Note: 1. Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.

2. The pressure thru the economizer is greater for 100% outdoor air then for 100% return air. If the resistance of the return air duct 

system is less then 0.25 IWG, the unit will deliver less CFM during full economizer operation.

FIGURE 2 - TYPICAL FIELD WIRING DIAGRAM

TABLE 8: SIDE AND BOTTOM SUPPLY AIR BLOWER PERFORMANCE

Model No.

DEB

Blower

Speed

Setting

External Static Pressure (Inches Water Gauge)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

1.1

CFM

W

CFM

W

CFM

W

CFM

W

CFM

W

CFM

W

CFM

W

CFM W CFM W CFM W CFM W

030

(2.5)

High

-

-

-

-

-

-

-

-

1171

504

1080

486

990

468

888

456

786

444

-

-

-

-

Medium

1080

351

1021

341

961

331

902

321

841

305

781

290

-

-

-

-

-

-

-

-

-

-

Low

810

261

765

240

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

036

(3.0)

High

-

-

-

-

1440

605

1361

581

1273

555

1185

530

1097

504

1004 480

912

456

-

-

-

-

Medium

1465

531

1395

512

1325

492

1255

473

1167

446

1079

419

992

392

-

-

-

-

-

-

-

-

Low

1316

473

1260

455

1204

438

1148

420

1069

396

990

372

911

348

-

-

-

-

-

-

-

-

042

(3.5)

High

-

-

-

-

1728

725

1633

697

1527

666

1422

635

1317

605

1205 576 1094 547

-

-

-

-

Medium

-

-

1674

614

1590

590

1506

567

1400

535

1295

502

1190

470

1063 428

-

-

-

-

-

-

Low

1579

567

1512

546

1444

525

1377

504

1282

476

1188

447

1093

418

-

-

-

-

-

-

-

-

048

(4.0)

High

-

-

1985

870

1939

850

1897

830

1813

800

1728

770

1644

740

1559 707 1474 673 1389 640

-

-

Medium

1694

690

1662

673

1629

657

1597

640

1542

623

1486

607

1431

590

1336 563 1240 537

-

-

-

-

Low

1385

520

1349

510

1312

500

1276

490

1235

480

-

-

-

-

-

-

-

-

-

-

-

-

060

(5.0)

High

-

-

-

-

2450 1213 2366 1165 2282 1117 2198 1068 2114 1020 1989 993 1864 967 1739 940

-

-

Medium

2339 1170 2275 1118 2211 1067 2147 1015 2083

963

2019

912

1955

860

1854 824 1753 788 1652 752

-

-

Low

1929

940

1877

903

1824

867

1772

830

1720

793

1667

757

1615

720

1586 706 1557 691 1528 677

-

-

TABLE 9: ADDITIONAL STATIC RESISTANCE

Description

Resistance, IWG

CFM

500

600

700

800

900

1,000

1,100

1,200

1,300

1,400

1,500

1,600

Wet Evaporator Coil

.01

.01

.01

.02

.03

.04

.05

.06

.07

.08

.09

.09

Economizer

.00

.00

.00

.01

.01

.01

.01

.02

.03

.04

.05

.06

Filter/Frame Kit

.01

.02

.02

.02

.02

.02

.03

.03

.03

.03

.04

.05

Electric Heat

.02

.03

.03

.03

.04

.04

.05

.06

.07

.08

.09

.10

THERMOSTAT 

 

PROGRAMMABLE 

THERMOSTAT ONLY 

UNIT TERMINAL STRIP 

24 VOLT

TRANSFORMER

NOTE: 
HEAT ANTICIPATOR 
SHOULD BE SET AT 0.25 
AMPS FOR ALL MODELS 

Minimum wire size of 18 AWG 
wire should be used for all field 
installed 24 volt wire. 

** =  

Only required on units with
supplemental electric heat.

* = 

** 

*

CAUTION: 

Label all wires prior to disconnection 
when servicing controls. Wiring errors 
can cause improper and dangerous 
operation. Verify proper operation 
after servicing. 

CONTROL WIRING 

POWER WIRING 

CONTACTOR

FIELD SUPPLIED

DISCONNECT

THREE
PHASE
POWER
SUPPLY

GROUND

LUG

CONTACTOR

FIELD SUPPLIED

DISCONNECT

SINGLE
PHASE
POWER
SUPPLY

GROUND

LUG

REFER TO ELECTRICAL DATA
TABLES TO SIZE THE DISCON-
NECT SWITCH, WIRING AND
OVERCURRENT PROTECTION.

REFER TO ELECTRICAL DATA
TABLES TO SIZE THE DISCON-
NECT SWITCH, WIRING AND
OVERCURRENT PROTECTION.

Summary of Contents for D2EB030

Page 1: ...ds to carry less inventory LOWER INSTALLATION COST Installation time and costs are reduced by easy power and control wiring connections The small base dimension means less space is required on the gro...

Page 2: ...3 60 POWER SUPPLY DEB MODELS 20 LIST OF TABLES Tbl Pg 1 PHYSICAL DATA 5 2 RATINGS ARI 5 3 COOLING CAPACITIES 2 1 2 TON DEB030 6 4 COOLING CAPACITIES 3 TON DEB036 7 5 COOLING CAPACITIES 3 1 2 TON DEB04...

Page 3: ...e condenser fan does not disrupt neighboring areas and does not dry out vegetation surrounding the unit The warm air from the top mounted fan is blown up away from the structure and any landscaping Th...

Page 4: ...ed side return and unit mounted down shot return applications Damper capable of providing 0 thru 50 of outdoor air field supplied Closes on power loss includes hood and screen assembly RECTANGLE TO RO...

Page 5: ...IL ROWS DEEP 1 1 1 1 1 FINS PER INCH 20 18 16 13 20 FACE AREA Sq Ft 8 3 8 3 11 7 16 4 16 4 CHARGE REFRIGERANT 22 lbs oz 3 13 3 10 4 8 5 15 5 15 FILTER FACE AREA Sq Ft Qty Size 2 14 2 14 x 22 COMPRESSO...

Page 6: ...Power Input kW 3 38 3 28 3 22 3 22 3 45 3 35 3 29 3 28 3 52 3 42 3 36 3 35 3 66 3 55 3 49 3 48 3 79 3 68 3 62 3 61 Sensible Capacity MBH 1 Entering Dry Bulb F 86 16 5 21 3 22 2 22 3 18 5 23 4 23 1 23...

Page 7: ...ut kW 4 05 3 92 3 93 3 85 4 07 3 94 3 95 3 87 4 09 3 96 3 97 3 89 4 15 4 02 4 02 3 95 4 21 4 08 4 08 4 00 Sensible Capacity MBH 1 Entering Dry Bulb F 86 17 5 23 3 25 0 24 4 19 9 26 3 26 6 26 0 22 3 29...

Page 8: ...20 4 22 4 47 4 35 4 27 4 29 4 54 4 42 4 34 4 35 4 69 4 57 4 48 4 50 4 84 4 71 4 63 4 64 Sensible Capacity MBH 1 Entering Dry Bulb F 86 22 4 29 3 30 8 31 2 24 8 32 1 32 0 32 4 27 3 34 9 33 1 33 6 29 3...

Page 9: ...21 5 21 5 49 5 43 5 34 5 33 5 62 5 55 5 46 5 45 5 72 5 66 5 56 5 55 5 83 5 76 5 66 5 65 Sensible Capacity MBH 1 Entering Dry Bulb F 86 27 0 33 2 37 8 37 4 29 6 36 1 38 3 37 9 32 3 39 1 38 8 38 3 34 3...

Page 10: ...58 7 07 6 90 6 79 6 75 7 25 7 06 6 96 6 91 7 47 7 28 7 17 7 12 7 69 7 50 7 38 7 33 Sensible Capacity MBH 1 Entering Dry Bulb F 86 33 5 42 4 45 0 45 3 37 5 47 1 46 9 47 2 41 4 51 8 48 8 49 1 44 9 53 7...

Page 11: ...657 1597 640 1542 623 1486 607 1431 590 1336 563 1240 537 Low 1385 520 1349 510 1312 500 1276 490 1235 480 060 5 0 High 2450 1213 2366 1165 2282 1117 2198 1068 2114 1020 1989 993 1864 967 1739 940 Me...

Page 12: ...E KW CAP MULTIPLIER 240 208 230 75 92 480 460 92 600 575 92 TABLE 11 ELECTRICAL DATA COOLING ELECTRIC HEAT MODEL DEB POWER SUPPLY COMPRESSOR COND FAN MOTORS SUPPLY AIR BLOWER MOTOR ELECTRIC HEAT ACCES...

Page 13: ...501546 1 15 0 18 24 8 25 25 048 460 3 60 7 1 55 0 0 8 2 0 2NP04501046 1 10 0 12 17 5 20 20 2NH04501546 1 15 0 18 25 1 30 30 2NH04502046 2 20 0 24 1 32 6 35 35 2NH04502546 2 25 0 30 1 40 1 45 45 060 46...

Page 14: ...RALL 4 1 2 UNIT CONDENSATE CONNECTION NPTI TRAP REQUIRED OVERALL SIDE SUPPLY AIR OPENING SIDE RETURN AIR OPENING COMPRESSOR SERVICE ACCESS COMPARTMENT PANEL HIGH VOLTAGE CONN DIA KNOCKOUT HIGH VOLTAGE...

Page 15: ...2 UNIT WEIGHTS Unit Size Shipping Weight Operating Weight Corner Weights Economizer lbs Roof Curb lbs A B C D 030 333 328 85 81 82 86 40 8 70 14 75 036 338 333 91 80 78 88 042 347 342 94 83 80 91 048...

Page 16: ...OWER SUPPLY SUPPLY AIR DUCT RETURN AIR DUCT FIELD SUPPLIED DISCONNECT SWITCH LOCATED TO REAR OF UNIT CONTROL WIRING TO INDOOR THERMOSTAT SLAB ON GROUND INSTALLATION ROOF CURB INSTALLATION BOTTOM DUCT...

Page 17: ...ED PANELS 22 14 OPENING FOR RETURN AIR DUCT OPENING FOR SUPPLY AIR DUCT RECOMMENDED DUCT SIZE SUPPLY AIR DUCT x RETURN AIR DUCT x UNIT BASE RAIL UNIT BASE WOOD NAILER 8 MIN ABOVE FINISHED ROOF CURB FR...

Page 18: ...Controls Unitary Products FIGURE 9 TYPICAL WIRING DIAGRAM 208 230 1 60 POWER SUPPLY DEB MODELS 15695BASH0301 SEE DETAIL A T2 M1 2 DETAIL A BLK BLK CCH L1 T1 OPTIONAL CCH S P CONFIGURATION BLK BLK CCH...

Page 19: ...0508 Johnson Controls Unitary Products 19 TYPICAL WIRING DIAGRAM NOTES TYPICAL WIRING DIAGRAM LEGEND FIGURE 10 TYPICAL WIRING DIAGRAM 208 230 3 60 POWER SUPPLY DEB MODELS 6 F 9 N O T U S E D 2 M 3 2...

Page 20: ...360101 XTG B 0508 20 Johnson Controls Unitary Products FIGURE 11 TYPICAL WIRING DIAGRAM 460 3 60 AND 575 3 60 POWER SUPPLY DEB MODELS 2...

Page 21: ...and base unit 10 Condensate pan shall be internally sloped and conform to ASHRAE 62 89 self draining standards with 3 4 NPTI copper ridged mount connection INDOOR EVAPORATOR FAN ASSEMBLY 1 Fan shall b...

Page 22: ...eset to prevent the heating element system from operating at an excessive temperature 3 The heating section assembly shall slide out of the unit for easy maintenance and service 4 Units with electric...

Page 23: ...360101 XTG B 0508 Johnson Controls Unitary Products 23...

Page 24: ...change without notice Printed in U S A 360101 XTG B 0508 Copyright 2008 by Johnson Controls Inc All rights reserved Supersedes 360101 XTG A 0108 Johnson Controls Unitary Products 5005 York Drive Norma...

Reviews: