5
MODEL
DEB
POWER SUP-
PLY
VOLTAGE
LIMITATIONS
1
COMPRESSOR
COND.
FAN
MOTOR,
FLA
SUPPLY
AIR
BLOWER
MOTOR,
FLA
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE,
AMPS
2
MAX.
HACR
BREAKER
SIZE,
AMPS
UNIT
POWER
FACTOR
TRANSFORMER
SIZE (VA)
MIN.
MAX.
RLA
LRA
018
208/230-1-60
187
253
9.0
48.0
1.1
2.6
14.9
20
20
.96
40
024
208/230-1-60
187
253
11.5
60.0
1.1
2.6
18.1
25
25
.96
40
030
208/230-1-60
187
253
14.7
73.0
1.1
2.6
22.1
30
30
.96
40
036
208/230-1-60
187
253
17.3
94.0
1.1
3.5
26.2
35
35
.96
40
042
208/230-1-60
187
253
20.5
120.0
1.1
3.5
30.2
40
40
.96
40
048
208/230-1-60
187
253
24.4
140.0
1.3
4.0
35.8
45
45
.96
40
060
208/230-1-60
187
253
28.9
165.0
1.3
4.0
44.4
60
60
.96
40
= Rated in accordance with ARI Standard 110, utilization range “A”.
= Dual element, time delay type.
TABLE 4 -
ELECTRICAL DATA (BASIC UNIT)
*
= KW listed is for 240 volts, use this table for 208 or 230 volts.
ELECTRIC HEAT
CORRECTION
FACTORS
NOMINAL VOLTAGE
VOLTAGE
KW CAP. MULTI-
PLIER
240
208
230
.75
.92