background image

The limit switch, operates when a high temperature
condition, caused by inadequate supply air flow occurs,
thus shutting down the ignition control and closing the main
gas valve.

2. Centrifugal Switch (CS-36). If the draft motor should fail, the

centrifugal switch attached to the shaft of the motor
prevents the ignition control and gas valve from being
energized.

3. Redundant Gas Valve. This valve is an integral part of the

main gas valve and is located up stream of the main gas
valve. Should the main gas valve fail in the open position
the redundant valve serves as a back up and shuts off the
flow of gas.

4. Flame Sensor Rod. This sensor rod is located on the far

side of the carryover tube. If the ignition control does not
receive a signal from the flame sensor indicating that the
pilot flame has ignited properly, the main gas valve will not
open. If the flame sensor fails to detect the pilot flame during

operation of the main burners, a signal is sent to the ignition
control to close the main gas valve.

5. Rollout Switch. This switch is located in the burner

vestibule. In the event of a sustained main burner flame
rollout, it shuts off the ignition control and closes the main
gas valve.

6. Auxiliary Limit Switch. This control is located inside the heat

exchanger compartment and is set to open at 180

°

F. It is a

manual reset switch. If the auxiliary limit switch trips, then
the primary limit switch has not functioned properly.
Replace the primary limit switch.

HEAT ANTICIPATOR SETPOINTS

The anticipator must be set correctly. Too high of a setting will
result in longer heat cycles and a greater temperature swing in
the conditioned space.

Reducing the value below the correct setpoint will give shorter
“ON” cycles and may result in the lowering of the temperature
within the conditioned space.

PRE-START CHECK LIST

Complete the following checks before starting the unit.

1. Check the type of gas being supplied. Be sure that it is the

same as listed on the unit nameplate.

2. Make sure that the vent and combustion air hoods have

been properly installed.

Units

(Tons)

Capacity, MBH

Limit Control

Opens, 

°

F

Input

Output

3
4
3
4
5
5
6
6

50
75

100
125
100
125
100
125

40
60
79
99
79
99
79
99

165
165
165
165
165
165
165
165

TABLE 16 - LIMIT CONTROL SETTING

Gas Valve

Anticipator Setpoint

Honeywell VR8204M

0.60 amp

White-Rodgers 36E36

0.54 amp

START-UP

OPERATING INSTRUCTIONS

CAUTION: This furnace is equipped with an intermittent pilot

and automatic re-ignition system. DO NOT attempt
to manually light the pilot.

TO LIGHT PILOT AND MAIN BURNERS:

1. Turn “off” electric power to unit.

2. Turn room thermostat to lowest setting.

3. Turn gas valve knob to “on” position.

4. Turn “on” electric power to unit.

5. Set room thermostat to desired temperature.

(If thermostat “set” temperature is above room temperature,
pilot burner ignition will occur and, after an interval to prove
pilot flame, main burners will ignite).

TO SHUT DOWN:

1. Turn “off” electric power to unit.

2. Depress knob of gas valve while turning to “off” position.

POST-START CHECK LIST (GAS)

After the entire control circuit has been energized and the
heating section is operating, make the following checks:

1. Check for gas leaks in the unit piping as well as the supply piping.

2. Check for correct manifold gas pressures. See “Checking

Gas Input”.

3. Check the supply gas pressure. It must be within the limits

shown on rating nameplate. Supply pressure should be
checked with all gas appliances in the building at full fire.
At no time should the standby gas line pressure exceed 13",
nor the operating pressure drop below 4.5" for natural gas
units. If gas pressure is outside these limits, contact the
local gas utility for corrective action.

MANIFOLD GAS PRESSURE ADJUSTMENT

Small adjustments to the high-fire gas flow may be made by
turning the pressure regulator adjusting screw on the automatic
gas valve. Refer to Figure 9.

Adjust as follows:

1. Remove the cap on the regulator. (High Fire adjusting

screw on valve).

2. To decrease the gas pressure, turn the adjusting screw

counterclockwise.

3. To increase the gas pressure, turn the adjusting screw clockwise.

NOTE: Check the unit dataplate for the proper manifold pres-

sure and orifice size of the furnace.

PILOT ADJ.
(UNDER
SCREW)

“ON”-"OFF"
 CONTROL
HIGH FIRE ADJ.
(UNDER SCREW)

Honeywell
VR8204M

“ON”-"OFF" CONTROL

PRESSURE REGULATOR

MANIFOLD ADJUST.  SCREW

1/2-14 NPT (OUTLET)

White-Rodgers
36E36

PILOT ADJ.
(UNDER
SCREW)

FIG. 9 - GAS VALVES

530.18-N8W

Unitary Products Group

15

Summary of Contents for DHUC 036

Page 1: ...CGA and UL listed as follows 1 For use as a forced air furnace with cooling unit 2 For outdoor installation only 3 For installation directly on combustible flooring or in the U S A on wood flooring or...

Page 2: ...tatic Resistances 7 5 Physical Data 7 6 Supply Air Blower Perf 3 6 Ton Direct Drive 8 7 Motor Drive Data Belt Drive Blower 8 8 Supply Air Blower Perf 3 4 Ton Belt Drive 9 9 Supply Air Blower Perf 5 6...

Page 3: ...ulation in your area RIGGING AND HANDLING Exercise care when moving the unit Do not remove any packaging until the unit is near the place of installation Rig the unit by attaching chain or cable sling...

Page 4: ...internal wiring harness furnished with this unit is an integral part of a UL and CGA design certified unit Field alteration to comply with electrical codes should not be required A disconnect switch...

Page 5: ...TYPICAL FIELD WIRING REFER TO ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT SWITCH WIRING OVERCURRENT PROTECTION REFER TO ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT SWITCH WIRING OVERCURRENT PROTE...

Page 6: ...LAME 6 The furnace and its individual manual shut off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1 2 psig 3...

Page 7: ...Table 2 The pressure thru the economizer is greater for 100 outdoor air than for 100 return air If the resistance of the return air duct system is less than 0 25 IWG the unit will deliver less CFM du...

Page 8: ...00 710 1631 1464 780 690 1699 1582 1421 825 750 670 1650 1524 1367 785 720 650 1570 1410 1315 755 690 620 1430 1324 1246 725 650 605 1360 1260 1185 700 630 590 1280 1185 1110 680 610 570 1180 1100 102...

Page 9: ...S REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN GAS ELECTRIC UNITS WITH SIDE DUCT AIRFLOWS UNIT SIZE AIR FLOW CFM Available External Static Pressure IWG 0 20 0...

Page 10: ...re IWG 0 20 0 30 0 40 0 50 0 60 0 70 0 80 RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts 060 2500 1059 1560 1077 1590 1095 1630 1114 1650 1134 1660 1158 1685 1181 1720 2400 1032...

Page 11: ...504 630 28 9 16 0 8 0 6 4 165 0 125 0 67 0 50 0 1 3 1 3 0 8 0 8 8 6 6 0 3 0 2 4 46 0 27 3 13 8 11 2 70 40 20 15 70 40 20 072 208 230 3 60 460 3 60 575 3 60 187 414 518 253 504 630 20 3 10 2 8 2 146 0...

Page 12: ...32 3 33 4 75 13 7 15 9 18 1 20 3 22 5 24 7 26 9 28 1 29 3 30 5 31 8 80 10 4 12 8 15 1 17 4 19 8 22 1 24 5 25 9 27 3 28 7 30 2 85 7 2 9 7 12 2 14 6 17 1 19 6 22 0 23 7 25 3 27 0 28 6 90 6 6 8 9 11 3 13...

Page 13: ...material and the supply air ductwork for a distance of 3 feet from the unit The products of combustion must not be allowed to accumulate within a confined space and recirculate Locate unit so that th...

Page 14: ...DMC is energized The DMR or DMC power contacts close which energizes the line voltage draft motor As the speed of the draft motor reaches approximately 2500 RPM the centrifugal switch contact CS locat...

Page 15: ...nput Output 3 4 3 4 5 5 6 6 50 75 100 125 100 125 100 125 40 60 79 99 79 99 79 99 165 165 165 165 165 165 165 165 TABLE 16 LIMIT CONTROL SETTING Gas Valve Anticipator Setpoint Honeywell VR8204M 0 60 a...

Page 16: ...Adjust the resistances in both the supply and the return air duct systems to balance the air distribution throughout the conditioned space The job specifications may require that this balancing be don...

Page 17: ...e permissible range of the regulator setting replace the orifice spuds with spuds of the proper size NOTE To find the Btu input multiply the number of cubic feet of gas consumed per hour by the Btu co...

Page 18: ...e baffles 8 Run the wire brush down the vent tube from the flue collector end 9 If soot build up is particularly bad remove the vent motor and clean the wheel and housing Run the wire brush down the f...

Page 19: ...ed at the draft motor outlet a Check to make sure gas is being supplied to the unit Make sure that the gas pressure to the unit is within the proper limits as described in the POST START CHECK LIST an...

Page 20: ...in U S A Copyright by Unitary Products Group 1998 All rights reserved 530 18 N8W Post Office Box 1592 York Pennsylvania 17405 1592 Unitary Products Group 208 230 575 VOLT MODELS ONLY 208 230 1 60 VOLT...

Reviews: