![background image](http://html2.mh-extra.com/html/york/dnh018/dnh018_technical-manual_3989435012.webp)
036-21233-002-A-0903
12
Unitary Products Group
TABLE 7: DNH042 COOLING CAPACITIES - 3-1/2 TON
TEMPERATURE
OF AIR ON
CONDENSER COIL
AIR ON EVAPORATOR COIL
1,050 CFM
1,225 CFM
1,400 CFM
1,575 CFM
1,750 CFM
WB °F
WB °F
WB °F
WB °F
WB °F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
85 °F
NET CAP.
MBH
38.6
38.4
34.0
33.3
42.1
41.8
37.0
36.3
45.5
45.3
40.1
39.2
45.3
45.0
39.9
39.1
45.1
44.8
39.7
38.9
TOTAL POWER
INPUT kW
4.05
3.83
3.95
3.91
4.01
3.79
3.92
3.87
3.98
3.76
3.88
3.84
4.12
3.90
4.02
3.98
4.27
4.03
4.16
4.12
Se
n
s
ib
le
Ca
p
a
city
MB
H
1
E
n
ter
ing D
ry
Bu
lb
°
F
86
25.5
32.6
34.0
33.3
28.9
36.8
37.0
36.3
32.2
41.0
40.1
39.2
34.4
42.9
39.9
39.1
36.6
44.8
39.7
38.9
83
22.5
29.6
34.0
33.3
25.4
33.3
37.0
36.3
28.2
36.9
40.1
39.2
29.8
38.9
39.9
39.1
31.4
40.9
39.7
38.9
80
19.6
26.6
31.9
31.9
21.8
29.7
35.6
35.6
24.1
32.8
39.3
39.2
25.1
34.3
39.5
39.1
26.2
35.7
39.7
38.9
77
16.6
23.6
28.9
28.9
18.3
26.2
32.1
32.0
20.0
28.7
35.2
35.2
20.5
29.6
34.8
34.4
21.0
30.5
34.5
33.6
74
13.6
20.7
25.9
25.9
14.7
22.7
28.5
28.5
15.9
24.7
31.1
31.1
15.8
25.0
30.2
29.8
15.8
25.3
29.2
28.4
71
-
17.7
22.9
22.9
-
19.1
25.0
24.9
-
20.6
27.1
27.0
-
20.3
25.5
25.1
-
20.1
24.0
23.2
68
-
14.7
19.9
19.9
-
15.6
21.5
21.4
-
16.5
23.0
22.9
-
15.7
20.9
20.5
-
14.9
18.8
18.0
105 °F
NET CAP.
MBH
36.8
36.2
32.1
31.6
40.2
39.5
35.1
34.5
43.6
42.9
38.1
37.5
43.4
42.7
37.9
37.3
43.3
42.6
37.8
37.2
TOTAL POWER
INPUT kW
4.45
4.20
4.29
4.28
4.41
4.17
4.25
4.24
4.37
4.13
4.21
4.20
4.51
4.26
4.34
4.33
4.65
4.39
4.48
4.46
S
e
nsi
b
le
C
apaci
ty
MB
H
1
En
te
ri
n
g
Dr
y
Bu
lb
°
F
86
25.5
32.1
32.1
31.6
28.9
36.2
35.1
34.5
32.2
40.4
38.1
37.5
34.6
41.5
37.9
37.3
36.9
42.6
37.8
37.2
83
22.5
29.1
32.1
31.6
25.3
32.7
35.1
34.5
28.1
36.3
38.1
37.5
29.9
38.5
37.9
37.3
31.7
40.7
37.8
37.2
80
19.5
26.1
30.6
30.4
21.8
29.2
34.2
33.9
24.1
32.2
37.8
37.5
25.3
33.8
37.8
37.3
26.5
35.4
37.8
37.2
77
16.5
23.1
27.7
27.4
18.3
25.6
30.7
30.4
20.0
28.1
33.7
33.4
20.6
29.2
33.1
32.7
21.3
30.2
32.6
32.0
74
13.5
20.1
24.7
24.4
14.7
22.1
27.1
26.8
15.9
24.0
29.6
29.3
16.0
24.5
28.5
28.0
16.1
25.0
27.4
26.8
71
-
17.1
21.7
21.4
-
18.5
23.6
23.3
-
19.9
25.5
25.2
-
19.9
23.8
23.4
-
19.8
22.2
21.6
68
-
14.1
18.7
18.4
-
15.0
20.1
19.8
-
15.9
21.5
21.1
-
15.2
19.2
18.7
-
14.6
16.9
16.3
115 °F
NET CAP.
MBH
35.4
33.7
29.9
29.5
38.7
36.8
32.7
32.2
42.1
40.0
35.5
35.0
41.8
39.7
35.2
34.8
41.4
39.4
35.0
34.5
TOTAL POWER
INPUT kW
4.80
4.64
4.73
4.72
4.78
4.62
4.71
4.70
4.75
4.59
4.68
4.67
4.88
4.71
4.80
4.80
5.00
4.83
4.93
4.92
S
e
n
s
ib
le
C
apaci
ty
MB
H
1
E
n
te
ring
Dry
Bu
lb
°
F
86
24.8
31.0
29.9
29.5
28.2
34.9
32.7
32.2
31.6
38.7
35.5
35.0
34.0
39.1
36.2
34.8
36.3
39.4
35.0
34.5
83
21.8
28.0
29.9
29.5
24.7
31.6
32.7
32.2
27.5
35.3
35.5
35.0
29.3
36.8
35.2
34.8
31.1
38.4
35.0
34.5
80
18.8
25.0
28.4
28.1
21.1
28.1
31.9
31.6
23.5
31.2
35.4
35.0
24.7
32.8
35.2
34.8
25.9
34.4
35.0
34.5
77
15.8
22.0
25.4
25.1
17.6
24.6
28.3
28.0
19.4
27.1
31.3
30.9
20.0
28.2
30.5
30.1
20.7
29.2
29.7
29.3
74
12.8
19.0
22.4
22.1
14.1
21.0
24.8
24.5
15.3
23.0
27.2
26.9
15.4
23.5
25.9
25.5
15.5
24.0
24.5
24.1
71
-
16.0
19.4
19.1
-
17.5
21.3
21.0
-
18.9
23.1
22.8
-
18.9
21.2
20.8
-
18.8
19.3
18.8
68
-
13.1
16.4
16.1
-
14.0
17.7
17.4
-
14.9
19.0
18.7
-
14.2
16.6
16.2
-
13.6
14.1
13.6
125 °F
NET CAP.
MBH
34.0
31.1
27.6
27.3
37.3
34.1
30.3
30.0
40.6
37.1
32.9
32.6
40.1
36.6
32.5
32.2
39.6
36.2
32.1
31.8
TOTAL POWER
INPUT kW
5.16
5.08
5.18
5.17
5.14
5.07
5.16
5.16
5.13
5.05
5.15
5.14
5.24
5.17
5.26
5.26
5.36
5.28
5.38
5.37
Se
n
s
ib
le
Ca
p
a
city
MB
H
1
E
n
ter
ing D
ry
Bu
lb
°
F
86
24.1
29.9
27.6
27.3
27.6
33.5
30.3
30.0
31.0
37.1
32.9
32.6
33.4
36.6
32.5
32.2
35.7
36.2
32.1
31.8
83
21.1
26.9
27.6
27.3
24.0
30.6
30.3
30.0
26.9
34.3
32.9
32.6
28.7
35.2
32.5
32.2
30.5
36.2
32.1
31.8
80
18.1
23.9
26.1
25.9
20.5
27.1
29.5
29.2
22.8
30.2
32.9
32.6
24.1
31.8
32.5
32.2
25.3
33.4
32.1
31.8
77
15.1
21.0
23.1
22.9
17.0
23.5
26.0
25.7
18.8
26.1
28.8
28.5
19.4
27.2
27.9
27.5
20.1
28.2
26.9
26.6
74
12.1
18.0
20.1
19.9
13.4
20.0
22.5
22.2
14.7
22.0
24.8
24.4
14.8
22.5
23.2
22.9
14.9
23.0
21.7
21.3
71
-
15.0
17.2
16.9
-
16.4
18.9
18.6
-
17.9
20.7
20.3
-
17.9
18.6
18.2
-
17.8
16.5
16.1
68
-
12.0
14.2
13.9
-
12.9
15.4
15.1
-
13.8
16.6
16.3
-
13.2
13.9
13.6
-
12.6
11.2
10.9
125 °F
NET CAP.
MBH
32.7
28.6
25.4
25.2
35.9
31.4
27.9
27.7
39.1
34.2
30.4
30.2
38.4
33.6
29.8
29.6
37.7
33.0
29.2
29.1
TOTAL POWER
INPUT kW
5.50
5.50
5.60
5.60
5.50
5.50
5.60
5.60
5.50
5.50
5.60
5.60
5.60
5.60
5.70
5.70
5.70
5.70
5.80
5.80
S
e
nsi
b
le
C
apaci
ty
MB
H
1
En
te
ri
n
g
Dr
y
Bu
lb
°
F
86
23.4
28.9
25.4
25.2
26.9
32.2
27.9
27.7
30.4
35.5
30.4
30.2
32.8
34.2
29.8
29.6
35.2
33.0
29.2
29.1.
83
20.4
25.9
25.4
25.2
23.4
29.6
27.9
27.7
26.3
33.3
30.4
30.2
28.1
33.6
29.8
29.6
29.9
33.9
29.2
29.1
80
17.4
22.9
23.9
23.6
19.8
26.0
27.2
26.9
22.2
29.2
30.5
30.2
23.5
30.8
29.9
29.6
24.7
32.4
29.2
29.1
77
14.4
19.9
20.9
20.6
16.3
22.5
23.7
23.3
18.2
25.1
26.4
26.1
18.8
26.2
25.2
25.0
19.5
27.2
24.0
23.8
74
11.5
16.9
17.9
17.6
12.8
18.9
20.1
19.8
14.1
21.0
22.3
22.0
14.2
21.5
20.6
20.3
14.3
22.0
18.8
18.6
71
-
13.9
14.9
14.6
-
15.4
16.6
16.3
-
16.9
18.3
17.9
-
16.9
15.9
15.7
-
16.8
13.6
13.4
68
-
10.9
11.9
11.6
-
11.9
13.0
12.7
-
12.8
14.2
13.8
-
12.2
11.3
11.0
-
11.6
8.4
8.2
1.
These capacities are net capacities (the indoor fan heat is deducted).
ALL SENSIBLE CAPACITY