background image

036-21540-001-A-0503

18

Unitary Products Group

LOW AMBIENT DAMPER INSTALLATION

If unit operation is required at outdoor ambient below
60

°

F, the optional Low Ambient Damper kit should be

installed to maintain acceptable condensing pressure.

The damper is installed directly onto the discharge duct
connection as illustrated. The damper is controlled via
a refrigerant pressure actuator. Two different actuator
mounting arrangements are used, depending on the
size of the damper. Appropriate mounting hardware for
the actuator is provided with each kit. The pressure
actuator is connected to the liquid line access fitting
through a 1/4 in. copper tube. Attach the tubing using
flare nuts at each end. A routing hole is provided in the
condenser corner panel near the actuator mounting
position. Purge the 1/4-in. sensing line by loosening the
flare nut at the actuator until liquid refrigerant is
observed leaking from the fitting. Tighten the flare nuts
securely.

NOTE:

On dual and triple compressor units, the actuator
MUST be connected to the #1 circuit liquid line fit-
ting. Connection to the second or third stage refrig-
erant circuit will result in system malfunction.

A solid-state timer(s) is provided with the damper kit.
The timer will bypass the low-pressure switch during
compressor start-up. The time delay allows the con-
densing pressure to rise sufficiently for refrigerant flow
through the evaporator to be established. The 8-25 ton
units require a timer to be installed on each compres-
sor circuit.

Mount the timer(s) in the condenser electrical panel.
Mounting holes are provided near the lockout relays
(R1, R2). Connect the timers into the compressor con-
trol circuit as shown. The wire splice between the LPC
and HPC switches is accessible inside the electrical
panel, in the low voltage section of the enclosure.

Test run the unit, and confirm proper operation. The
damper should be fully closed when condensing pres-
sure is below 165 psig, and should be fully open at con-
densing pressures of 250 psig and above.

  

 FIGURE 9 - LOW AMBIENT DAMPER INSTALLATION

Summary of Contents for EMBASSY Series

Page 1: ...ADJUSTMENT 17 LOW AMBIENT DAMPER INSTALLATION 18 START UP AND OPERATION 19 MAINTENANCE SERVICE 20 See the following page for a complete Table of Contents NOTES CAUTIONS AND WARNINGS The installer shou...

Page 2: ...T CIRCUIT S 20 LIST OF FIGURES Fig Pg 1 DSK TYPICAL APPLICATIONS 4 2 3 4 5 TON UNITS DIMENSIONAL DATA CORNER WEIGHTS 7 3 8 10 TON UNITS DIMENSIONAL DATA CORNER WEIGHTS 8 4 12 15 TON UNITS DIMENSIONAL...

Page 3: ...duce vibration and noise while operating Each refrigerant circuit is equipped with high pressure and low pressure switches An electrically re settable lockout relay will shut off the compressor in the...

Page 4: ...036 21540 001 A 0503 4 Unitary Products Group FIGURE 1 DSK TYPICAL APPLICATIONS...

Page 5: ...urrounding areas should be taken when choosing a location to install the unit Common vibration and sound levels associated with commercial equipment may be objectionable to people or equip ment Refer...

Page 6: ...brackets from the out side corners of the cabinet at the joint line between the evaporator and condenser sections Remove the evaporator section ASSEMBLY OF SPLIT UNITS All models Place the condensing...

Page 7: ...036 21540 001 A 0503 Unitary Products Group 7 FIGURE 2 3 4 5 TON UNITS DIMENSIONAL DATA CORNER WEIGHTS...

Page 8: ...036 21540 001 A 0503 8 Unitary Products Group FIGURE 3 8 10 TON UNITS DIMENSIONAL DATA CORNER WEIGHTS...

Page 9: ...036 21540 001 A 0503 Unitary Products Group 9 FIGURE 4 12 15 TON UNITS DIMENSIONAL DATA CORNER WEIGHTS...

Page 10: ...036 21540 001 A 0503 10 Unitary Products Group FIGURE 5 20 TON UNIT DIMENSIONAL DATA CORNER WEIGHTS...

Page 11: ...036 21540 001 A 0503 Unitary Products Group 11 FIGURE 6 25 TON UNIT DIMENSIONAL DATA CORNER WEIGHTS...

Page 12: ...ute Size condenser air discharge for 1 200 1 500 feet minute nominal velocity Maximum recommended 1 700 feet minute The use of louvers with higher velocities than above may be employed at the discreti...

Page 13: ...ting panel Do not remove fasteners securing blowers to panel The blowers are to remain attached to the mounting panel at all times Carefully remove the blower panel assembly from the evaporator cabine...

Page 14: ...ned to be read Provide individual power disconnects for each unit or each section in the case of split applications Install a secure ground to both evaporator and condenser If canvas flexible joints a...

Page 15: ...230 1 60 1 17 9 88 0 0 50 4 4 1 00 7 4 34 18 50 208 230 3 60 1 11 4 77 0 0 50 2 1 1 00 3 1 19 45 30 460 3 60 1 5 7 39 0 0 50 1 0 1 00 1 4 9 53 15 575 3 60 1 4 7 31 0 0 50 0 8 1 00 1 1 7 79 15 4 TON 20...

Page 16: ...6 870 2 41 920 2 70 970 2 90 1010 3 20 1050 3 46 1100 3 70 1145 3 90 1180 4 30 15 TON 6000 824 2 52 873 2 77 920 3 03 967 3 30 1010 3 58 1052 3 90 1097 4 24 1137 4 59 1178 4 95 1220 5 33 6600 903 3 33...

Page 17: ...1VP44 X 7 8 6 7 AK69H 4L370 1 15 TON 848 1064 5 184 87 5 4 7 5 9 1VP60 X 1 1 8 9 7 BK100H B40 1 20 TON 848 1064 5 184 87 5 4 7 5 9 1VP60 X 1 1 8 9 7 BK100H B50 1 25 TON 902 1082 7 1 2 213 88 5 5 0 6 0...

Page 18: ...ighten the flare nuts securely NOTE On dual and triple compressor units the actuator MUST be connected to the 1 circuit liquid line fit ting Connection to the second or third stage refrig erant circui...

Page 19: ...re is no negative impacts on durability caused by operating three phase Scroll compressors in the reversed direction for a short period of time less than one hour However after several minutes of oper...

Page 20: ...ing screw is properly set Check that the blower wheel is tight on the shaft and that the hub setscrews are properly torqued DRIVE BELTS Examine belts periodically for wear Glazed areas on the drive su...

Reviews: