![York E*BD-(T Technical Manual Download Page 13](http://html1.mh-extra.com/html/york/e-bd-t/e-bd-t_technical-manual_4200839013.webp)
246819-BTG-H-0208
Unitary Products Group
13
CP equals MBH output divided by (total KW input x 3.412).
HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by
the total electric power input during the same period.
— = Not Applicable.
1 PH 13 SEER HP WITH AV - VARIABLE SPEED
EABD-F018S
AV24
–
17.6
3.86
1.33
10.1
2.42
1.21
8.40
EABD-F024S
AV24
–
22.2
3.68
1.77
12.4
2.46
1.49
8.40
EABD-F030S
AV36
–
30.0
3.90
2.27
15.5
2.34
1.94
8.25
EABD-F036S
AV36
–
35.4
4.10
2.52
21.8
2.96
2.14
9.30
EABD-F042S
AV/SV48
–
41.0
3.72
3.27
24.2
2.64
2.71
8.75
EABD-F048S
AV/SV48
–
47.0
3.60
3.87
29.0
2.40
3.56
8.20
EABD-F060S
AV/SV60
–
57.0
3.58
4.71
34.8
2.36
4.30
8.15
1 & 3 PH HP SEER AC WITH AHP / F*FP / F*FV
EABD-F018S
AHP18
–
18.0
3.66
1.43
10.5
2.30
1.32
8.00
F*FP024
–
17.9
3.66
1.43
10.4
2.30
1.32
8.00
EABD-F024S
AHP24
–
23.0
3.44
1.96
13.1
2.30
1.67
8.00
F*FP030
–
23.0
3.44
1.96
13.1
2.30
1.67
8.00
EABD-F030S
AHP30
–
29.6
3.66
2.48
16.1
2.22
2.14
8.00
F*FP040
–
30.0
3.66
2.48
16.2
2.22
2.14
8.00
EABD-(T,W)030S
AHP30
–
28.6
3.66
2.28
15.6
3.66
1.24
8.00
F*FP040
–
29.0
3.66
2.32
15.7
3.66
1.25
8.00
EABD-F036S
AHP36
–
33.6
3.44
2.91
22.4
2.50
2.37
8.50
AHP42
–
34.4
3.44
2.93
20.4
2.50
2.39
8.40
F*FP040
–
34.2
3.44
2.91
20.2
2.50
2.37
8.00
F*FP042
–
34.2
3.44
2.91
20.2
2.50
2.37
8.00
EABD-(T,W)036S
AHP36
–
33.0
3.66
2.64
22.0
3.66
1.76
8.00
AHP42
–
34.0
3.66
2.72
20.2
3.66
1.61
8.00
F*FP040
–
34.0
3.66
2.72
20.1
3.66
1.60
8.00
F*FP042
–
34.0
3.66
2.72
20.1
3.66
1.60
8.00
EABD-F042S
AHP48
–
42.0
3.56
3.46
25.0
2.52
2.93
8.40
EABD-(T,W)042S
AHP48
–
41.0
3.66
3.28
24.4
3.66
1.95
8.00
EABD-F048S
F*FV060
–
47.5
3.60
3.87
29.2
2.40
3.56
8.30
AHP48
–
48.0
3.44
4.09
29.6
2.30
3.82
8.00
AHP60
–
48.0
3.44
4.09
29.6
2.30
3.82
8.10
EABD-(T,W)048S
F*FV060
–
46.5
3.66
3.72
28.6
3.66
2.28
8.00
AHP48
–
47.0
3.66
3.76
29.0
3.66
2.32
8.00
AHP60
–
47.0
3.66
3.76
29.0
3.66
2.32
8.00
EABD-F060S
F*FV060
–
57.5
3.56
4.73
34.6
2.34
4.33
8.15
AHP60
–
58.0
3.46
4.91
35.0
2.28
4.52
8.00
EABD-(T,W)060S
F*FV060
–
56.5
3.66
4.52
34.0
3.66
2.72
8.00
AHP60
–
57.0
3.66
4.56
34.4
3.66
2.75
8.00
1. Rated CFM same as for cooling.
2. Heating MBH based on ARI standards of 70° DB entering indoor air, 72% RH outdoor air with 25 feet of interconnecting piping and
no supplemental electric heat operation.
HEATING PERFORMANCE - With Air Handler (Continued)
UNIT
MODEL*
AIR
HANDLER
COIL
1
MODEL
ARI HEATING
2
47
°
F
17
°
F
HSPF
MBH
COP
KW
MBH
COP
KW
STD