![background image](http://html.mh-extra.com/html/york/dnh-030/dnh-030_installation-manual_912469021.webp)
282911-YIM-B-0807
Unitary Products Group
21
TABLE 16: SUPERHEAT CHARGING TABLE FOR DNH048
OUTDOOR
TEMP. °F
SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 1,600 CFM
INDOOR WB TEMP. (°F)
55
57
59
61
63
65
67
69
71
73
75
65
23.8
25.1
26.5
27.8
29.1
30.5
31.8
32.8
3.7
34.7
35.7
70
22.4
23.4
24.4
25.3
26.3
27.3
28.2
29.7
31.1
32.5
33.9
75
21.1
21.7
22.3
22.9
23.5
24.1
24.7
26.6
28.5
30.3
32.2
80
19.7
20.0
20.2
20.4
20.6
20.9
21.1
23.5
25.8
28.2
30.5
85
18.4
18.2
18.1
17.9
17.8
17.7
17.5
20.3
23.2
26.0
28.8
90
13.1
13.0
12.9
12.8
12.7
12.6
12.5
16.6
20.7
24.7
28.8
95
7.9
7.8
7.7
7.6
7.6
7.5
7.4
12.8
18.1
23.5
28.9
100
6.1
6.1
6.1
6.2
6.2
6.3
6.3
11.1
15.9
20.7
25.4
105
-
-
-
-
-
5.0
5.2
9.4
13.6
17.8
22.0
110
-
-
-
-
-
-
-
7.7
11.3
14.9
18.5
115
-
-
-
-
-
-
-
6.0
9.0
12.1
15.1
TABLE 17: SUPERHEAT CHARGING TABLE FOR DNH060
OUTDOOR
TEMP. °F
SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 600 CFM
INDOOR WB TEMP. (°F)
55
57
59
61
63
65
67
69
71
73
75
65
27.7
29.3
30.9
32.5
34.0
35.6
37.2
37.3
37.3
37.4
37.5
70
21.1
23.2
25.2
27.2
29.3
31.3
33.3
34.2
35.1
35.9
36.8
75
14.5
17.0
19.5
22.0
24.5
27.0
29.5
31.1
32.8
34.4
36.0
80
7.9
10.9
13.8
16.8
19.8
22.7
25.7
28.1
30.5
32.9
35.3
85
-
-
8.2
11.6
15.0
18.4
21.8
25.0
28.2
31.4
34.6
90
-
-
6.0
8.6
11.2
13.8
16.3
20.5
24.6
28.8
32.9
95
-
-
-
5.6
7.4
9.1
10.9
16.0
21.1
26.2
31.3
100
-
-
-
-
5.8
7.1
8.4
12.6
16.8
21.0
26.2
105
-
-
-
-
-
5.0
5.9
9.2
12.5
15.8
19.0
110
-
-
-
-
-
-
-
5.8
8.2
10.5
12.9
115
-
-
-
-
-
-
-
-
-
5.3
6.8