![background image](http://html1.mh-extra.com/html/york/enjc-09/enjc-09_installation-instructions-manual_3824632019.webp)
by johnson controls
19
GB
Technical specifications
Model
ENJC-D-R
Outdoor unit
09
12
18
24
30
36
42
48
60
Capacities
Cooling *
kW
2.7
(1.2 - 3.0)
3.5
(1.6 - 3.6)
5.3
(1.6 - 5.8)
7.0
(2.0 - 7.7)
8.2
(2.7 - 8.3)
10.3
(3.5 - 11.5)
11.0
(3.5 - 13.0)
14.0
(4.9 - 14.1)
17.0
(4.0 - 17.5)
Heating *
kW
2.9
(1.0 - 3.0)
3.8
(1.6 - 4.0)
6.2
(1.4 - 6.5)
7.5
(2.4 - 8.0)
8.8
(2.0 - 9.3)
11.5
(3.8 - 12.8)
12.4
(3.8 - 14.5)
16.5
(5.3 - 18.3)
18.0
(5.0 - 18.8)
Compressor
Rotary
Refrigerant
R-410A
Expansion/location
Capillary/outdoor unit
Power supply
V.ph.Hz
230.1.50
230.1.50
380.3.50
380.3.50
Consumption *
Cooling / Heating
kW
0.83 / 0.80 1.07 / 0.97 1.65 / 1.70 2.19 / 2.08 2.56 / 2.44 3.20 / 3.06 3.42 / 3.43 4.36 / 4.50 5.30 / 5.00
Outdoor noise level (1 m.)
dB (A)
53
54
57
59
59
61
61
61
63
Outer dia. condensed water drain pipe
mm
16.5
Nett Weight
kg
28
30
48
65
68
86
90
122
127
Type of connection
Nut
Tubing
Gas diameter
3/8”
3/8”
1/2"
5/8"
5/8"
5/8"
5/8"
5/8"
3/4”
Liquid diameter
1/4"
1/4"
1/4"
3/8"
3/8"
3/8"
3/8"
3/8"
3/8”
Maximum tubing length
m
20
20
20
30
30
30
50
50
50
Maximum elevation tubing
m
15
15
15
15
15
15
30
30
30
Refrigerant load
g
1 200
1 350
1 400
2 400
2 600
3 500
3 800
4 300
5 500
Nominal cooling capacity is based on: Indoor air temp. = 27°C DB/19°C WB. Outdoor air temp. = 35°C DB, 5-meter tubing.
Nominal heating capacity is based on : Indoor air temp. = 21°C DB - Outdoor air temp. = 7°C DB/6°C WB, 5-meter tubing.
* Data for duct indoor unit type
ATTENTION
Your product is marked with this symbol. This means that at the end of its service life it should not be mixed
with other non-classified household waste. Therefore, disposal should be carried out in compliance with the
corresponding local and national regulations, in a correct and environment-friendly manner.
The dismantling of the air conditioning unit, as well as the processing of refrigerant, oil and other components,
should be carried out by a qualified technician and in compliance with the applicable legislation.
Contact your local authorities for further information
All data and dimensions are subject to change without prior notice.