background image

COOLING SYSTEM

The cooling section is a complete factory package utilizing an
air-cooled condenser. The system is factory-charged with
Refrigerant-22.

The scroll compressor is hermetically sealed and internally
sprung. The scroll compressors have inherent (internal)
protection. If there is an abnormal temperature rise in the scroll
compressor, the protector will open to shut down the scroll
compressor.

COOLING SEQUENCE OF OPERATION

Single-Stage Cooling: When the thermostat calls for “cooling”,
“R” is closed to “G” and “Y1" (wiring schematic) which
completes the low voltage control circuit, immediately
energizing the scroll compressor, condenser fan motor and
blower motor simultaneously.

Two-Stage Cooling: A two-stage cooling thermostat may be
used if the unit has an economizer. First-stage cooling is
provided by the economizer - if the outdoor air enthalpy is
acceptable, and second-stage cooling is provided by the scroll
compressor. Jumper wire J1 must be removed. Refer to the unit
wiring diagram.

After the thermostat is satisfied and opens, all components will
stop simultaneously.

CONTINUOUS BLOWER - Continuous blower operation is
possible by closing the R to G circuit on the thermostat.

SAFETY CONTROLS (Cooling)

The refrigerant system is equipped with the following safety
controls:

1. A Suction Line Freezestat to protect aginst low evaporator

temperatures due to a low air flow or a low return air
temperature.

2. A High Pressure Cutout Switch to protect against excessive

discharge pressures due to a blocked condenser coil or a
condenser motor failure.

3. A Low Pressure Switch to protect against loss of refrigerant

charge.

If either one of the above safety controls opens, the refrigerant
system will bo locked out. The lock out of the system can be
reset by opening the 24V circuit either at the room thermostat
or at the unit disconnect.

HEATING SEQUENCE OF OPERATION

The following sequence describes the operation of the gas heat
section.

CONTINUOUS BLOWER: With the room thermostat switch set
to “ON”, the supply air blower will operate continuously. The
normally closed blower interlock relay contact “K3-1” provides
24 volt power to the blower relay “BR”. The “BR” power contacts
close and the blower motor operates.

INTERMITTENT BLOWER: With the room thermostat system
switch set to the “AUTO” or “HEAT” position and the fan switch
set to “AUTO”, the supply air blower will operate after the room
thermostat calls for heat and the air in the gas heat
compartment has achieved a pre-set temeprature.

When “TH1” on the thermostat closes, the draft motor relay
“DMR” or “DMC” is energized. The “DMR” or “DMC” power
contacts close which energizes the line voltage draft motor. As
the speed of the draft motor reaches approximately 2500 RPM,
the centrifugal switch contact “CS” located on the end of the
draft motor shaft closes to power the ignition control “IC”.

After 15 seconds, the “IC” will start the ignitor sparking and will
open the redundant valve locted inside the main gas valve “GV”
to allow a flow of gas to only the carryover tube. See Figure 10.
Only after the pilot flame has been ignited and the presence of
pilot flame detected at the “IC” by a signal sent back through
the flame sensor is sparking terminated and the main gas valve
opened.

Gas flows into each of the main burners and is ignited from the
carryover tube flame.

The “IC” will try for 85 seconds to ignite the pilot carryover tube.
If the “IC” fails to detect a pilot flame during the 85 seconds, it
will close the redundant valve. After a 5 minute purge period,
the “IC” will again try to light the pilot carryover tube. This will
continue continuously until the “IC” detects a pilot flame.

If, after detecting a pilot flame and opening the main gas valve,
the “IC” looses pilot flame indication, it will close both the main
and redundant gas valves. The “IC” will start the above
sequence over until a pilot flame is detected and it will open the
main gas valve again.

The “IC” will only allow 16 pilot flameouts and a single rollout
switch opening per thermostat cycle. After 16 pilot flameouts or
a single rollout switch opening, the “IC” closes both the main
and redundant gas valves. The “IC” requires resetting the
thermostat or removal of it’s power lead coming from the draft
motor to reset the “IC” and return it to the above sequence of
operation.

At the same time power was supplied to the “DMR” or “DMC”,
a parallel circuit activates the time delay (“BT” or “ETD”). The
“BT” or “ETD” closes in approximetly 35 seconds and starts the
circulating air blower by energizing the blower interlock relay
“K3”, thus closing the “K3-2” contact and energizing the blower
relay “BR”.

When the heating cycle is complete, “TH-1” opens
de-energizing the “IC”, thus closing the redundant and main
gas valves. The blower motor and the draft motor continue to
run for a short period after the furnace is shut down until the
“BT” or “ETD” opens (in approximately 25 seconds)
de-energizing the “K3”, “BR” and “DMR” or “DMC” relays.

SAFETY CONTROLS (Heating)

The control circuit includes the following safety controls:

1. Limit Control (LS). This control is located inside the heat

exchanger compartment and is set to open at the
temperature indicated in Table 16. It resets automatically.

GAS
VALVE

GAS MAIN

MAIN VALVE

TO MAIN
BURNER

REDUNDANT
VALVE

TO PILOT BURNER

FIG. 8 - GAS VALVE PIPING

OPERATION

530.18-N8W

14

Unitary Products Group

Summary of Contents for DHUC 036

Page 1: ...CGA and UL listed as follows 1 For use as a forced air furnace with cooling unit 2 For outdoor installation only 3 For installation directly on combustible flooring or in the U S A on wood flooring or...

Page 2: ...tatic Resistances 7 5 Physical Data 7 6 Supply Air Blower Perf 3 6 Ton Direct Drive 8 7 Motor Drive Data Belt Drive Blower 8 8 Supply Air Blower Perf 3 4 Ton Belt Drive 9 9 Supply Air Blower Perf 5 6...

Page 3: ...ulation in your area RIGGING AND HANDLING Exercise care when moving the unit Do not remove any packaging until the unit is near the place of installation Rig the unit by attaching chain or cable sling...

Page 4: ...internal wiring harness furnished with this unit is an integral part of a UL and CGA design certified unit Field alteration to comply with electrical codes should not be required A disconnect switch...

Page 5: ...TYPICAL FIELD WIRING REFER TO ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT SWITCH WIRING OVERCURRENT PROTECTION REFER TO ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT SWITCH WIRING OVERCURRENT PROTE...

Page 6: ...LAME 6 The furnace and its individual manual shut off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1 2 psig 3...

Page 7: ...Table 2 The pressure thru the economizer is greater for 100 outdoor air than for 100 return air If the resistance of the return air duct system is less than 0 25 IWG the unit will deliver less CFM du...

Page 8: ...00 710 1631 1464 780 690 1699 1582 1421 825 750 670 1650 1524 1367 785 720 650 1570 1410 1315 755 690 620 1430 1324 1246 725 650 605 1360 1260 1185 700 630 590 1280 1185 1110 680 610 570 1180 1100 102...

Page 9: ...S REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN GAS ELECTRIC UNITS WITH SIDE DUCT AIRFLOWS UNIT SIZE AIR FLOW CFM Available External Static Pressure IWG 0 20 0...

Page 10: ...re IWG 0 20 0 30 0 40 0 50 0 60 0 70 0 80 RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts 060 2500 1059 1560 1077 1590 1095 1630 1114 1650 1134 1660 1158 1685 1181 1720 2400 1032...

Page 11: ...504 630 28 9 16 0 8 0 6 4 165 0 125 0 67 0 50 0 1 3 1 3 0 8 0 8 8 6 6 0 3 0 2 4 46 0 27 3 13 8 11 2 70 40 20 15 70 40 20 072 208 230 3 60 460 3 60 575 3 60 187 414 518 253 504 630 20 3 10 2 8 2 146 0...

Page 12: ...32 3 33 4 75 13 7 15 9 18 1 20 3 22 5 24 7 26 9 28 1 29 3 30 5 31 8 80 10 4 12 8 15 1 17 4 19 8 22 1 24 5 25 9 27 3 28 7 30 2 85 7 2 9 7 12 2 14 6 17 1 19 6 22 0 23 7 25 3 27 0 28 6 90 6 6 8 9 11 3 13...

Page 13: ...material and the supply air ductwork for a distance of 3 feet from the unit The products of combustion must not be allowed to accumulate within a confined space and recirculate Locate unit so that th...

Page 14: ...DMC is energized The DMR or DMC power contacts close which energizes the line voltage draft motor As the speed of the draft motor reaches approximately 2500 RPM the centrifugal switch contact CS locat...

Page 15: ...nput Output 3 4 3 4 5 5 6 6 50 75 100 125 100 125 100 125 40 60 79 99 79 99 79 99 165 165 165 165 165 165 165 165 TABLE 16 LIMIT CONTROL SETTING Gas Valve Anticipator Setpoint Honeywell VR8204M 0 60 a...

Page 16: ...Adjust the resistances in both the supply and the return air duct systems to balance the air distribution throughout the conditioned space The job specifications may require that this balancing be don...

Page 17: ...e permissible range of the regulator setting replace the orifice spuds with spuds of the proper size NOTE To find the Btu input multiply the number of cubic feet of gas consumed per hour by the Btu co...

Page 18: ...e baffles 8 Run the wire brush down the vent tube from the flue collector end 9 If soot build up is particularly bad remove the vent motor and clean the wheel and housing Run the wire brush down the f...

Page 19: ...ed at the draft motor outlet a Check to make sure gas is being supplied to the unit Make sure that the gas pressure to the unit is within the proper limits as described in the POST START CHECK LIST an...

Page 20: ...in U S A Copyright by Unitary Products Group 1998 All rights reserved 530 18 N8W Post Office Box 1592 York Pennsylvania 17405 1592 Unitary Products Group 208 230 575 VOLT MODELS ONLY 208 230 1 60 VOLT...

Reviews: