background image

DUCT COVERS - Units are shipped with all air duct
openings covered.
For side duct applications;
1. Remove and discard the supply and return air duct
    covers.
2. Connect ductwork to duct flanges on the rear of the
    unit.
For bottom duct applications;
1. Remove the side supply air duct cover to gain
    access to the bottom supply air knockout panel.
2. Remove and discard the bottom knockout panel.
3. Replace the side duct cover.
4. With filter section access panel removed from the
    unit, remove and discard the bottom return air
    knockout panel.
5. Replace the filter access panel.

SCROLL COMPR.
ACCESS

11

1

2

4

5

8

3

7

7

8

6

1

2

17

1

2

11

1

2

17

1

2

REAR VIEW

SIDE SUPPLY AND RETURN

Front

32"

Back

12" (Less Economizer)
36" (With Economizer or Fixed
        Air/Motorized Air Damper)

Left Side (Filter Access)

24" (Less Economizer)
36" (With Economizer)

Right Side (Cond. Coil)

24"

Below Unit

1

2

0"

Above Unit

2

72" (For Condenser Air Discharge)

Units may be installed on combustible floors made from wood or class A, B or C

   roof covering material (Applicable in the USA only).

2

 Units must be installed oudoors. Overhanging structures or shrubs should not

   obstruct the outdoor coil nor the fan outlet.
NOTE: A 1" clearance must be provided between any combustible material and the
   supply air ductwork for a distance of 3 feet from the unit.
   The products of combustion must not be allowed to accumulate within a confined
   space and recirculate.
Locate unit so that the vent air outlet hood is at least:

 Three (3) feet above any forced air inlet located within 10 horizontal feet (excluding

   those integral to the unit).

 Four (4) feet below, 4 horizontal feet from, or 1 foot above any door or gravity air

   inlet into the building.

 Four (4) feet from electric meters, gas meters, regulators and relief equipment.

CLEARANCES

All dimensions are in inches. They are sub-
ject to change without notice. Certified di-
mensions will be provided upon request.

AIR FLOW LEGEND

RETURN AIR

SUPPLY AIR

OUTDOOR AIR

OUTDOOR AIR
(Economizer)

HOLE

KNOCKOUT

SIZE

(DIA.)

USED FOR

A

7/8"  *

Control Wiring
(Side or Bottom)**

B

2"  *

Power Wiring
(Side or Bottom)

C

1-5/8"

Gas Piping (Front)

D

1-1/2"

Gas Piping (Bottom)

 *

Knockouts in the bottom of the unit can be located by the slice

   in the insulation.

**

Do not remove the 2" knockout ring.

UTILITIES ENTRY DATA

FIG. 7 - DIMENSIONS AND CLEARANCE (3, 4, 5 & 6 TON)

(Direct-Drive Units)

UNIT WITH ECONOMIZER RAIN HOOD

44

7

8

B

30

7

8

"A"

10

1

4

4

3

8

A

3

1

2

8

1

4

19

1

8

44

7

8

19

1

2

27

1

2

19

3

4

3

4

“ CONDENSATE

DRAIN
(must be trapped)

DETAIL “A”

DETAIL “B”

DIMENSION "A"

FIXED

OUTDOOR

AIR DAMPER

12

MOTORIZED

DAMPER

16

1

2

UNIT WITH FIXED OUTDOOR

AIR/MOTORIZED DAMPER RAIN HOOD

530.18-N8W

Unitary Products Group

13

Summary of Contents for DHUC 036

Page 1: ...CGA and UL listed as follows 1 For use as a forced air furnace with cooling unit 2 For outdoor installation only 3 For installation directly on combustible flooring or in the U S A on wood flooring or...

Page 2: ...tatic Resistances 7 5 Physical Data 7 6 Supply Air Blower Perf 3 6 Ton Direct Drive 8 7 Motor Drive Data Belt Drive Blower 8 8 Supply Air Blower Perf 3 4 Ton Belt Drive 9 9 Supply Air Blower Perf 5 6...

Page 3: ...ulation in your area RIGGING AND HANDLING Exercise care when moving the unit Do not remove any packaging until the unit is near the place of installation Rig the unit by attaching chain or cable sling...

Page 4: ...internal wiring harness furnished with this unit is an integral part of a UL and CGA design certified unit Field alteration to comply with electrical codes should not be required A disconnect switch...

Page 5: ...TYPICAL FIELD WIRING REFER TO ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT SWITCH WIRING OVERCURRENT PROTECTION REFER TO ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT SWITCH WIRING OVERCURRENT PROTE...

Page 6: ...LAME 6 The furnace and its individual manual shut off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1 2 psig 3...

Page 7: ...Table 2 The pressure thru the economizer is greater for 100 outdoor air than for 100 return air If the resistance of the return air duct system is less than 0 25 IWG the unit will deliver less CFM du...

Page 8: ...00 710 1631 1464 780 690 1699 1582 1421 825 750 670 1650 1524 1367 785 720 650 1570 1410 1315 755 690 620 1430 1324 1246 725 650 605 1360 1260 1185 700 630 590 1280 1185 1110 680 610 570 1180 1100 102...

Page 9: ...S REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN GAS ELECTRIC UNITS WITH SIDE DUCT AIRFLOWS UNIT SIZE AIR FLOW CFM Available External Static Pressure IWG 0 20 0...

Page 10: ...re IWG 0 20 0 30 0 40 0 50 0 60 0 70 0 80 RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts 060 2500 1059 1560 1077 1590 1095 1630 1114 1650 1134 1660 1158 1685 1181 1720 2400 1032...

Page 11: ...504 630 28 9 16 0 8 0 6 4 165 0 125 0 67 0 50 0 1 3 1 3 0 8 0 8 8 6 6 0 3 0 2 4 46 0 27 3 13 8 11 2 70 40 20 15 70 40 20 072 208 230 3 60 460 3 60 575 3 60 187 414 518 253 504 630 20 3 10 2 8 2 146 0...

Page 12: ...32 3 33 4 75 13 7 15 9 18 1 20 3 22 5 24 7 26 9 28 1 29 3 30 5 31 8 80 10 4 12 8 15 1 17 4 19 8 22 1 24 5 25 9 27 3 28 7 30 2 85 7 2 9 7 12 2 14 6 17 1 19 6 22 0 23 7 25 3 27 0 28 6 90 6 6 8 9 11 3 13...

Page 13: ...material and the supply air ductwork for a distance of 3 feet from the unit The products of combustion must not be allowed to accumulate within a confined space and recirculate Locate unit so that th...

Page 14: ...DMC is energized The DMR or DMC power contacts close which energizes the line voltage draft motor As the speed of the draft motor reaches approximately 2500 RPM the centrifugal switch contact CS locat...

Page 15: ...nput Output 3 4 3 4 5 5 6 6 50 75 100 125 100 125 100 125 40 60 79 99 79 99 79 99 165 165 165 165 165 165 165 165 TABLE 16 LIMIT CONTROL SETTING Gas Valve Anticipator Setpoint Honeywell VR8204M 0 60 a...

Page 16: ...Adjust the resistances in both the supply and the return air duct systems to balance the air distribution throughout the conditioned space The job specifications may require that this balancing be don...

Page 17: ...e permissible range of the regulator setting replace the orifice spuds with spuds of the proper size NOTE To find the Btu input multiply the number of cubic feet of gas consumed per hour by the Btu co...

Page 18: ...e baffles 8 Run the wire brush down the vent tube from the flue collector end 9 If soot build up is particularly bad remove the vent motor and clean the wheel and housing Run the wire brush down the f...

Page 19: ...ed at the draft motor outlet a Check to make sure gas is being supplied to the unit Make sure that the gas pressure to the unit is within the proper limits as described in the POST START CHECK LIST an...

Page 20: ...in U S A Copyright by Unitary Products Group 1998 All rights reserved 530 18 N8W Post Office Box 1592 York Pennsylvania 17405 1592 Unitary Products Group 208 230 575 VOLT MODELS ONLY 208 230 1 60 VOLT...

Reviews: