7 / 2.5
4.0 / 3.5
5.3 / 4.9
6.5 / 5.5
Nominal flow
m
3
/h
600
840
1 400
2 000
2 000
2 500
Available pressure
Pa
25
40
80
150
150
150
Noise level (1 m.)
dB (A)
36 / 38 / 40
38 / 40 / 42
40 / 42 / 44
46 / 48 / 50
46 / 48 / 50
48 / 50 / 53
Dimensions (Height / Width / Depth)
mm
220 / 913 / 680 266 / 1 012 / 736 268 / 1 270 / 504 290 / 1 251 / 744 290 / 1 251 / 744 330 / 1 251 / 788
Nett Weight
kg
27
36
37
57
57
66
Tubing
Gas diameter
1/2"
1/2"
5/8"
3/4”
3/4”
3/4”
Liquid diameter
1/4"
1/4"
3/8"
1/2”
1/2”
1/2”
Maximum tubing length
m
20
20
30
50
50
50
Maximum elevation tubing
m
15
15
15
30
30
30
Nominal cooling capacity is based on: Indoor air temp. = 27°C DB/19°C WB. Outdoor air temp. = 35°C DB, 5-meter tubing.
Nominal heating capacity is based on : Indoor air temp. = 21°C DB - Outdoor air temp. = 7°C DB/6°C WB, 5-meter tubing.
GB
ATTENTION
Your product is marked with this symbol. This means that at the end of its service life it should not be mixed
with other non-classified household waste. Therefore, disposal should be carried out in compliance with the
corresponding local and national regulations, in a correct and environment-friendly manner.
The dismantling of the air conditioning unit, as well as the processing of refrigerant, oil and other components,
should be carried out by a qualified technician and in compliance with the applicable legislation.
Contact your local authorities for further information