GUIDE SPECIFICATIONS

GENERAL

Units shall be manufactured by York International Unitary 
Products Group in an ISO 9001 certified facility.

York's Sunline 2000

TM

 units are convertible single package-

units. Although the units are primarily designed for curb 
mounting on a roof, they can also be slab-mounted at ground 
level or set on steel beams above a finished roof. Cooling 
only, cooling with gas heat and cooling with electric heat 
models are available with a wide variety of factory-mounted 
options and field-installed accessories to make them suitable 
for almost every application. All units are self-contained and 
assembled on full perimeter base rails with holes in the four 
corners for overhead rigging. Every unit is completely piped, 
wired, charged and tested at the factory to simplify the field 
installation and to provide years of dependable operation. All 
models (including those with an economizer) are suitable for 
either bottom or horizontal duct connections. Models with 
power exhaust are suitable for bottom duct connections only. 
For bottom duct, remove the sheet metal panels from the 
supply and return air openings through the base of the unit. 
For horizontal duct, remove the supply and return air panels 
on the rear of the unit. 

All non-Scroll compressors include crankcase heaters and all 
compressors have internal pressure relief. Every refrigerant 
circuit includes a liquid line filter-drier, a discharge line high 
pressure switch and a suction line with a freezestat and low 
pressure/loss of charge switch.The unit control circuit 
includes a 75 VA transformer, a 24-volt circuit breaker and a 
relay board with a compressor lockout circuit, a terminal strip 
for thermostat wiring, plus an additional set of pin connectors 
to simplify the interface of additional field controls. All units 
have long lasting powder paint cabinets with 750 hour salt 
spray test approval under ASTMB117 procedures. All models 
are CSA listed. All models include a 1-year limited warranty 
on the complete unit. Compressors and electric heater ele-
ments carry a 5-year warranty. Aluminized steel and Stainless 
steel tubular heat exchangers carry a 10-year warranty.

DESCRIPTION

Units shall be factory-assembled, single packaged, Electric 
Cooling/Gas Heat,  Electric Cooling/Optional Electric Heat 
and designed for outdoor mounted installation.

The 3 thru 5  ton units shall have minimum SEER ratings of 
10.0 and the 6 ton units shall have minimum EER ratings of 
9.0. They shall have built-in field convertible duct connections 
for down discharge supply/return or horizontal discharge sup-
ply/return, and be available with factory installed options or 
field installed accessories. The units shall be factory wired, 
piped, charged with R-22 refrigerant and factory tested prior 
to shipment. All unit wiring shall be both numbered and color 
coded. All units the cooling performance shall be rated in 
accordance with DOE and ARI test procedures. Units shall be 
CSA listed, classified to ANSI Z21.47, UL 1995/CSA No. 236 
standards.

UNIT CABINET

Unit cabinet shall be constructed of G90 galvanized steel, 
with exterior surfaces coated with a non-chalking, powdered 
paint finish, certified at 750 hours salt spray test per 
ASTMB117 standards. Indoor blower section shall be insu-
lated with a minimum 1/2” thick insulation, coated on the air-
side. Aluminum foil faced insulation shall be used in the 
furnace compartment and be fastened with ridged fasteners 
to prevent insulation from entering the air stream. Cabinet 
panels shall be “large” size, easily removable for servicing 
and maintenance. Full perimeter base rails shall be provided 
to assure reliable transit of equipment, overhead rigging and 
proper sealing on roof curb applications. Disposable 1" filters 
shall be furnished and be accessible through a removable 
access door, sealed airtight. Units filter track shall be 
designed to accommodate either 1” or 2” filters. Fan perfor-
mance measuring ports shall be provided on the outside of 
the cabinet to allow accurate air measurements of evaporator 
fan performance without removing panels or creating air by-
pass of the coils. Condensate pan shall be internally sloped 
and conform to ASHRAE 62-89 self-draining standards. Con-
densate connection shall be a minimum of 3/4” I.D. female 
and be a ridged mount connection.

INDOOR (EVAPORATOR) FAN ASSEMBLY

The indoor fan shall be direct drive, multi-speed, or a factory 
installed belt drive assembly that includes an adjustable pitch 
motor pulley. Job site selected (B.H.P.) brake horsepower 
shall not exceed the motors nameplate horsepower rating, 
plus the service factor. Units shall be designed not to operate 
above service factor. Fan wheel shall be double-inlet type 
with forward-curved blades, dynamically balanced to operate 
smoothly throughout the entire range of operation. Airflow 
design shall be constant air volume. Bearings shall be sealed 
and permanently lubricated for longer life and no mainte-
nance.

OUTDOOR (CONDENSER) FAN ASSEMBLY

The outdoor fan shall be of the direct-driven propeller type, 
discharge air vertically, have aluminum blades riveted to a 
corrosion resistant steel spider bracket and shall be dynami-
cally balanced for smooth operation. The outdoor fan motor 
shall be totally enclosed with permanently lubricated bear-
ings, internally protected against overload conditions and 
staged independently.

REFRIGERANT COMPONENTS

Compressor:

a.

Shall be  internally protected with internal high-pres-
sure relief and over temperature protection.

b.

Shall have internal spring isolation and sound muf-
fling to minimize vibration and noise, and be exter-
nally isolated on a dedicated, independent 
mounting.

Coils:

a.

Evaporator and condenser coils shall have alumi-
num plate fins mechanically bonded to seamless 

Summary of Contents for DM 048

Page 1: ...roof jack or frame All units include Powder Paint finish that meets ASTM B 117 750 hour salt spray standards Permanently lubricated motors Bottom or side air discharge configuration capability field...

Page 2: ...DRIVE SIDE DUCT APPLICATION 17 10 SUPPLY AIR BLOWER PERFORMANCE 5 TON BELT DRIVE SIDE DUCT APPLICATION 18 11 SUPPLY AIR BLOWER PERFORMANCE 6 TON BELT DRIVE SIDE DUCT APPLICATION 19 12 SUPPLY AIR BLOW...

Page 3: ...Options 2 4 Q Options 2 3 4 R Options 3 4 S Option 5 T Options 1 5 U Options 1 3 5 V Options 1 4 5 W Options 1 3 4 5 X Options 3 5 Y Options 4 5 Z Options 3 4 5 Options 1 Disconnect 2 Non Pwr d Conv...

Page 4: ...ond Coils CP CPC Controller DFS APS Technicoat Evap Cond Coils Phase Monitor CQ CPC Controller DFS APS Technicoat Evap Cond Coils Coil Guard CR CPC Controller DFS APS Technicoat Evap Cond Coils Phase...

Page 5: ...oneywell Excel 10 Controller DFS APS Technicoat Cond Coil Phase Monitor Hinged Filter Door Toolless Access Panels GG Honeywell Excel 10 Controller DFS APS Technicoat Cond Coil Coil Guard Hinged Filter...

Page 6: ...Evap Cond Coils NP Novar ETC 3 Controller DFS APS Technicoat Evap Cond Coils Phase Monitor NQ Novar ETC 3 Controller DFS APS Technicoat Evap Cond Coils Coil Guard NR Novar ETC 3 Controller DFS APS Te...

Page 7: ...er Coil Phase Monitor Dirty Filter Switch Hinged Filter Door Toolless Access Panels UG Technicoat Condenser Coil Coil Guard Dirty Filter Switch Hinged Filter Door Toolless Access Panels UH Technicoat...

Page 8: ...f cooling and heat Safety Monitoring The control board monitors the high and low pressure switches the freezestats the gas valve if applicable and the temperature limit switch on gas heat units The un...

Page 9: ...s that utilizes Technicoat 10 1TM processes Coating is applied by total immersion of the complete coil for maximum protection ELECTRIC HEATERS wired for single point power sup ply These nickel chromiu...

Page 10: ...fin ished roof These full perimeter curbs meet the require ments of the National Roofing Contractors Association NRCA and are shipped knocked down for field assem bly Roof curbs are designed to fit in...

Page 11: ...of knowing the details of each system This constitutes and expectation to any specification or guaran tee requiring a dBA value or sound data in any other form than sound power level ratings 2 At a di...

Page 12: ...34 33 29 25 21 17 13 62 33 3 7 33 33 33 29 25 21 17 31 4 0 31 31 31 27 23 19 15 57 34 3 6 34 34 34 30 26 22 18 32 4 0 32 32 32 28 24 20 16 72 39 3 7 27 24 20 17 14 37 4 1 26 23 20 16 13 67 36 3 6 34...

Page 13: ...45 42 37 32 27 22 17 62 43 4 9 43 43 43 38 33 28 23 40 5 4 40 40 40 35 30 26 21 57 43 4 9 43 43 43 38 33 28 23 40 5 4 40 40 40 35 30 25 20 72 53 5 0 36 32 28 23 19 51 5 5 35 31 26 22 17 67 46 4 9 44 4...

Page 14: ...50 47 42 36 30 24 18 62 48 5 8 48 48 48 42 37 31 25 44 6 4 44 44 44 38 32 26 20 57 46 5 8 46 46 46 40 35 29 23 42 6 4 42 42 42 36 31 25 19 72 60 6 0 42 37 32 26 21 57 6 6 41 36 30 25 20 67 54 5 8 52 4...

Page 15: ...66 61 54 47 40 32 25 62 64 7 0 64 64 64 56 49 42 35 58 7 8 58 58 58 51 43 36 29 57 64 7 0 64 64 64 56 49 42 34 58 7 7 58 58 58 50 43 36 29 72 75 7 1 56 49 43 36 29 76 8 0 55 48 41 34 27 67 70 7 1 68 6...

Page 16: ...RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 1700 1600 1500 1400 1055 875 1300 1036 780 1066 850 1200 1011 735 1047 765 1075 800 1100 987 690 1028 720 1060 750 1084 775 1000...

Page 17: ...RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2000 1103 1270 1900 1085 1210 1800 1064 1145 1102 1180 1700 1040 1075 1081 1115 1121 1140 1600 1020 1005 1060 1050 1100 1085 1500 1003 945...

Page 18: ...RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2500 2400 1193 1665 2300 1170 1580 1202 1620 2200 1148 1480 1180 1530 2100 1121 1385 1155 1425 1190 1475 2000 1100 1285 1133 1340...

Page 19: ...TS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 3200 3000 2800 1245 2190 2600 1193 1920 1222 1990 1250 2060 2400 1142 1675 1173 1730 1205 1800 1234 1885 2200 1090 1380 1124 1450 1155 1550 1186 16...

Page 20: ...800 1644 770 1531 710 0721 HI 2101 1260 2000 1205 1914 1155 1830 1110 0361 0481 0 70 AVAILABLE EXTERNAL STATIC PRESSURE IWG2 0 90 0 80 1 00 0361 0481 0601 AVAILABLE EXTERNAL STATIC PRESSURE IWG2 0601...

Page 21: ...utdoor air than for 100 return air If the resistance of the return air duct system is less than 0 25 IWG the unit will deliver less CFM during full economizer operation 3 Add these resistance values t...

Page 22: ...706 7 5 31 3 45 3 60 2CE04511006 10 6 44 2 61 5 70 2CE04511506 15 9 66 3 89 1 90 2CE04512006 21 2 88 3 116 7 125 NONE 0 0 0 0 25 7 40 2CE045105252 4 0 11 1 25 7 40 2CE04510725 2 5 6 15 5 25 7 40 2CE04...

Page 23: ...40 NONE 0 0 0 0 31 7 50 2CE045105252 4 0 11 1 31 7 50 2CE045107252 5 6 15 5 31 7 50 2CE04511025 8 0 22 2 36 3 50 2CE04511525 11 9 33 0 49 8 50 2CE04512025 15 9 44 1 63 7 70 2CE04513025 22 2 61 6 85 5...

Page 24: ...10706 7 5 31 3 48 6 60 2CE04511006 10 6 44 2 64 7 70 2CE04511506 15 9 66 3 92 3 100 2CE04512006 21 2 88 3 119 9 125 NONE 0 0 0 0 24 1 35 2CE04510525 2 4 0 11 1 24 1 35 2CE045107252 5 6 15 5 25 9 35 2C...

Page 25: ...40 NONE 0 0 0 0 29 9 45 2CE045105252 4 0 11 1 29 9 45 2CE045107252 5 6 15 5 29 9 45 2CE04511025 8 0 22 2 34 0 45 2CE04511525 11 9 33 0 47 5 50 2CE04512025 15 9 44 1 61 4 70 2CE04513025 22 2 61 6 83 3...

Page 26: ...5 31 3 57 8 70 2CE04511006 10 6 44 2 74 0 80 2CE04511506 15 9 66 3 101 6 110 2CE04512006 21 2 88 3 129 2 150 NONE 0 0 0 0 33 9 45 2CE045105252 4 0 11 1 33 9 45 2CE045107252 5 6 15 5 38 2 45 2CE045110...

Page 27: ...NONE 0 0 0 0 41 7 60 2CE045105252 4 0 11 1 41 7 60 2CE045107252 5 6 15 5 41 7 60 2CE04511025 8 0 22 2 48 8 60 2CE04511525 11 9 33 0 62 3 70 2CE04512025 15 9 44 1 76 2 80 2CE04513025 22 2 61 6 98 0 100...

Page 28: ...6 7 5 31 3 61 1 70 2CE04511006 10 6 44 2 77 2 80 2CE04511506 15 9 66 3 104 8 110 2CE04512006 21 2 88 3 132 4 150 NONE 0 0 0 0 34 1 45 2CE04510525 2 4 0 11 1 34 1 45 2CE045107252 5 6 15 5 38 4 45 2CE04...

Page 29: ...NONE 0 0 0 0 39 9 50 2CE045105252 4 0 11 1 39 9 50 2CE045107252 5 6 15 5 39 9 50 2CE04511025 8 0 22 2 46 5 50 2CE04511525 11 9 33 0 60 0 70 2CE04512025 15 9 44 1 73 9 80 2CE04513025 22 2 61 6 95 8 10...

Page 30: ...00 3400 3400 CONDENSER COILS Rows Deep 1 1 1 2 Fins Per Inch 16 16 22 16 Face Area Sq Ft 17 1 17 1 17 1 16 7 COMPRESSOR Qty Per Unit Scroll Type 1 1 1 1 AIR FILTERS Quantity Per Unit 15 X 20 X 1 or 2...

Page 31: ...COND STAGE COOLING OR TO HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO STAGES OF HEAT USE THERMOSTAT 2TH0471024 THERMOSTAT1 TERMINALS UNIT TERMINAL STRIP TB1 24 VOLT TRANSFORMER ADD JUMPER ADD JUMPER 1 ELE...

Page 32: ...036 21502 002 A 0303 32 Unitary Products Group FIGURE 3 UNIT DIMENSIONS 3 6 TON COOLING ONLY ELECTRIC HEAT FRONT VIEW FIGURE 4 UNIT DIMENSIONS 3 6 TON COOLING GAS HEAT FRONT VIEW...

Page 33: ...036 21502 002 A 0303 Unitary Products Group 33 FIGURE 5 UNIT WITH ECONOMIZER RAINHOOD FIGURE 6 UNIT WITH FIXED OUTDOOR AIR MOTORIZED DAMPER RAINHOOD DETAIL A DETAIL B...

Page 34: ...NG ENTRY See Detail B MOUNTING BRACKET FOR DICONNECT SWITCH Shipped attached to the blower housing inside the blower compartment FIELD SUPPLIED DISCONNECT SWITCH LOCATION BLOWER MOTOR ACCESS FILTER AC...

Page 35: ...036 21502 002 A 0303 Unitary Products Group 35 FIGURE 9 TYPICAL APPLICATIONS...

Page 36: ...ION UNIT TOTAL A B C D E F DM036 Cooling Electric 565 84 83 82 104 105 107 DM036N04 625 93 92 91 115 117 118 DM036N08 635 94 93 92 117 119 120 DM048 Cooling Electric 615 91 90 89 113 115 116 DM048N06...

Page 37: ...TON BASIC UNIT DM Cooling Only 565 615 640 720 DM Gas Electric N04 625 N06 675 N08 635 700 775 N10 685 710 785 OPTIONS Economizer 50 Motorized Damper 26 Electric Heater 5 7 kW 18 10 15 kW 23 20 30 kW...

Page 38: ...factory tested prior to shipment All unit wiring shall be both numbered and color coded All units the cooling performance shall be rated in accordance with DOE and ARI test procedures Units shall be C...

Page 39: ...and redun dant main gas valve Venter wheel shall be constructed of stainless steel for corrosion resistance The heat exchanger shall be of the tubular type constructed of T1 40 aluminized steel for c...

Page 40: ...the conditioned space during normal operation Whenever the indoor fan motor is energized the dampers open up to one of two pre selected positions regardless of the outdoor air enthalpy Dampers return...