background image

LIMITATIONS

These units must be installed in accordance with the following
national and local safety codes.

1. National Electrical Code ANSI/NFPS No. 70 or Canadian

Electrical Code Part 1, C22.1 (latest editions).

2. Local plumbing and waste water codes and other applica-

ble local codes.

Refer to Table 1 for unit application data and to Table 5 for elec-
tric heat application data.

If components are to be added to a unit to meet local codes, they
are to be installed at the dealer's and/or the customer's expense.

Size of unit for proposed installation should be based on heat
loss/heat gain calculations made in accordance with industry
recognized procedures identified by the Air Conditioning Con-
tractors of America.

LOCATION

Use the following guidelines to select a suitable location for
these units.

1. Unit is designed for outdoor installation only.

2. Condenser must have an unlimited supply of air. Where a

choice of location is possible, position unit on either north or
east side of building.

3. For ground level installation, a level pad or slab should be

used. The thickness and size of the pad or slab used should
meet local codes and unit weight. Do not tie the slab to the
building foundation.

4. For roof top installation, be sure the structure will support

the weight of the unit plus any field installed components.
Unit must be installed on a level roof curb or appropriate an-

gle iron frame providing adequate support under the
compressor/condenser section.

5. Maintain level tolerance of unit to 1/8" maximum.

RIGGING OR HANDLING

Care must be exercised when moving the unit. Do not remove
any packaging until the unit is near the place of installation. Rig
unit with slings placed under the unit. Spreader bars of suffi-
cient length should be used across the top of the unit.

BEFORE LIFTING A UNIT, MAKE SURE THAT ITS WEIGHT
IS DISTRIBUTED EQUALLY ON THE CABLES SO THAT IT
WILL LIFT EVENLY.

Units may also be moved or lifted with a fork-lift. Slotted open-
ings in the skid are provided for this purpose. Forks must pass
completely through the base.

Refer to Table 2 for unit weights and to Figure 1 for approximate
center of gravity.

174065-YIM-A-0206

2

Unitary Products Group

Voltage Variation

Min. / Max

.1

208/230V

3

187 / 253

3

Wet Bulb Temperature (

°

F) of Air on

Evaporator Coil,

Min. / Max.

57 / 72

Dry Bulb Temperature (

°

F) of Air on

Condenser Coil,

Min.

2

/ Max.

45 / 120

Rated in accordance with ARI Standard 110, utilization range “A”.

 

A low ambient accessory is available for operation down to 0

°

F

!

“T1" transformer primary tap must be moved from the 230 volt connection to the 208 volt

connection for low voltage applications of 208 volt and below.

TABLE 1

- UNIT APPLICATION DATA

FIG. 1

- CENTER OF GRAVITY

49

&

26

47

"

CENTER OF GRAVITY

FRONT

OF

UNIT

“A”

“B”

“C”

“D”

UNIT

SIZE

SHIPPING

WEIGHT

(lbs.)

OPERAT-

ING

WEIGHT

(lbs.)

CORNER WEIGHTS

(location, lbs.)

“A”

“B”

“C”

“D”

018

318

313

86

76

73

83

024

324

319

88

77

75

85

030

333

328

85

81

82

86

036

338

333

91

80

78

88

042

347

342

94

83

80

91

048

368

363

92

88

92

97

060

376

371

105

100

84

87

TABLE 2

- UNITS WEIGHTS

D

2

E

B

A

PRODUCT NOMENCLATURE

PRODUCT GENERATION

2 = 2nd Generation

PRODUCT CATEGORY

D = Single Package Air Conditioner

(Air Cooled)

PRODUCT IDENTIFIER

EB = 10 SEER Cooling Models

2

0

4

0

6

FACTORY

INSTALLED ELECTRIC HEAT

A = No Electric Heat Installed

VOLTAGE CODE

06 = 208/230-1-60

NOMINAL COOLING

CAPACITY (MBH)

018 = 18,000 BTUH
024 = 24,000 BTUH
030 = 30,000 BTUH
036 = 36,000 BTUH
042 = 42,000 BTUH
048 = 48,000 BTUH
060 = 60,000 BTUH

INSTALLATION

Summary of Contents for CHAMPION D2EB

Page 1: ...information on the design installation operation and service of this equipment is available in the following refer ence forms 174065 General Installation 511 26 N1 1V Electric Heater Accessory REPLACEMENT PARTS Refer to Replacement Parts Manual for complete listing of replacement parts on this equipment Installer should pay particular attention to the words NOTE CAUTION and WARNING Notes are inten...

