FEATURES

All models are available with a wide variety of factory-
mounted options such as electric heaters, phase monitor, 
convenience outlet, dirty filter switch, disconnect switch, 
smoke detectors, and coil guards to make them suitable for 
almost every application.

All units are self-contained and assembled on full perimeter 
base rails with forklift holes on three sides and holes for over-
head rigging. Every unit is completely piped, wired, charged 
and tested at the factory to simplify the field installation and to 
provide years of dependable operation.

All models (including those with an economizer) are suitable 
for either bottom or horizontal duct connections. For bottom 
duct, remove the sheet metal panels from the supply and 
return air openings through the base of the unit. For horizon-
tal duct, remove the supply and return air panels on the rear 
of the unit.

All models are available with these “factory mounted” outdoor 
air damper options:

Single enthalpy economizer

Motorized outdoor air damper

Supply air blowers are equipped with either a direct drive or a 
belt drive that can be adjusted to meet the exact require-
ments of the job.

All compressors are equipped with internal pressure relief. 
Every refrigerant circuit includes a liquid line filter-drier, a high 
pressure switch and a suction line with a freezestat and low 
pressure/loss of charge switch to protect all system compo-
nents.

Simplicity

™ 

Controls - 

Simplicity

™ control boards have 

standardized a number of features previously available 
only as options or by utilizing additional controls.

Low Ambient 

- An integrated low-ambient control 

allows all units to operate in the cooling mode down 
to 0ºF outdoor ambient without additional assis-
tance. Optionally, the control board can be pro-
grammed to lockout the compressors when the 
outdoor air temperature is low or when free cooling 
is available.

Anti-Short Cycle Protection

 - To aid compressor 

life, an anti-short cycle delay is incorporated into the 
standard controls. Compressor reliability is further 
ensured by programmable minimum run times. For 
testing, the anti short cycle delay can be temporarily 
overridden with the push of a button.

Fan Delays

 - Fan on and fan off delays are fully pro-

grammable and are independent of one another. All 
units are programmed with default values based 
upon their configuration of cooling and heat.

Safety Monitoring

 - The control board monitors the 

high and low-pressure switches, the freezestats, the 
gas valve, if applicable, and the temperature limit 
switch on gas heat units. The unit control board will 
alarm on ignition failures, compressor lockouts and 
repeated limit switch trips.

Nuisance Trip Protection

- To prevent nuisance 

trouble calls, the control board uses a “three strikes, 
you’re out” philosophy. The high and low-pressure 
switches and the freezestats must trip three times 
within two hours before the unit control board will 
lock out the compressor.

On Board Diagnostics

 - Each alarm will energize a 

trouble light on the thermostat, if so equipped, and 
flash an alarm code on the control board LED. Each 
high and low-pressure switch alarm as well as each 
freezestat alarm has its own flash code. The control 
board saves the five most recent alarms in memory, 
and these alarms can be reviewed at any time. 
Alarms and programmed values are retained 
through the loss of power.

All units have long lasting powder paint cabinets with 750 
hour salt spray test approval under ASTM-B117 procedures.

All models are CSA listed.

Warranty

 - All models include a one-year limited parts 

warranty on the complete unit. Compressors and electric 
heater elements carry a five-year warranty

Electric Heat Operation

 - All electric heat models are 

wired for a single power source and include a bank of 
nickel chromium elements mounted at the discharge of 
the supply air blower to provide a high velocity and uni-
form distribution of air across the heating elements. 
Every element is fully protected against excessive tem-
perature by thermal limit switches.

The power supply wiring can be routed into the control 
box through a threaded pipe connection (field supplied) 
in the base pan of the unit or through a knockout in the 
wiring panel on the side of the unit.

BAS Controls

 - York’s Sunline™ series units offer fac-

tory mounted BAS controls such as 

SImplicity

™ 

INTELLI-Comfort™, Novar, Honeywell, Johnson, and 
CPC.

Summary of Contents for BQ 036

Page 1: ...or frame All units include Powder Paint finish that meets ASTM B 117 1000 hour salt spray standards Permanently lubricated motors Bottom or side air discharge configuration capability field convertibl...

Page 2: ...9 SUPPLY AIR BLOWER PERFORMANCE 5 TON BELT DRIVE SIDE DUCT APPLICATION 22 10 SUPPLY AIR BLOWER PERFORMANCE 3 5 TON DIRECT DRIVE SIDE DUCT APPLICATION 23 11 BELT DRIVE BLOWER MOTOR AND DRIVE DATA 23 1...

Page 3: ...ion 1 C Option 2 D Options 1 2 E Option 3 F Option 4 G Options 1 3 H Options 1 4 J Options 1 2 3 K Options 1 2 4 L Options 1 3 4 M Options 1 2 3 4 N Options 2 3 P Options 2 4 Q Options 2 3 4 R Options...

Page 4: ...ase Monitor CQ CPC Controller DFS APS Technicoat Evap Cond Coils Coil Guard CR CPC Controller DFS APS Technicoat Evap Cond Coils Phase Monitor Coil Guard CS CPC Controller DFS APS SS Drain Pan CT CPC...

Page 5: ...Controller DFS APS SS Drain Pan Phase Monitor Coil Guard HU Honeywell Excel 10 Controller DFS APS SS Drain Pan Technicoat Cond Coils HV Honeywell Excel 10 Controller DFS APS SS Drain Pan Technicoat Ev...

Page 6: ...Intelli Comfort Controller LB Simplicity Intelli Comfort Controller Phase Monitor LC Simplicity Intelli Comfort Controller Coil Guard LD Simplicity Intelli Comfort Controller Phase Monitor Coil Guard...

Page 7: ...S Drain Pan Dirty Filter Switch Hinged Filter Door Toolless Access Panels BN SS Drain Pan Phase Monitor Coil Guard Dirty Filter Switch Hinged Filter Door Toolless Access Panels BS Bottom Drain Connect...

Page 8: ...FS APS SS Drain Pan Phase Monitor Coil Guard Technicoat Evap and Cond Coils Hinged Filter Door Toolless Access Panels GA Honeywell Excel 10 Controller with Dirty Filter Switch Air Proving Switch Hinge...

Page 9: ...Guard Dirty Filter Switch Hinged Filter Door Toolless Access Panels UH Technicoat Condenser Coil Phase Monitor Coil Guard Dirty Filter Switch Hinged Filter Door Toolless Access Panels UJ Technicoat E...

Page 10: ...oller Hinged Filter Door Toolless Access Panels XB Intelli Comfort w Mod Link Controller Phase Monitor Hinged Filter Door Toolless Access Panels XC Intelli Comfort w Mod Link Controller Coil Guard Hin...

Page 11: ...nimum run times For testing the anti short cycle delay can be temporarily overridden with the push of a button Fan Delays Fan on and fan off delays are fully pro grammable and are independent of one a...

Page 12: ...e complete coil for maximum protection ELECTRIC HEATERS Wired for single point power supply These nickel chromium heater elements are pro vided with limit and automatic reset capability to prevent ope...

Page 13: ...p operation of the unit by interrupting power to the control board if smoke is detected within the air compartment STAINLESS STEEL DRAIN PAN An optional rust proof stainless steel drain pan is availab...

Page 14: ...without power exhaust This accessory includes a rain hood a bird screen and a fully assembled damper With bottom duct connections the damper should be mounted over the opening in the return air panel...

Page 15: ...048 48 10 20 9 25 8 6 6 7 48 0 3 0 26 4 2 0 060 59 10 00 9 20 8 4 7 0 59 0 3 0 36 0 2 1 HSPF UNIT SIZE MBH ARI RATINGS1 HEATING CAPACITY 47 F 17 F COOLING PERFORMANCE SOUND RATING2 bels NOTES 1 Certi...

Page 16: ...8 25 22 18 15 11 62 34 3 9 34 34 33 30 26 23 19 33 4 1 33 33 32 29 25 22 19 57 34 3 9 34 34 34 31 28 24 20 32 4 1 32 32 32 29 26 22 19 72 42 4 0 28 25 21 17 14 39 4 2 26 23 19 16 13 67 37 4 0 32 30 26...

Page 17: ...42 4 6 42 42 41 37 32 27 22 39 4 8 39 39 37 34 29 24 19 57 42 4 5 42 42 42 37 33 27 23 38 4 7 38 38 38 33 30 25 20 72 49 4 8 35 31 26 22 46 5 1 34 29 25 20 67 44 4 6 40 40 35 31 26 22 39 4 9 36 36 32...

Page 18: ...53 5 8 53 53 52 46 40 34 28 49 6 5 49 49 47 42 36 30 24 57 53 5 8 53 53 52 46 41 35 27 49 6 4 49 49 48 43 37 31 25 72 62 5 9 45 39 34 28 59 6 8 44 38 33 27 67 57 5 9 51 49 44 38 33 27 53 6 5 45 45 42...

Page 19: ...9 24 9 32 1 39 4 47 6 54 5 KW 3 6 3 7 4 4 4 1 4 4 5 5 7 MBH 12 1 17 22 27 7 34 5 42 3 51 2 58 6 KW 3 3 3 4 3 5 3 6 3 6 3 8 4 4 5 MBH 11 6 16 3 21 2 26 6 33 2 40 7 49 2 56 3 KW 3 4 3 5 3 6 3 7 3 8 4 4...

Page 20: ...M WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2000 1103 1270 1900 1085 1210 1800 1064 1145 1102 1180 1700 1040 1075 1081 1115 1121 1140 1600 1020 1005 1060 1050 1100 1085 1500 10...

Page 21: ...M WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2000 1103 1270 1900 1085 1210 1800 1064 1145 1102 1180 1700 1040 1075 1081 1115 1121 1140 1600 1020 1005 1060 1050 1100 1085 1500 10...

Page 22: ...65 830 RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2500 2400 1193 1665 2300 1170 1580 1202 1620 2200 1148 1480 1180 1530 2100 1121 1385 1155 1425 1190 1475 2000 1100 1285 113...

Page 23: ...0 LOW 2030 1070 1960 1020 1890 970 1810 920 3 1 4 1 0 70 AVAILABLE EXTERNAL STATIC PRESSURE IWG2 0 90 0 80 1 00 3 1 4 1 5 1 AVAILABLE EXTERNAL STATIC PRESSURE IWG2 5 1 0 60 0 20 0 30 0 40 0 50 UNIT TO...

Page 24: ...RMANCE Tables 2 The pressure through the economizer is greater for 100 outdoor air than for 100 return air If the resistance of the return air duct system is less than 0 25 IWG the unit will deliver l...

Page 25: ...10706 7 5 31 3 77 6 90 2CE04511006 10 6 44 2 93 8 100 2CE04511506 15 9 66 3 121 4 125 2CE04512006 21 2 88 3 149 0 150 NONE 0 0 0 0 25 7 40 2CE045105252 4 0 11 1 39 6 50 2CE04510725 2 5 6 15 5 45 1 50...

Page 26: ...5 10 6 25 5 64 9 70 2CE04511525 15 9 38 2 80 8 90 2CE04512025 21 2 51 0 96 8 100 2CE04513025 29 6 71 2 122 0 125 NONE 0 0 0 0 17 1 25 2CE045107462 6 8 8 2 27 3 35 2CE045110462 10 1 12 1 32 3 35 2CE045...

Page 27: ...11006 10 6 44 2 94 0 100 2CE04511506 15 9 66 3 121 6 125 2CE04512006 21 2 88 3 149 2 150 NONE 0 0 25 9 40 2CE04510525 2 4 0 11 1 39 8 50 2CE045107252 5 6 15 5 45 3 50 2CE04511025 8 0 22 2 53 6 60 2CE0...

Page 28: ...5 10 6 25 5 63 5 70 2CE04511525 15 9 38 2 79 4 80 2CE04512025 21 2 51 0 95 4 100 2CE04513025 29 6 71 2 120 6 125 NONE 0 0 0 0 16 4 25 2CE045107462 6 8 8 2 26 6 30 2CE045110462 10 1 12 1 31 6 35 2CE045...

Page 29: ...10 6 44 2 103 8 110 2CE04511506 15 9 66 3 131 4 150 2CE04512006 21 2 88 3 159 0 175 NONE 0 0 35 7 50 2CE04510525 2 4 0 11 1 49 6 60 2CE045107252 5 6 15 5 55 1 60 2CE04511025 8 0 22 2 63 4 70 2CE045115...

Page 30: ...0 6 25 5 74 9 80 2CE04511525 15 9 38 2 90 8 100 2CE04512025 21 2 51 0 106 8 110 2CE04513025 29 6 71 2 132 0 150 NONE 0 0 0 0 22 1 30 2CE045107462 6 8 8 2 32 3 40 2CE045110462 10 1 12 1 37 3 40 2CE0451...

Page 31: ...10 6 44 2 106 4 110 2CE04511506 15 9 66 3 134 0 150 2CE04512006 21 2 88 3 161 6 175 NONE 0 0 35 9 50 2CE04510525 2 4 0 0 0 11 1 49 8 60 2CE045107252 5 6 15 5 55 3 60 2CE04511025 8 0 22 2 63 6 70 2CE0...

Page 32: ...0 6 25 5 73 5 80 2CE04511525 15 9 38 2 89 4 90 2CE04512025 21 2 51 0 105 4 110 2CE04513025 29 6 71 2 130 6 150 NONE 0 0 0 0 21 4 30 2CE045107462 6 8 8 2 31 6 35 2CE045110462 10 1 12 1 36 6 40 2CE04511...

Page 33: ...CONDENSER COILS Rows Deep 1 1 1 Fins Per Inch 20 20 20 Face Area Sq Ft 17 1 17 1 17 1 COMPRESSOR Qty Per Unit Reciprocating Type 1 1 1 AIR FILTERS Quantity Per Unit 15 X 20 X 1 or 2 2 2 2 Quantity Pe...

Page 34: ...TRANSFORMER TO REMOTE SENSOR 2TH040702224 IF USED NOT USED ADD JUMPER ADD JUMPER 4 4 3 2 1 ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET04700224 INCLUDES SUBBASE 2 SECOND STAGE COOLING IS NOT REQUIRED ON UN...

Page 35: ...036 21508 005 A 0305 Unitary Products Group 35 FIGURE 3 UNIT DIMENSIONS 3 5 TON HEAT PUMP FRONT VIEW FIGURE 4 UNIT WITH ECONOMIZER RAINHOOD DETAIL A...

Page 36: ...036 21508 005 A 0305 36 Unitary Products Group FIGURE 5 UNIT WITH FIXED OUTDOOR AIR MOTORIZED DAMPER RAINHOOD DETAIL B FIGURE 6 UNIT DIMENSIONS REAR VIEW...

Page 37: ...Wiring Side Bottom C 1 5 8 KO Gas Piping Front D 1 1 2 KO Gas Piping Bottom 1 Opening in the bottom to the unit can be located by the side in the insulation 2 Do not remove the 2 knockout ring TABLE 2...

Page 38: ...036 21508 005 A 0305 38 Unitary Products Group FIGURE 8 TYPICAL APPLICATIONS...

Page 39: ...A B C D BQ036 628 139 137 174 177 BQ048 668 148 146 185 189 BQ060 693 154 151 192 196 TABLE 28 BQ 6 POINT LOADS WEIGHT DISTRIBUTION UNIT TOTAL A B C D E F BQ036 628 93 92 91 116 117 119 BQ048 668 99 9...

Page 40: ...ure switch and a suction line with a freezestat and low pressure loss of charge switch The unit control circuit includes a 75 VA transformer a 24 volt circuit breaker and a relay board with a compress...

Page 41: ...l have internal spring isolation and sound muf fling to minimize vibration and noise and be exter nally isolated on a dedicated independent mounting Coils a Evaporator and condenser coils shall have a...

Page 42: ...o prevent the supply air temperature from dropping below 55 F Changeover from compressor to economizer oper ation shall be provided by an integral electronic enthalpy control that feeds input into the...

Page 43: ...mfort CPC JOHNSON HONEYWELL NOVAR BAS READY ECONOMIZER BELIMO ACTUATOR WITHOUT A CONTROLLER HINGED FILTER DOOR ACCESS AND TOOLESS ACCESS PANELS STAINLESS STEEL DRAIN PAN BOTTOM DRAIN CONNECTION 2 PLEA...

Page 44: ...o change without notice Printed in U S A 036 21508 005 A 0305 Copyright 2005 by Unitary Products Group All rights reserved Supersedes 036 21508 004 A 0504 Unitary 5005 Norman Products York OK Group Dr...

Reviews: