SPLIT-SYSTEM HEAT PUMPS

13 SEER – R-22

MODELS:
E*BD-F018 THRU 060
(1.5 THRU 5 NOMINAL TONS, 1 PHASE)

E*BD-(T,W)036 THRU 060
(2.5 THRU 5 NOMINAL TONS, 3 PHASE)

Due to continuous product improvement, specifications 
are subject to change without notice.

Visit us on the web at www.york.com

Additional rating information can be found at 
www.ahridirectory.org

LISTED

ISO 9001

Certified Quality

Management System

TECHNICAL
GUIDE 

TECHNICAL
GUIDE 

DESCRIPTION

The 13 SEER series heat pumps are designed for use with a 
variety of UPG evaporator sections to suit any application 
need. A full line of matching Add-On Coils are available for 
use with upflow, downflow or horizontal furnaces. Matching 
Air Handlers are also available for upflow, downflow or hori-
zontal installation to provide a complete system. Electric heat 
may be installed in air handlers. All units are factory charged 
to assure easy installation.

WARRANTY

Single Phase Units:

5-year limited parts warranty.

5-

year limited compressor warranty.

Three Phase Units:

1-year limited parts warranty.

5-

year limited compressor warranty.

FEATURES

DURABLE CONSTRUCTION - 

The outdoor unit is con-

structed of pre-painted steel that offers tough protection
against corrosion and resists fading when exposed to sun-
light. Drain holes are incorporated into the base pan to per-
mit free drainage of moisture.

QUALITY COILS - 

The coil is constructed of enhanced

copper tube and aluminum fins.

COIL PROTECTION -

 Coils are protected from damage by

a polymer mesh applied between the coil face, and a PVC
coated steel coil guard.

PROTECTED COMPRESSOR - 

The hermetic compressor

is internally protected against high pressure and tempera-
ture by the simultaneous operation of a high pressure relief
valve and temperature sensors which stop the compressor
if operating temperatures go too high. Both protectors
reset automatically. A discharge line solid core filter drier
further protects the compressor.

Complete System Control – 

These heat pumps utilize

the unique microprocessor defrost control system to pro-
vide optimal comfort and to monitor the overall system for
reliable operation. The defrost control system continuously
monitors the space environment to maintain optimum effi-
ciency. It initiates defrost only when necessary to further
reduce heating costs and improve reliability. In the event
improper operating conditions occur, the control will auto-
matically shut the system down to extend the life of the
heat pump. Rapid cycling is prevented by use of an inter-
nal anti-recycle timer.

LOW OPERATING SOUND LEVEL - 

The compressor is

mounted on rubber isolators to reduce operating sounds.
The slow moving condenser fan keeps air turbulence and
sound to a low level.

EASY ACCESS - 

Removable panel affords accessibility to

the electrical box.

FULLY CHARGED AND FACTORY WIRED - 

to simply

installation and reduce labor costs. Only power supply and
control wiring and refrigerant lines must be connected. All
models are sweat connect with reusable service valves.

Factory tested 

- to verify system operation and control

functioning before shipment.

U.L. and C.U.L. 

listed - approved for outdoor application.

Certified in accordance with the Unitary Small Equipment cer-
tification program, which is based on ARI Standard 210/240.

Summary of Contents for E*BD-(T

Page 1: ...er mesh applied between the coil face and a PVC coated steel coil guard PROTECTED COMPRESSOR The hermetic compressor is internally protected against high pressure and tempera ture by the simultaneous...

Page 2: ...0 Rows Deep 1 1 1 1 1 2 2 Fin Inches 22 22 22 22 22 18 18 Liquid Line Set OD Field Installed 3 8 3 8 3 8 3 8 3 8 3 8 3 8 Vapor Line Set OD Field Installed 3 4 3 4 7 8 7 8 7 8 7 8 1 1 8 Unit Charge Lbs...

Page 3: ...2B2C 0 9 FC MC PC UC42C2C 0 9 FC MC PC UC48C2C 9 14 FC MC PC UC48D2C 9 14 FC PC UC60C2C 7 7 FC MC PC UC60D2C 7 7 MC61D2C 7 7 HC18A2A 0 HC30A2A 0 HC36B2A 0 HC42C2C 9 HC60C2C 7 7 HD24A2A 0 HD36B2A 0 9 H...

Page 4: ...porator nameplate has been marked with the correct orifice TXV size HD24A3X 0 HD36B3X 0 9 HD48C3X 14 HD60D3X 7 7 AHP18B3X 0 AHP24B3X 0 AHP30B3X 0 AHP36C3X 9 AHP42C3X 9 AHP SHP48D3X 14 7 AHP SHP60D3X 7...

Page 5: ...Coil Face Area Sq Ft 20 96 23 58 23 58 24 00 27 00 20 96 23 58 23 58 24 00 27 00 Rows Deep 1 1 1 2 2 1 1 1 2 2 Fin Inches 22 22 22 18 18 22 22 22 18 18 Liquid Line Set OD Field Installed 3 8 3 8 3 8 3...

Page 6: ...W 042S EABD T W 048S EABD T W 060S Required TXV 1TVM2A1 1TVM2A1 1TVM2C1 1TVM2C1 1TVM2C1 Factory Charge lbs oz 8 9 8 7 8 7 12 8 16 9 Indoor Coil1 Additional Charge Oz FC MC PC UC35B2C 0 9 FC MC PC UC35...

Page 7: ...21 FC MC60D 1600 46 0 35 4 13 00 11 00 MA20D 24 MC61D 1600 46 0 35 5 13 00 11 00 EABD T W 048S MA16C 21 FC60C 1600 45 0 34 6 13 00 11 00 MA20D 21 FC MC60D 1600 45 0 34 6 13 00 11 00 MA20D 24 MC61D 160...

Page 8: ...11 00 AHP42 21 1200 34 0 24 8 13 00 11 00 EABD F042S AHP SHP48 24 1400 41 0 30 7 13 00 11 00 EABD T W 042S AHP SHP48 24 1400 40 0 29 9 13 00 11 00 EABD F048S F FV060 24 1600 46 0 34 6 13 50 11 00 AHP...

Page 9: ...ABD T W 036S 1000 1400 17 21 FC MC PC35 1200 34 0 24 8 13 00 11 00 17 21 FC MC PC UC42 1200 34 0 24 8 13 00 11 00 21 24 FC MC PC UC48 1200 34 4 25 1 13 00 11 00 21 HC42 1140 33 8 24 0 13 00 11 00 HD36...

Page 10: ...14 00 12 00 F L L8VC16 FC MC PC42C 21 1000 29 0 20 3 14 00 12 00 FL9 C V C16 FC MC PC42C 21 1000 29 0 20 4 14 00 12 00 F L L8VB16 HC36 17 1000 29 0 20 4 14 00 12 00 FL9 C V B12 HC36 17 1000 29 0 20 4...

Page 11: ...C V D20 FC MC PC60D 24 1620 54 5 38 6 13 25 11 00 F L L8VC20 FC PC60C 21 1730 54 5 38 6 13 25 11 00 FL9 C V C20 FC PC60C 21 1620 54 0 39 6 13 10 11 00 FL9 C V D20 HC60 24 1620 54 5 38 9 13 25 11 00 F...

Page 12: ...02 29 6 2 34 3 71 8 00 MA20D MC61D 48 0 3 50 4 02 29 6 2 34 3 71 8 00 EABD T W 048S MA16C FC60C 47 0 3 66 3 76 29 0 3 66 2 32 8 00 MA20D FC MC60D 47 0 3 66 3 76 29 0 3 66 2 32 8 00 MA20D MC61D 47 0 3...

Page 13: ...2 32 15 7 3 66 1 25 8 00 EABD F036S AHP36 33 6 3 44 2 91 22 4 2 50 2 37 8 50 AHP42 34 4 3 44 2 93 20 4 2 50 2 39 8 40 F FP040 34 2 3 44 2 91 20 2 2 50 2 37 8 00 F FP042 34 2 3 44 2 91 20 2 2 50 2 37 8...

Page 14: ...35 8 3 86 2 72 22 4 2 78 2 36 9 00 HD36 36 0 3 86 2 73 22 4 2 78 2 36 9 00 EABD T W 036S FC MC PC35 34 0 3 66 2 72 20 2 3 66 1 61 8 00 FC MC PC UC 42 34 0 3 66 2 72 20 2 3 66 1 61 8 00 FC MC PC UC 48...

Page 15: ...FL9 C V C16 FC MC PC42C 29 6 3 82 2 33 15 8 2 30 1 99 8 10 F L L8VB16 HC36 29 6 3 86 2 23 15 6 2 30 1 91 8 20 F L L8VC16 HC36 29 6 3 88 2 28 15 8 2 34 1 94 8 10 F L L8VC16 HD36 29 6 3 88 2 28 15 6 2...

Page 16: ...5 8 20 FL9 C V C16 FC PC60C 47 0 3 50 3 93 29 6 2 34 3 71 8 15 FL9 C V C20 FC PC60C 47 5 3 52 3 95 29 6 2 36 3 67 8 20 FL9 C V C20 HC60 47 5 3 52 3 95 29 4 2 36 3 67 8 20 F L L8VC20 HD60 47 5 3 54 3 9...

Page 17: ...ation refer to the price book or consult factory SOUND POWER RATINGS Rated in accordance with ARI 270 95 Standards INSTALLATION CLEARANCES TYPICAL FIELD WIRING UNIT MODEL dBA Cooling Heating 018 73 72...

Page 18: ...1 2 1 3 1 3 1 3 1 3 1 3 1 3 1 3 1 3 1 3 1 3 1 3 1 3 1 3 1 4 95 T C 14 8 16 0 15 8 17 9 20 4 16 3 17 1 16 8 19 1 21 2 17 9 18 3 17 7 20 3 21 9 S C 14 2 12 9 10 9 11 1 9 3 15 8 15 1 12 7 12 9 10 4 17 5...

Page 19: ...C 17 9 17 1 13 9 14 3 11 8 19 9 19 7 16 2 16 8 13 5 21 8 22 2 18 6 19 2 15 1 K W 1 7 1 7 1 7 1 8 1 8 1 8 1 7 1 8 1 8 1 8 1 8 1 8 1 8 1 8 1 8 105 T C 16 9 16 8 17 6 17 4 22 5 18 7 19 5 19 2 20 1 23 2...

Page 20: ...24 0 25 0 19 1 K W 2 3 2 3 2 3 2 4 2 4 2 3 2 3 2 3 2 4 2 4 2 4 2 4 2 4 2 4 2 5 105 T C 22 5 23 6 22 9 26 2 29 8 24 1 24 6 23 8 26 8 30 1 25 7 25 5 24 6 27 3 30 3 S C 22 4 22 1 18 6 18 9 15 4 24 0 24 2...

Page 21: ...7 2 7 2 8 2 7 2 7 2 7 2 7 2 8 2 7 2 7 2 7 2 8 2 8 115 T C 27 7 28 0 27 9 30 7 34 2 28 9 28 9 28 6 31 3 35 0 30 1 29 8 29 3 32 0 35 8 S C 26 8 26 6 22 6 22 4 17 7 28 1 28 4 24 9 24 7 19 2 29 4 30 2 27...

Page 22: ...8 2 9 3 0 95 T C 34 2 37 2 36 0 40 0 42 2 35 9 38 9 36 8 41 0 42 0 37 6 40 5 37 6 41 6 41 8 S C 34 2 33 8 28 0 28 3 23 0 35 9 36 3 30 3 30 8 24 6 37 6 38 8 32 6 33 0 26 3 K W 3 0 3 1 3 0 3 1 3 2 3 1 3...

Page 23: ...3 48 2 S C 38 9 38 4 32 2 32 5 25 4 40 4 39 9 34 4 35 4 26 8 41 9 41 4 36 6 37 2 28 1 K W 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 4 3 4 3 3 3 3 3 3 3 3 3 3 105 T C 40 5 40 2 37 6 42 1 45 0 42 6 41 8 38 2 4...

Page 24: ...47 3 48 9 54 0 58 7 47 4 48 2 50 0 55 0 59 8 49 6 49 1 51 1 55 9 60 9 S C 45 3 45 2 38 6 38 3 29 9 47 4 48 2 41 6 41 1 31 6 49 6 49 1 44 6 43 9 33 2 K W 4 1 4 1 4 1 4 2 4 2 4 1 4 1 4 1 4 2 4 2 4 1 4 2...

Page 25: ...13 4 1 3 2 9 14 1 1 3 3 1 14 8 1 3 3 3 30 60 13 2 1 2 3 2 13 8 1 2 3 4 14 3 1 2 3 6 70 12 1 1 2 2 9 12 7 1 2 3 1 13 4 1 2 3 3 80 10 9 1 3 2 5 11 7 1 2 2 8 12 5 1 2 3 0 17 60 9 6 1 1 2 5 10 0 1 1 2 6...

Page 26: ...6 11 7 1 2 2 8 16 6 1 6 3 0 17 60 13 3 1 5 2 6 10 0 1 1 2 6 15 3 1 4 3 1 70 11 4 1 5 2 2 9 0 1 1 2 3 13 0 1 5 2 6 80 9 5 1 6 1 8 8 0 1 2 2 0 10 8 1 5 2 0 10 60 12 0 1 5 2 4 8 9 1 1 2 3 11 8 1 4 2 5 7...

Page 27: ...0 70 15 1 1 8 2 5 15 6 1 8 2 6 16 1 1 8 2 7 80 13 2 1 9 2 0 14 0 1 9 2 2 14 7 1 9 2 3 10 60 14 9 1 7 2 5 14 9 1 7 2 6 14 9 1 7 2 6 70 12 9 1 8 2 1 13 2 1 8 2 2 13 4 1 8 2 2 80 10 9 1 8 1 8 11 4 1 8 1...

Page 28: ...2 7 NOTE ALL CAPACITIES ARE NET KBTUH WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH 1000 CFM For three phase decrease T C by 1 0 and S C by 0 7 Air Handler Coil T C S C KW MA12B FC MC35B 0 96 1...

Page 29: ...3 3 33 4 2 5 3 3 33 3 2 4 3 3 70 31 0 2 6 3 0 31 7 2 6 3 0 32 3 2 5 3 0 80 28 6 2 7 2 7 30 0 2 7 2 8 31 3 2 7 2 8 17 60 27 1 2 3 2 9 27 4 2 3 2 9 27 7 2 3 2 9 70 25 2 2 4 2 6 25 0 2 4 2 6 26 4 2 4 2...

Page 30: ...2 8 35 1 3 6 2 9 35 3 3 5 3 0 17 60 30 2 2 8 3 1 30 1 2 7 3 3 30 1 2 7 3 3 70 29 8 4 0 2 2 29 8 3 7 2 3 29 8 2 2 2 9 80 29 7 3 8 2 0 29 5 3 8 2 1 29 4 2 0 2 5 10 60 27 3 2 8 2 9 27 0 2 7 2 9 26 6 2 6...

Page 31: ...3 4 2 8 70 43 9 4 2 2 7 43 3 4 1 2 7 42 8 3 9 2 7 80 43 4 4 8 2 4 44 6 4 6 2 5 45 8 4 5 2 6 17 60 37 4 3 5 2 7 36 2 3 5 2 6 35 0 3 4 2 5 70 34 9 3 9 2 3 35 0 3 8 2 3 36 2 3 8 2 3 80 32 4 4 3 1 9 34 9...

Page 32: ...o change without notice Printed in U S A 246819 BTG H 0208 Copyright by Unitary Products Group 2008 All rights reserved Supersedes 246819 BTG G 0607 Unitary 5005 Norman Product York OK Group Drive 730...

Reviews: