Location
Use the following guidelines to select a suitable location for
these units:
1.
Unit is designed for
outdoor installation only
.
2.
Condenser coils must have an unlimited supply of air.
Where a choice of location is possible, position the unit on
either north or east side of building.
3.
Suitable for mounting on roof curb.
4.
For ground level installation, use a level concrete slab with
a minimum thickness of 101mm (4”). The length and width
should be at least 152mm (6”) greater than the unit base
rails. Do not tie slab to the building foundation.
5.
Roof structures must be able to support the weight of the
unit and its options/accessories. Unit must be installed on a
solid, level roof curb or appropriate angle iron frame.
6.
Maintain level tolerance to 13 mm (1/2”) maximum
across the entire length or width of the unit.
If a unit is to be installed on a roof curb or special frame other
than a YORK roof curb, gasketing must be applied to all
surfaces that come in contact with the unit underside.
Rigging And Handling
Exercise care when moving the unit. Do not remove any
packaging until the unit is near the place of installation. Rig the
unit by attaching chain or cable slings to the lifting holes
provided in the base rails. Spreader bars, whose length
exceeds the largest dimension across the unit,
MUST
be used
across the top of the unit.
Units may be moved or lifted with a forklift. Slotted openings in
the base rails are provided for this purpose.
Remove the nesting brackets from the four corners on the top
of the unit. All screws that are removed when removing the
brackets must be replaced on the unit.
Refer to Tables 8 and 9 for unit weights and to the Figure 10 for
approximate center of gravity.
Table 1:
Unit Application Data (DM)
UNIT MODEL NUMBER
036
048
060
076
Voltage Variation,
Min. / Max.
1
380/415
342 / 456
Supply Air m
3
/s (ft
3
/min.), Nom.
0.57 (1200)
0.76 (1600)
0.94 (2000)
1.13 (2400)
Wet Bulb Temperature of Air on
Evaporator Coil, Min. / Max
14°C / 22°C (57°F / 72°F)
Dry Bulb Temperature of Air on
Condenser Coil, Min. / Max.
-18°C / 50°C (0°F / 122°F)
1. Utilization range “A” in accordance with ARI Standard 110.
Excessive exposure of this furnace to contaminated
combustion air may result in equipment damage or
personal injury. Typical contaminates include:
permanent wave solution, chlorinated waxes and
cleaners, chlorine based swimming pool chemicals,
water softening chemicals, carbon tetrachloride,
Halogen type refrigerants, cleaning solvents (e.g.
perchloroethylene), printing inks, paint removers,
varnishes, hydrochloric acid, cements and glues, anti-
static fabric softeners for clothes dryers, masonry acid
washing materials.
Before lifting a unit, make sure that all panels are in
place and that its weight is distributed equally on all
cables so it will lift evenly.
An adhesive backed label is provided over the outside of
the combustion air inlet opening to prevent moisture
from entering the unit, which could cause damage to
electrical components. Allow this closure label to remain
in place until the combustion air hood is to be installed
(refer to Vent and Combustion Hood Figure 7).
If a unit is to be installed on a roof curb other than a
York
®
roof curb, gasketing must be applied to all
surfaces that come in contact with the unit underside.
Before lifting, make sure the unit weight is distributed
equally on the rigging cables so it will lift evenly.