036-21489-001-C-1004
14
Unitary Products Group
EER =
Energy Efficiency Ratio at full load - the cooling capacity in BTU’s per hour
(Btuh) divided by the power input expressed in BTUH per watt (Btuh/watt).
COP
= Coefficient of Performance - the total heating capacity provided by the refrig-
eration system, including circulating fan heat, but excluding supplementary resis-
tance (Btu's per hour) divided by the total electric input (watts) x 3.412.
IPLV
= Integrated part load value. The EER of the unit operating on first stage only.
FIGURE 1 : SUNLINE 2000
TM
HEAT PUMP
HIGH EFFICIENCY COMPRESSORS
WITH CRANKCASE HEATERS
COPPER TUBE/ALUMINUM FIN
OUTDOOR COILS
LOW VOLTAGE RELAY BOARD
AND TERMINAL STRIP
ELECTRICAL DISCONNECT
MOUNTING LOCATION
(Field Installed)
TERMINAL BLOCK
(For Single Point Power Supply
With Electirc Heat)
KNOCKOUT FOR
SIDE CONTROL WIRING AND
SIDE POWER WIRING ENTRY
BOTTOM & CONTROL
WIRING ENTRY
ELECTRIC HEATER LOCATION
(OPTION)
BELT-DRIVE
BLOWER MOTOR
FULL PERIMTER 14 GUAGE BASE
RAILS WITH LIFTING HOLES
NPT FEMALE
CONDENSATE DRAIN
SIDE AND BOTTOM
SUPPLY & RETURN AIR
OUTDOOR AIR OPENING
FOR INTERNAL ECONOMIZER
2" DISPOSABLE
FILTERS
ECONOMIZER HOOD
LONG LASTING POWDER PAINT FINISH
TABLE 1: RATINGS
MODEL
COOLING CAPACITY
1
80//67-95º F
1. Certified in accordance with the Unitary Large Equipment Certifi-
cation Program which is based on ARI Standard 340/360.
HEATING CAPACITY
1
ELECTRIC
HEAT
NOM.
CAPACITY
2
(KW)
2. Models with electric heat have single point power supply.
47º F
17º F
MBH
EER
IPLV
MBH COP MBH COP
KW
BQ240
222
8.5
7.5
226
3.0
120
2.0
18,36,54,72
HEAT PUMP WITH ELECTRIC HEAT
MODEL
MBH
EER
IPLV
BQ240E18
222
8.5
7.5
BQ240E36
222
8.5
7.5
BQ240E54
220
8.5
7.4
BQ240E72
218
8.5
7.4
TABLE 2: INDOOR SOUND POWER RATINGS
Unit
Size
CFM
ESP
Blower
Sound Power (db 10
-12
Watts)
Octave B and Centerline Frequency (Hz)
SWL db(A)
db(A)@ 10 Ft.
1
IWG
RPM
BHP
63
125
250
500
1,000
2,000
4,000
8,000
BQ240
8,000
1.00
1,020
6.65
102
102
92
85
87
80
75
70
92
59
1. At a distance of 10 ft. from the blower.
NOTE: These values have been derived using a model of sound propagation, measuring the indoor ambient sound levels ten feet from the source.
The dBA values provided are for reference only. Calculation for dBA values cover matters of system design and application. This constitutes
an exception to any specification or guarantee requiring a dBA value or sound data in any other form than sound power level ratings.