background image

036-21502-002-A-0303

10

Unitary Products Group

COIL GUARD - Customers can purchase a coil guard kit 
to protect the condenser coil from damage. This is not a 
hail guard kit.

STAINLESS STEEL HEAT EXCHANGER - For applica-
tions in corrosive environments, this option provides a 
full stainless steel heat exchanger assembly.

PHASE MONITORS - Designed to prevent unit damage. 
The phase monitor will shut the unit down in an out-of-
phase condition.

DIRTY FILTER SWITCH - This kit includes a differential 
pressure switch that energizes the fault light on the unit 
thermostat, indicating that there is an abnormally high 
pressure drop across the filters. Factory installed option 
or field installed accessory.

HINGED FILTER DOOR/“TOOLLESS” BLOWER AND 
ACCESS PANELS 
(not hinged) - This option allows for 
easy access and maintenance.

NOTE: Knobs are shipped inside the unit to prevent ship-

ping damage. These must be field installed for 
tool-less operation.

FIELD-INSTALLED ACCESSORIES

SINGLE INPUT ELECTRONIC ENTHALPY ECONO-
MIZERS
 - Includes a slide-in / plug-in damper assembly 
with fully modulating spring-return motor actuator capa-
ble of introducing up to 100% outdoor air with nominal 
1% leakage type dampers.

The enthalpy system contains one sensor that monitors 
the outdoor air and determines when the air is cool 
enough and dry enough to provide free cooling.

The rainhood is painted to match the basic unit and must 
be field-assembled before installing.

MOTORIZED OUTDOOR AIR INTAKE DAMPER - 
Includes a slide-in / plug-in damper assembly with a 2-
position, spring return motor actuator which opens to 
some pre-set position whenever the supply air blower is 
operating and will drive fully closed when the blower unit 
shuts down.

The rain hood is painted to match the basic unit and 
must be field assembled before installing.

ELECTRIC HEATERS wired for single point power sup-
ply. These nickel chromium heater elements are pro-
vided with limit and automatic reset capability to prevent 
operation at excessive temperatures.

ROOF CURBS - Eight and fourteen-inch high roof curbs 
provide a water-tight seal between the unit and the fin-
ished roof. These full perimeter curbs meet the require-
ments of the National Roofing Contractors Association 
(NRCA) and are shipped knocked-down for field assem-
bly.

Roof curbs are designed to fit inside the base rails of the 
unit and include both a wood nailing strip and duct 
hanger supports.

HIGH ALTITUDE NATURAL GAS - Burner orifices and 
pilot orifices are provided for proper furnace operation at 
altitudes up to 6,000 feet.

PROPANE - Burner orifices, pilot orifices and gas valve 
parts are provided to convert a natural gas furnace to 
propane.

HIGH ALTITUDE PROPANE - Burner orifices and pilot 
orifices are provided for proper furnace operation at alti-
tudes up to 6,000 feet. This accessory supplements the 
basic propane conversion kit.

LOW NOX KIT- Required to reduce the emission of 
nitrogen oxides below 40 nanograms per joule.

POWER EXHAUST - Our single input economizer 
options are available with power exhaust. Whenever the 
outdoor air intake dampers are opened for free cooling, 
the exhaust fan will be energized to prevent the condi-
tioned space from being over-pressurized during econo-
mizer operation.

The power exhaust option can only be used on bot-
tom duct configurations.

BAROMETRIC RELIEF DAMPER - This damper acces-
sory can be used to relieve internal building air pressure 
on units with an economizer without power exhaust. This 
accessory includes a rain hood, a bird screen and a fully 
assembled damper. With bottom duct connections, the 
damper should be mounted over the opening in the 
return air panel. With horizontal ductwork, the accessory 
should be mounted on the return air duct.

ENTHALPY ACCESSORY CONTROL KIT - This kit 
contains the required components to convert a single 
enthalpy economizer to dual enthalpy.

BURGLAR BARS - Mount in the supply and return 
openings to prevent entry into the duct work.

FLUE EXHAUST EXTENSION KIT - In locations with 
wind or weather conditions which may interfere with 
proper exhausting of furnace combustion products, this 
kit can be installed to prevent the flue exhaust from 
entering nearby fresh air intakes.

CO

2

 SENSOR - Senses CO

2

 levels and automatically 

overrides the economizer when levels rise above the 
present limits.

COIL GUARD - Customers can purchase a coil guard kit 
to protect the condenser coil from damage. This is not a 
hail guard kit.

Summary of Contents for DM 048

Page 1: ...roof jack or frame All units include Powder Paint finish that meets ASTM B 117 750 hour salt spray standards Permanently lubricated motors Bottom or side air discharge configuration capability field...

Page 2: ...DRIVE SIDE DUCT APPLICATION 17 10 SUPPLY AIR BLOWER PERFORMANCE 5 TON BELT DRIVE SIDE DUCT APPLICATION 18 11 SUPPLY AIR BLOWER PERFORMANCE 6 TON BELT DRIVE SIDE DUCT APPLICATION 19 12 SUPPLY AIR BLOW...

Page 3: ...Options 2 4 Q Options 2 3 4 R Options 3 4 S Option 5 T Options 1 5 U Options 1 3 5 V Options 1 4 5 W Options 1 3 4 5 X Options 3 5 Y Options 4 5 Z Options 3 4 5 Options 1 Disconnect 2 Non Pwr d Conv...

Page 4: ...ond Coils CP CPC Controller DFS APS Technicoat Evap Cond Coils Phase Monitor CQ CPC Controller DFS APS Technicoat Evap Cond Coils Coil Guard CR CPC Controller DFS APS Technicoat Evap Cond Coils Phase...

Page 5: ...oneywell Excel 10 Controller DFS APS Technicoat Cond Coil Phase Monitor Hinged Filter Door Toolless Access Panels GG Honeywell Excel 10 Controller DFS APS Technicoat Cond Coil Coil Guard Hinged Filter...

Page 6: ...Evap Cond Coils NP Novar ETC 3 Controller DFS APS Technicoat Evap Cond Coils Phase Monitor NQ Novar ETC 3 Controller DFS APS Technicoat Evap Cond Coils Coil Guard NR Novar ETC 3 Controller DFS APS Te...

Page 7: ...er Coil Phase Monitor Dirty Filter Switch Hinged Filter Door Toolless Access Panels UG Technicoat Condenser Coil Coil Guard Dirty Filter Switch Hinged Filter Door Toolless Access Panels UH Technicoat...

Page 8: ...f cooling and heat Safety Monitoring The control board monitors the high and low pressure switches the freezestats the gas valve if applicable and the temperature limit switch on gas heat units The un...

Page 9: ...s that utilizes Technicoat 10 1TM processes Coating is applied by total immersion of the complete coil for maximum protection ELECTRIC HEATERS wired for single point power sup ply These nickel chromiu...

Page 10: ...fin ished roof These full perimeter curbs meet the require ments of the National Roofing Contractors Association NRCA and are shipped knocked down for field assem bly Roof curbs are designed to fit in...

Page 11: ...of knowing the details of each system This constitutes and expectation to any specification or guaran tee requiring a dBA value or sound data in any other form than sound power level ratings 2 At a di...

Page 12: ...34 33 29 25 21 17 13 62 33 3 7 33 33 33 29 25 21 17 31 4 0 31 31 31 27 23 19 15 57 34 3 6 34 34 34 30 26 22 18 32 4 0 32 32 32 28 24 20 16 72 39 3 7 27 24 20 17 14 37 4 1 26 23 20 16 13 67 36 3 6 34...

Page 13: ...45 42 37 32 27 22 17 62 43 4 9 43 43 43 38 33 28 23 40 5 4 40 40 40 35 30 26 21 57 43 4 9 43 43 43 38 33 28 23 40 5 4 40 40 40 35 30 25 20 72 53 5 0 36 32 28 23 19 51 5 5 35 31 26 22 17 67 46 4 9 44 4...

Page 14: ...50 47 42 36 30 24 18 62 48 5 8 48 48 48 42 37 31 25 44 6 4 44 44 44 38 32 26 20 57 46 5 8 46 46 46 40 35 29 23 42 6 4 42 42 42 36 31 25 19 72 60 6 0 42 37 32 26 21 57 6 6 41 36 30 25 20 67 54 5 8 52 4...

Page 15: ...66 61 54 47 40 32 25 62 64 7 0 64 64 64 56 49 42 35 58 7 8 58 58 58 51 43 36 29 57 64 7 0 64 64 64 56 49 42 34 58 7 7 58 58 58 50 43 36 29 72 75 7 1 56 49 43 36 29 76 8 0 55 48 41 34 27 67 70 7 1 68 6...

Page 16: ...RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 1700 1600 1500 1400 1055 875 1300 1036 780 1066 850 1200 1011 735 1047 765 1075 800 1100 987 690 1028 720 1060 750 1084 775 1000...

Page 17: ...RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2000 1103 1270 1900 1085 1210 1800 1064 1145 1102 1180 1700 1040 1075 1081 1115 1121 1140 1600 1020 1005 1060 1050 1100 1085 1500 1003 945...

Page 18: ...RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2500 2400 1193 1665 2300 1170 1580 1202 1620 2200 1148 1480 1180 1530 2100 1121 1385 1155 1425 1190 1475 2000 1100 1285 1133 1340...

Page 19: ...TS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 3200 3000 2800 1245 2190 2600 1193 1920 1222 1990 1250 2060 2400 1142 1675 1173 1730 1205 1800 1234 1885 2200 1090 1380 1124 1450 1155 1550 1186 16...

Page 20: ...800 1644 770 1531 710 0721 HI 2101 1260 2000 1205 1914 1155 1830 1110 0361 0481 0 70 AVAILABLE EXTERNAL STATIC PRESSURE IWG2 0 90 0 80 1 00 0361 0481 0601 AVAILABLE EXTERNAL STATIC PRESSURE IWG2 0601...

Page 21: ...utdoor air than for 100 return air If the resistance of the return air duct system is less than 0 25 IWG the unit will deliver less CFM during full economizer operation 3 Add these resistance values t...

Page 22: ...706 7 5 31 3 45 3 60 2CE04511006 10 6 44 2 61 5 70 2CE04511506 15 9 66 3 89 1 90 2CE04512006 21 2 88 3 116 7 125 NONE 0 0 0 0 25 7 40 2CE045105252 4 0 11 1 25 7 40 2CE04510725 2 5 6 15 5 25 7 40 2CE04...

Page 23: ...40 NONE 0 0 0 0 31 7 50 2CE045105252 4 0 11 1 31 7 50 2CE045107252 5 6 15 5 31 7 50 2CE04511025 8 0 22 2 36 3 50 2CE04511525 11 9 33 0 49 8 50 2CE04512025 15 9 44 1 63 7 70 2CE04513025 22 2 61 6 85 5...

Page 24: ...10706 7 5 31 3 48 6 60 2CE04511006 10 6 44 2 64 7 70 2CE04511506 15 9 66 3 92 3 100 2CE04512006 21 2 88 3 119 9 125 NONE 0 0 0 0 24 1 35 2CE04510525 2 4 0 11 1 24 1 35 2CE045107252 5 6 15 5 25 9 35 2C...

Page 25: ...40 NONE 0 0 0 0 29 9 45 2CE045105252 4 0 11 1 29 9 45 2CE045107252 5 6 15 5 29 9 45 2CE04511025 8 0 22 2 34 0 45 2CE04511525 11 9 33 0 47 5 50 2CE04512025 15 9 44 1 61 4 70 2CE04513025 22 2 61 6 83 3...

Page 26: ...5 31 3 57 8 70 2CE04511006 10 6 44 2 74 0 80 2CE04511506 15 9 66 3 101 6 110 2CE04512006 21 2 88 3 129 2 150 NONE 0 0 0 0 33 9 45 2CE045105252 4 0 11 1 33 9 45 2CE045107252 5 6 15 5 38 2 45 2CE045110...

Page 27: ...NONE 0 0 0 0 41 7 60 2CE045105252 4 0 11 1 41 7 60 2CE045107252 5 6 15 5 41 7 60 2CE04511025 8 0 22 2 48 8 60 2CE04511525 11 9 33 0 62 3 70 2CE04512025 15 9 44 1 76 2 80 2CE04513025 22 2 61 6 98 0 100...

Page 28: ...6 7 5 31 3 61 1 70 2CE04511006 10 6 44 2 77 2 80 2CE04511506 15 9 66 3 104 8 110 2CE04512006 21 2 88 3 132 4 150 NONE 0 0 0 0 34 1 45 2CE04510525 2 4 0 11 1 34 1 45 2CE045107252 5 6 15 5 38 4 45 2CE04...

Page 29: ...NONE 0 0 0 0 39 9 50 2CE045105252 4 0 11 1 39 9 50 2CE045107252 5 6 15 5 39 9 50 2CE04511025 8 0 22 2 46 5 50 2CE04511525 11 9 33 0 60 0 70 2CE04512025 15 9 44 1 73 9 80 2CE04513025 22 2 61 6 95 8 10...

Page 30: ...00 3400 3400 CONDENSER COILS Rows Deep 1 1 1 2 Fins Per Inch 16 16 22 16 Face Area Sq Ft 17 1 17 1 17 1 16 7 COMPRESSOR Qty Per Unit Scroll Type 1 1 1 1 AIR FILTERS Quantity Per Unit 15 X 20 X 1 or 2...

Page 31: ...COND STAGE COOLING OR TO HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO STAGES OF HEAT USE THERMOSTAT 2TH0471024 THERMOSTAT1 TERMINALS UNIT TERMINAL STRIP TB1 24 VOLT TRANSFORMER ADD JUMPER ADD JUMPER 1 ELE...

Page 32: ...036 21502 002 A 0303 32 Unitary Products Group FIGURE 3 UNIT DIMENSIONS 3 6 TON COOLING ONLY ELECTRIC HEAT FRONT VIEW FIGURE 4 UNIT DIMENSIONS 3 6 TON COOLING GAS HEAT FRONT VIEW...

Page 33: ...036 21502 002 A 0303 Unitary Products Group 33 FIGURE 5 UNIT WITH ECONOMIZER RAINHOOD FIGURE 6 UNIT WITH FIXED OUTDOOR AIR MOTORIZED DAMPER RAINHOOD DETAIL A DETAIL B...

Page 34: ...NG ENTRY See Detail B MOUNTING BRACKET FOR DICONNECT SWITCH Shipped attached to the blower housing inside the blower compartment FIELD SUPPLIED DISCONNECT SWITCH LOCATION BLOWER MOTOR ACCESS FILTER AC...

Page 35: ...036 21502 002 A 0303 Unitary Products Group 35 FIGURE 9 TYPICAL APPLICATIONS...

Page 36: ...ION UNIT TOTAL A B C D E F DM036 Cooling Electric 565 84 83 82 104 105 107 DM036N04 625 93 92 91 115 117 118 DM036N08 635 94 93 92 117 119 120 DM048 Cooling Electric 615 91 90 89 113 115 116 DM048N06...

Page 37: ...TON BASIC UNIT DM Cooling Only 565 615 640 720 DM Gas Electric N04 625 N06 675 N08 635 700 775 N10 685 710 785 OPTIONS Economizer 50 Motorized Damper 26 Electric Heater 5 7 kW 18 10 15 kW 23 20 30 kW...

Page 38: ...factory tested prior to shipment All unit wiring shall be both numbered and color coded All units the cooling performance shall be rated in accordance with DOE and ARI test procedures Units shall be C...

Page 39: ...and redun dant main gas valve Venter wheel shall be constructed of stainless steel for corrosion resistance The heat exchanger shall be of the tubular type constructed of T1 40 aluminized steel for c...

Page 40: ...the conditioned space during normal operation Whenever the indoor fan motor is energized the dampers open up to one of two pre selected positions regardless of the outdoor air enthalpy Dampers return...