036-21489-001-C-1004
Unitary Products Group
23
Note 1: Maximum HACR breaker of the same amp size is acceptable.
Note 2: Only 18kW of the 36 or 54kW, or only 36kW of the 72kW electric heat can be simultaneously energized with the mechanical
heating. The full heater kW operates only if both compressors are locked out.
TABLE 11: ELECTRICAL DATA -WITHOUT POWERED CONVENIENCE OUTLET
MODEL
TONNAGE
VOLTAGE
COMPRESSORS
OD FAN
MOTORS
FLA EACH
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
AMPS
HEATER OPTION
MIN.
CIRCUIT
AMPACITY
(AMPS)
MAX.
FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
MODEL KW
2
STAGES
AMPS
BQ240
208
16.7
150
4.5
19.4
0.0
-
0.0
-
-
100.1
110
E18
13.5
1
37.5
146.9
150
E36
27.0
2
75.1
146.9
150
E54
40.6
2
112.6
165.1
175
E72
54.1
2
150.1
193.7
200
230
16.7
150
4.3
21.0
0.0
-
0.0
-
-
101.7
110
E18
18.0
1
43.3
155.8
175
E36
36.0
2
86.6
155.8
175
E54
54.0
2
129.9
156.2
175
E72
72.0
2
173.2
209.9
225
460
9.6
75
2.2
9.7
0.0
-
0.0
-
-
54.9
60
E18
18.0
1
21.7
82.0
90
E36
36.0
2
43.3
82.0
90
E54
54.0
2
65.0
82.0
90
E72
72.0
2
86.6
109.1
110
575
6.4
62
1.7
7.8
0.0
-
0.0
-
-
38.8
45
E18
18.0
1
17.3
60.4
70
E36
36.0
2
34.6
60.4
70
E54
54.0
2
52.0
61.7
70
E72
72.0
2
69.3
82.1
90