Page 2: ...near the place of installation Rig unit with slings placed under the unit Spreader bars of suffi cient length should be used across the top of the unit BEFORE LIFTING A UNIT MAKE SURE THAT ITS WEIGHT IS DISTRIBUTED EQUALLY ON THE CABLES SO THAT IT WILL LIFT EVENLY Units may also be moved or lifted with a fork lift Slotted open ings in the skid are provided for this purpose Forks must pass complete...

Page 3: ... Filters must always be used and must be kept clean When fil ters become dirt laden insufficient air will be delivered by the blower decreasing your units efficiency and increasing operat ing costs and wear and tear on the unit and controls Filters should be checked monthly especially since this unit may be used for both heating and cooling CONDENSATE DRAIN A condensate trap is required to be inst...

Page 4: ...circuit fed directly from the meter panel and properly fused Refer to Figure 2 for typical field wiring and to the appropriate unit wiring diagram for control circuit and power wiring information COMPRESSORS Units are shipped with compressor mountings factory adjusted for shipping CAUTION Loosen compressor mounting bolts half turn before operating unit 174065 YIM A 0206 4 Unitary Products Group FI...

Page 5: ...6 40 030 208 230 1 60 187 253 14 7 73 0 1 1 2 6 22 1 30 30 96 40 036 208 230 1 60 187 253 17 3 94 0 1 1 3 5 26 2 35 35 96 40 042 208 230 1 60 187 253 20 5 120 0 1 1 3 5 30 2 40 40 96 40 048 208 230 1 60 187 253 24 4 140 0 1 3 4 0 35 8 45 45 96 40 060 208 230 1 60 187 253 28 9 165 0 1 3 4 0 44 4 60 60 96 40 Rated in accordance with ARI Standard 110 utilization range A Dual element time delay type T...

Page 6: ...1 82 5 50 60 80 90 50 60 80 90 042 208 230 1 60 20 5 120 0 1 1 3 5 2NH04500506 2NH04500706 2NH04501006 2NH04501506 1 2 2 2 3 8 5 0 5 6 7 5 7 5 10 0 11 3 15 0 18 1 20 8 27 1 31 3 36 1 41 7 54 2 62 5 30 2 30 4 38 2 43 4 49 5 56 5 72 1 82 5 40 40 50 50 50 60 80 90 40 40 50 50 50 60 80 90 048 208 230 1 60 24 4 140 0 1 3 4 0 2NH04501006 2NH04501506 2NH04502006 2NH04502506 2 2 2 2 7 5 10 0 11 3 15 0 15 ...

Page 7: ...ould be deactivated while the test is being run 4 Knowing the pressure drop across a dry coil the actual CFM through the unit can be determined from the curve in Coil Delta P vs Supply Air CFM figure WARNING Failure to properly adjust the total system air quan tity can result in extensive system damage After readings have been obtained remove the tubes and rein stall the two inch plugs removed in ...

Page 8: ...4 7 2 9 1 10 9 13 5 16 1 18 7 21 3 105 5 3 6 6 7 8 10 9 14 0 17 1 20 3 110 8 3 11 9 15 5 19 2 115 5 7 9 8 14 0 18 1 TABLE 6 SUPERHEAT CHARGING TABLE FOR MODEL D2EB018 OUTDOOR TEMPERATURE F SUPERHEAT AT COMPRESSOR SUCTION F AIRFLOW 600 CFM TON INDOOR WB TEMPERATURE F 55 57 59 61 63 65 67 69 71 73 75 65 17 8 19 8 21 8 23 9 25 9 27 9 29 9 31 1 32 3 33 6 34 8 70 12 2 14 9 17 5 20 2 22 8 25 4 28 1 29 3...

Page 9: ... 12 7 14 7 16 8 18 8 20 9 22 9 24 7 26 5 28 2 30 0 75 7 8 10 0 12 2 14 5 16 7 18 9 21 2 23 3 25 4 27 5 29 6 80 7 3 9 7 12 1 14 5 17 0 19 4 21 8 24 2 26 7 29 1 85 7 2 9 8 12 4 15 0 17 6 20 4 23 1 25 9 28 6 90 6 1 7 7 9 4 11 0 12 7 16 6 20 5 24 4 28 3 95 5 7 6 3 7 0 7 7 12 7 17 8 22 8 27 9 100 5 3 5 9 6 5 7 1 11 1 15 1 19 1 23 0 105 5 5 6 0 6 6 9 5 12 4 15 3 18 2 110 5 0 5 5 6 0 7 8 9 7 11 6 13 4 11...

Page 10: ... SUPPLY AIR OPENING BOTTOM RETURN AIR OPENING 15 14 28 3 3 28 2 3 8 13 4 13 4 13 4 3 15 14 14 BOTTOM SUPPLY AIR OPENING 2 3 8 3 47 LOW VOLTAGE CONN DIA KNOCKOUT HIGH VOLTAGE CONN 1 DIA KNOCKOUT FRONT ELECTRICAL FILTER SERVICE ACCESS COMPARTMENT PANEL OVERALL OVERALL 4 1 2 11 2 2 1 2 All dimensions are in inches They are subject to change without notice Certified dimensions will be provided upon re...

Page 11: ...send 24 volts to W1 on the fan control board The 24 volts signal will ener gize relay K2 on the fan control board and the first stage of electric heat will be energized 3 When the heating demand is satisfied the electric heat will be de energized when the 24 volt W1 and W2 signals are removed If the fan switch on the thermostat is in the ON position the indoor blower will continue to run If the fa...

Page 12: ...te on the outdoor coil surface or other parts in the air circuit Cleaning should be as often as necessary to keep the coil clean Use a brush vacuum cleaner attachment or other suitable means If water is used to clean the coil be sure that the power to the unit is shut off prior to cleaning CAUTION Exercise care when cleaning the coil so that the coil fins are not damaged Do not permit the hot cond...

Page 13: ...NDUCTORS ONLY SECONDARY POWER SUPPLY FOR DUAL POINT ELEC HEAT 208 230 1 60 USE COPPER CONDUCTORS ONLY HTR5 HTR4 HTR3 HTR2 M1 705 PR 708 PR 716 PR 713 PR 710 PR F6 F4 F2 K6 K4 K5 K3 M1 714 BK 706 BK 711 BK 703 BK 709 BK F1 F3 F5 DUAL POINT ELECTRIC HEAT SEE NOTE 9 DETAIL A SEE DETAIL B FOR DUAL POINT ELECTRIC HEAT POWER SUPPLY SEE DETAIL A ...

Page 14: ...C HEAT ELECTRIC HEATER OPT ACCSSRY 20 25 KW ELEC HEAT ELECTRIC HEATER OPT ACCSSRY 20 25 KW ELEC HEAT RELAY INDOOR FAN MOTOR RELAY ELECTRIC HEATER RELAY ELECTRIC HEATER 24 VDC COIL RELAY LIMIT TRIP 25 VDC COIL LOW PRESSURE SWITCH OPTIONAL ACCESSORY OPEN 7 PSIG LIMIT SWITCH ELECTRIC HEAT PART OF ELEC HEAT ACCESSORY CONTACTOR COMPRESSOR OUTDOOR FAN CONTACTOR ELECTRIC HEAT 230V COIL CONTACTOR ELECTRIC...

Page 15: ...Unitary Products Group 15 174065 YIM A 0206 NOTES ...

Page 16: ...Management System Unitary Products Group 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright by York International Corporation 2006 All Rights Reserved Supersedes Nothing 174065 YIM A 0206 ...

Reviews: