background image

036-21540-001-A-0503

6

Unitary Products Group

Floor mounted units should be secured on a solid, level
pad or sturdy stand. The base of the unit should be
approximately 6 inches higher than the lower edge of
the wall opening. This height will allow the condenser
air ducts to be pitched away from the unit, offering pro-
tection from rain water entering the base pan (refer to
typical installation diagram on Page #4). The use of an
isolating rubber sheet is recommended to reduce vibra-
tion and noise transmission. Ensure that the entire
base is continuously supported - do not support unit at
corner points only! Unit may be pitched slightly to
ensure efficient drainage of condensate.

EVAPORATOR / CONDENSER SEPARATION

 - (All

models except 20 and 25 Ton)

Reclaim the entire refrigerant charge from each 
compressor circuit.

Disconnect the evaporator motor high voltage 
wires at contactor/overload "C4/OL4". Pull all wir-
ing into the evaporator compartment. Remove 
bushing/clamp from routing hole for evaporator 
motor wiring.

Cut and remove sections of all liquid and suction 
refrigerant lines. Make two cuts in each line, 
approximately 6 inches above and below the evap-
orator floor/condenser roof. Use a tubing cutter 

only

 

- do not use a hacksaw to cut refrigerant tub-

ing!

Remove the corner securing brackets from the out-
side corners of the cabinet, at the joint line 
between the evaporator and condenser sections.

Remove the evaporator section.

ASSEMBLY OF SPLIT UNITS

 - (All models)

Place the condensing section in the required loca-
tion.

Carefully position the evaporator section atop the 
condensing section. Align all sides, the evaporator 
motor wire routing hole, and the refrigerant line 
routing holes.

Install the securing brackets at all four corners, on 
the evaporator/condenser separation joint. Note 
that one bracket, intended for use at the corner 
with the drain fitting, has a short "leg".

Use appropriate tubing couplings and splice previ-
ously cut refrigerant lines. (

On 20 and 25 Ton mod-

els, remove spun end caps with a tubing cutter - 
after releasing nitrogen pressure at shraeder fit-
tings. Short tubing sections and couplings are 
shipped with unit to connect refrigerant circuits

).

Pressure test refrigerant circuits with dry nitrogen   
(300 psig ).

Evacuate each circuit to at least 350 microns. If 
gauge pressure rises above 500 microns in one 
minute, evacuation is incomplete or the system has 
a leak.

Charge circuit(s) to the value indicated on the unit 
nameplate.

Install bushing/clamp into evaporator wiring routing 
hole, and pull wires through into electrical control 
panel. Connect motor leads to load terminals on 
contactor/overload relay "C4/OL4".

Ensure evaporator motor rotation is correct upon 
unit start-up. Switch any two wires at contactor 
"C4" if blower rotation is not correct.

Summary of Contents for EMBASSY Series

Page 1: ...ADJUSTMENT 17 LOW AMBIENT DAMPER INSTALLATION 18 START UP AND OPERATION 19 MAINTENANCE SERVICE 20 See the following page for a complete Table of Contents NOTES CAUTIONS AND WARNINGS The installer shou...

Page 2: ...T CIRCUIT S 20 LIST OF FIGURES Fig Pg 1 DSK TYPICAL APPLICATIONS 4 2 3 4 5 TON UNITS DIMENSIONAL DATA CORNER WEIGHTS 7 3 8 10 TON UNITS DIMENSIONAL DATA CORNER WEIGHTS 8 4 12 15 TON UNITS DIMENSIONAL...

Page 3: ...duce vibration and noise while operating Each refrigerant circuit is equipped with high pressure and low pressure switches An electrically re settable lockout relay will shut off the compressor in the...

Page 4: ...036 21540 001 A 0503 4 Unitary Products Group FIGURE 1 DSK TYPICAL APPLICATIONS...

Page 5: ...urrounding areas should be taken when choosing a location to install the unit Common vibration and sound levels associated with commercial equipment may be objectionable to people or equip ment Refer...

Page 6: ...brackets from the out side corners of the cabinet at the joint line between the evaporator and condenser sections Remove the evaporator section ASSEMBLY OF SPLIT UNITS All models Place the condensing...

Page 7: ...036 21540 001 A 0503 Unitary Products Group 7 FIGURE 2 3 4 5 TON UNITS DIMENSIONAL DATA CORNER WEIGHTS...

Page 8: ...036 21540 001 A 0503 8 Unitary Products Group FIGURE 3 8 10 TON UNITS DIMENSIONAL DATA CORNER WEIGHTS...

Page 9: ...036 21540 001 A 0503 Unitary Products Group 9 FIGURE 4 12 15 TON UNITS DIMENSIONAL DATA CORNER WEIGHTS...

Page 10: ...036 21540 001 A 0503 10 Unitary Products Group FIGURE 5 20 TON UNIT DIMENSIONAL DATA CORNER WEIGHTS...

Page 11: ...036 21540 001 A 0503 Unitary Products Group 11 FIGURE 6 25 TON UNIT DIMENSIONAL DATA CORNER WEIGHTS...

Page 12: ...ute Size condenser air discharge for 1 200 1 500 feet minute nominal velocity Maximum recommended 1 700 feet minute The use of louvers with higher velocities than above may be employed at the discreti...

Page 13: ...ting panel Do not remove fasteners securing blowers to panel The blowers are to remain attached to the mounting panel at all times Carefully remove the blower panel assembly from the evaporator cabine...

Page 14: ...ned to be read Provide individual power disconnects for each unit or each section in the case of split applications Install a secure ground to both evaporator and condenser If canvas flexible joints a...

Page 15: ...230 1 60 1 17 9 88 0 0 50 4 4 1 00 7 4 34 18 50 208 230 3 60 1 11 4 77 0 0 50 2 1 1 00 3 1 19 45 30 460 3 60 1 5 7 39 0 0 50 1 0 1 00 1 4 9 53 15 575 3 60 1 4 7 31 0 0 50 0 8 1 00 1 1 7 79 15 4 TON 20...

Page 16: ...6 870 2 41 920 2 70 970 2 90 1010 3 20 1050 3 46 1100 3 70 1145 3 90 1180 4 30 15 TON 6000 824 2 52 873 2 77 920 3 03 967 3 30 1010 3 58 1052 3 90 1097 4 24 1137 4 59 1178 4 95 1220 5 33 6600 903 3 33...

Page 17: ...1VP44 X 7 8 6 7 AK69H 4L370 1 15 TON 848 1064 5 184 87 5 4 7 5 9 1VP60 X 1 1 8 9 7 BK100H B40 1 20 TON 848 1064 5 184 87 5 4 7 5 9 1VP60 X 1 1 8 9 7 BK100H B50 1 25 TON 902 1082 7 1 2 213 88 5 5 0 6 0...

Page 18: ...ighten the flare nuts securely NOTE On dual and triple compressor units the actuator MUST be connected to the 1 circuit liquid line fit ting Connection to the second or third stage refrig erant circui...

Page 19: ...re is no negative impacts on durability caused by operating three phase Scroll compressors in the reversed direction for a short period of time less than one hour However after several minutes of oper...

Page 20: ...ing screw is properly set Check that the blower wheel is tight on the shaft and that the hub setscrews are properly torqued DRIVE BELTS Examine belts periodically for wear Glazed areas on the drive su...

Reviews: