background image

036-21508-005-A-0305

42

Unitary Products Group

matic reset to prevent the heating element system from oper-
ating at an excessive temperature. The heating section 
assembly shall slide out of the unit for easy maintenance and 
service. Units with Electric Heating shall be wired for a single 
point power supply with branch circuit fusing (where 
required).

UNIT OPERATING CHARACTERISTICS

a.

Unit shall be capable of starting and running at 
125°F outdoor temperature, exceeding maximum 
load criteria of ARI Standard 210/240. The compres-
sor, with standard controls, shall be capable of oper-
ation down to 0°F outdoor temperature. Unit shall be 
provided with fan time delay to prevent cold air 
delivery before heat exchanger warms up (Gas heat 
only).

ELECTRICAL REQUIREMENTS

All unit power wiring shall enter unit cabinet at a single factory 
provided location and be capable of side or bottom entry, to 
minimize roof penetrations and avoid unit field modifications. 
Separate side and bottom openings shall be provided for the 
control wiring.

STANDARD LIMITED WARRANTIES

Compressor 5 Years

Electric Heat Element 5 Years

Other Parts 1 Year

OPTIONAL OUTDOOR AIR 

(Shall be made available by 

either/or):

ELECTRONIC ENTHALPY AUTOMATIC ECONO-
MIZER

- Outdoor and return air dampers that are inter-

locked and positioned by a fully-modulating, spring 
return damper actuator. The maximum leakage rate for 
the outdoor air intake dampers shall not exceed 2% 
when dampers are fully closed and operating against a 
pressure differential of 0.5 IWG. A unit-mounted potenti-
ometer shall be provided to adjust the outdoor and return 
air damper assembly to take in CFM of outdoor air to 
meet the minimum ventilation requirement of the condi-
tioned space during normal operation. During econo-
mizer operation, a mixed-air temperature control shall 
modulate the outdoor and return air damper assembly to 
prevent the supply air temperature from dropping below 
55°F. Changeover from compressor to economizer oper-
ation shall be provided by an integral electronic enthalpy 
control that feeds input into the basic module. The out-
door intake opening shall be covered with a rain hood 
that matches the exterior of the unit. Water eliminator/fil-
ters shall be provided. Simultaneous economizer/com-
pressor operation is also possible. Dampers shall fully 
close on power loss.

MOTORIZED OUTDOOR AIR DAMPERS

 - Outdoor air 

dampers are positioned by a 2-position, spring-return 
damper actuator. The maximum leakage rate for the out-
door air intake dampers shall not exceed 2% when 
dampers are fully closed and operating against a pres-
sure differential of 0.5 IWG. A unit-mounted potentiome-
ter shall be provided to adjust the outdoor damper 
assembly to take in the design CFM of outdoor air to 
meet the ventilation requirements of the conditioned 
space during normal operation. Whenever the indoor fan 
motor is energized, the dampers open up to one of two 
pre-selected positions - regardless of the outdoor air 
enthalpy. Dampers return to the fully closed position 
when the indoor fan motor is de-energized. Dampers 
shall fully close on power loss.

OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE

ROOF CURB

 - 14"and 8”  high, full perimeter curb with 

wood nailer (shipped knocked-down).

BAROMETRIC RELIEF DAMPER

 - Contains a rain 

hood, air inlet screen, exhaust damper and mounting 
hardware. Used to relieve internal air pressure through 
the unit.

POWER EXHAUST OPTION

 - To work in conjunction 

with economizers.

ELECTRIC HEATERS

ECONOMIZER/MOTORIZED DAMPER RAIN HOOD

 -

Contains all hood panels and the hardware for assem-
bling.

MANUAL OUTDOOR AIR DAMPER

COIL GUARD KIT

 - Guard for cooling coil.

HAIL GUARD

OTHER FACTORY INSTALLED OPTIONS

POWER EXHAUST OPTION

 - To work in conjunction 

with economizers.

TECHNICOAT PHENOLIC COATED CONDENSER 
AND EVAPORATOR COIL

ELECTRONIC SINGLE ENTHALPY ECONOMIZER

DIRTY FILTER SWITCH

PHASE MONITOR

COIL GUARD

POWERED GFI CONVENIENCE OUTLET

NON-POWERED GFI CONVENIENCE OUTLET

Summary of Contents for BQ 036

Page 1: ...or frame All units include Powder Paint finish that meets ASTM B 117 1000 hour salt spray standards Permanently lubricated motors Bottom or side air discharge configuration capability field convertibl...

Page 2: ...9 SUPPLY AIR BLOWER PERFORMANCE 5 TON BELT DRIVE SIDE DUCT APPLICATION 22 10 SUPPLY AIR BLOWER PERFORMANCE 3 5 TON DIRECT DRIVE SIDE DUCT APPLICATION 23 11 BELT DRIVE BLOWER MOTOR AND DRIVE DATA 23 1...

Page 3: ...ion 1 C Option 2 D Options 1 2 E Option 3 F Option 4 G Options 1 3 H Options 1 4 J Options 1 2 3 K Options 1 2 4 L Options 1 3 4 M Options 1 2 3 4 N Options 2 3 P Options 2 4 Q Options 2 3 4 R Options...

Page 4: ...ase Monitor CQ CPC Controller DFS APS Technicoat Evap Cond Coils Coil Guard CR CPC Controller DFS APS Technicoat Evap Cond Coils Phase Monitor Coil Guard CS CPC Controller DFS APS SS Drain Pan CT CPC...

Page 5: ...Controller DFS APS SS Drain Pan Phase Monitor Coil Guard HU Honeywell Excel 10 Controller DFS APS SS Drain Pan Technicoat Cond Coils HV Honeywell Excel 10 Controller DFS APS SS Drain Pan Technicoat Ev...

Page 6: ...Intelli Comfort Controller LB Simplicity Intelli Comfort Controller Phase Monitor LC Simplicity Intelli Comfort Controller Coil Guard LD Simplicity Intelli Comfort Controller Phase Monitor Coil Guard...

Page 7: ...S Drain Pan Dirty Filter Switch Hinged Filter Door Toolless Access Panels BN SS Drain Pan Phase Monitor Coil Guard Dirty Filter Switch Hinged Filter Door Toolless Access Panels BS Bottom Drain Connect...

Page 8: ...FS APS SS Drain Pan Phase Monitor Coil Guard Technicoat Evap and Cond Coils Hinged Filter Door Toolless Access Panels GA Honeywell Excel 10 Controller with Dirty Filter Switch Air Proving Switch Hinge...

Page 9: ...Guard Dirty Filter Switch Hinged Filter Door Toolless Access Panels UH Technicoat Condenser Coil Phase Monitor Coil Guard Dirty Filter Switch Hinged Filter Door Toolless Access Panels UJ Technicoat E...

Page 10: ...oller Hinged Filter Door Toolless Access Panels XB Intelli Comfort w Mod Link Controller Phase Monitor Hinged Filter Door Toolless Access Panels XC Intelli Comfort w Mod Link Controller Coil Guard Hin...

Page 11: ...nimum run times For testing the anti short cycle delay can be temporarily overridden with the push of a button Fan Delays Fan on and fan off delays are fully pro grammable and are independent of one a...

Page 12: ...e complete coil for maximum protection ELECTRIC HEATERS Wired for single point power supply These nickel chromium heater elements are pro vided with limit and automatic reset capability to prevent ope...

Page 13: ...p operation of the unit by interrupting power to the control board if smoke is detected within the air compartment STAINLESS STEEL DRAIN PAN An optional rust proof stainless steel drain pan is availab...

Page 14: ...without power exhaust This accessory includes a rain hood a bird screen and a fully assembled damper With bottom duct connections the damper should be mounted over the opening in the return air panel...

Page 15: ...048 48 10 20 9 25 8 6 6 7 48 0 3 0 26 4 2 0 060 59 10 00 9 20 8 4 7 0 59 0 3 0 36 0 2 1 HSPF UNIT SIZE MBH ARI RATINGS1 HEATING CAPACITY 47 F 17 F COOLING PERFORMANCE SOUND RATING2 bels NOTES 1 Certi...

Page 16: ...8 25 22 18 15 11 62 34 3 9 34 34 33 30 26 23 19 33 4 1 33 33 32 29 25 22 19 57 34 3 9 34 34 34 31 28 24 20 32 4 1 32 32 32 29 26 22 19 72 42 4 0 28 25 21 17 14 39 4 2 26 23 19 16 13 67 37 4 0 32 30 26...

Page 17: ...42 4 6 42 42 41 37 32 27 22 39 4 8 39 39 37 34 29 24 19 57 42 4 5 42 42 42 37 33 27 23 38 4 7 38 38 38 33 30 25 20 72 49 4 8 35 31 26 22 46 5 1 34 29 25 20 67 44 4 6 40 40 35 31 26 22 39 4 9 36 36 32...

Page 18: ...53 5 8 53 53 52 46 40 34 28 49 6 5 49 49 47 42 36 30 24 57 53 5 8 53 53 52 46 41 35 27 49 6 4 49 49 48 43 37 31 25 72 62 5 9 45 39 34 28 59 6 8 44 38 33 27 67 57 5 9 51 49 44 38 33 27 53 6 5 45 45 42...

Page 19: ...9 24 9 32 1 39 4 47 6 54 5 KW 3 6 3 7 4 4 4 1 4 4 5 5 7 MBH 12 1 17 22 27 7 34 5 42 3 51 2 58 6 KW 3 3 3 4 3 5 3 6 3 6 3 8 4 4 5 MBH 11 6 16 3 21 2 26 6 33 2 40 7 49 2 56 3 KW 3 4 3 5 3 6 3 7 3 8 4 4...

Page 20: ...M WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2000 1103 1270 1900 1085 1210 1800 1064 1145 1102 1180 1700 1040 1075 1081 1115 1121 1140 1600 1020 1005 1060 1050 1100 1085 1500 10...

Page 21: ...M WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2000 1103 1270 1900 1085 1210 1800 1064 1145 1102 1180 1700 1040 1075 1081 1115 1121 1140 1600 1020 1005 1060 1050 1100 1085 1500 10...

Page 22: ...65 830 RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2500 2400 1193 1665 2300 1170 1580 1202 1620 2200 1148 1480 1180 1530 2100 1121 1385 1155 1425 1190 1475 2000 1100 1285 113...

Page 23: ...0 LOW 2030 1070 1960 1020 1890 970 1810 920 3 1 4 1 0 70 AVAILABLE EXTERNAL STATIC PRESSURE IWG2 0 90 0 80 1 00 3 1 4 1 5 1 AVAILABLE EXTERNAL STATIC PRESSURE IWG2 5 1 0 60 0 20 0 30 0 40 0 50 UNIT TO...

Page 24: ...RMANCE Tables 2 The pressure through the economizer is greater for 100 outdoor air than for 100 return air If the resistance of the return air duct system is less than 0 25 IWG the unit will deliver l...

Page 25: ...10706 7 5 31 3 77 6 90 2CE04511006 10 6 44 2 93 8 100 2CE04511506 15 9 66 3 121 4 125 2CE04512006 21 2 88 3 149 0 150 NONE 0 0 0 0 25 7 40 2CE045105252 4 0 11 1 39 6 50 2CE04510725 2 5 6 15 5 45 1 50...

Page 26: ...5 10 6 25 5 64 9 70 2CE04511525 15 9 38 2 80 8 90 2CE04512025 21 2 51 0 96 8 100 2CE04513025 29 6 71 2 122 0 125 NONE 0 0 0 0 17 1 25 2CE045107462 6 8 8 2 27 3 35 2CE045110462 10 1 12 1 32 3 35 2CE045...

Page 27: ...11006 10 6 44 2 94 0 100 2CE04511506 15 9 66 3 121 6 125 2CE04512006 21 2 88 3 149 2 150 NONE 0 0 25 9 40 2CE04510525 2 4 0 11 1 39 8 50 2CE045107252 5 6 15 5 45 3 50 2CE04511025 8 0 22 2 53 6 60 2CE0...

Page 28: ...5 10 6 25 5 63 5 70 2CE04511525 15 9 38 2 79 4 80 2CE04512025 21 2 51 0 95 4 100 2CE04513025 29 6 71 2 120 6 125 NONE 0 0 0 0 16 4 25 2CE045107462 6 8 8 2 26 6 30 2CE045110462 10 1 12 1 31 6 35 2CE045...

Page 29: ...10 6 44 2 103 8 110 2CE04511506 15 9 66 3 131 4 150 2CE04512006 21 2 88 3 159 0 175 NONE 0 0 35 7 50 2CE04510525 2 4 0 11 1 49 6 60 2CE045107252 5 6 15 5 55 1 60 2CE04511025 8 0 22 2 63 4 70 2CE045115...

Page 30: ...0 6 25 5 74 9 80 2CE04511525 15 9 38 2 90 8 100 2CE04512025 21 2 51 0 106 8 110 2CE04513025 29 6 71 2 132 0 150 NONE 0 0 0 0 22 1 30 2CE045107462 6 8 8 2 32 3 40 2CE045110462 10 1 12 1 37 3 40 2CE0451...

Page 31: ...10 6 44 2 106 4 110 2CE04511506 15 9 66 3 134 0 150 2CE04512006 21 2 88 3 161 6 175 NONE 0 0 35 9 50 2CE04510525 2 4 0 0 0 11 1 49 8 60 2CE045107252 5 6 15 5 55 3 60 2CE04511025 8 0 22 2 63 6 70 2CE0...

Page 32: ...0 6 25 5 73 5 80 2CE04511525 15 9 38 2 89 4 90 2CE04512025 21 2 51 0 105 4 110 2CE04513025 29 6 71 2 130 6 150 NONE 0 0 0 0 21 4 30 2CE045107462 6 8 8 2 31 6 35 2CE045110462 10 1 12 1 36 6 40 2CE04511...

Page 33: ...CONDENSER COILS Rows Deep 1 1 1 Fins Per Inch 20 20 20 Face Area Sq Ft 17 1 17 1 17 1 COMPRESSOR Qty Per Unit Reciprocating Type 1 1 1 AIR FILTERS Quantity Per Unit 15 X 20 X 1 or 2 2 2 2 Quantity Pe...

Page 34: ...TRANSFORMER TO REMOTE SENSOR 2TH040702224 IF USED NOT USED ADD JUMPER ADD JUMPER 4 4 3 2 1 ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET04700224 INCLUDES SUBBASE 2 SECOND STAGE COOLING IS NOT REQUIRED ON UN...

Page 35: ...036 21508 005 A 0305 Unitary Products Group 35 FIGURE 3 UNIT DIMENSIONS 3 5 TON HEAT PUMP FRONT VIEW FIGURE 4 UNIT WITH ECONOMIZER RAINHOOD DETAIL A...

Page 36: ...036 21508 005 A 0305 36 Unitary Products Group FIGURE 5 UNIT WITH FIXED OUTDOOR AIR MOTORIZED DAMPER RAINHOOD DETAIL B FIGURE 6 UNIT DIMENSIONS REAR VIEW...

Page 37: ...Wiring Side Bottom C 1 5 8 KO Gas Piping Front D 1 1 2 KO Gas Piping Bottom 1 Opening in the bottom to the unit can be located by the side in the insulation 2 Do not remove the 2 knockout ring TABLE 2...

Page 38: ...036 21508 005 A 0305 38 Unitary Products Group FIGURE 8 TYPICAL APPLICATIONS...

Page 39: ...A B C D BQ036 628 139 137 174 177 BQ048 668 148 146 185 189 BQ060 693 154 151 192 196 TABLE 28 BQ 6 POINT LOADS WEIGHT DISTRIBUTION UNIT TOTAL A B C D E F BQ036 628 93 92 91 116 117 119 BQ048 668 99 9...

Page 40: ...ure switch and a suction line with a freezestat and low pressure loss of charge switch The unit control circuit includes a 75 VA transformer a 24 volt circuit breaker and a relay board with a compress...

Page 41: ...l have internal spring isolation and sound muf fling to minimize vibration and noise and be exter nally isolated on a dedicated independent mounting Coils a Evaporator and condenser coils shall have a...

Page 42: ...o prevent the supply air temperature from dropping below 55 F Changeover from compressor to economizer oper ation shall be provided by an integral electronic enthalpy control that feeds input into the...

Page 43: ...mfort CPC JOHNSON HONEYWELL NOVAR BAS READY ECONOMIZER BELIMO ACTUATOR WITHOUT A CONTROLLER HINGED FILTER DOOR ACCESS AND TOOLESS ACCESS PANELS STAINLESS STEEL DRAIN PAN BOTTOM DRAIN CONNECTION 2 PLEA...

Page 44: ...o change without notice Printed in U S A 036 21508 005 A 0305 Copyright 2005 by Unitary Products Group All rights reserved Supersedes 036 21508 004 A 0504 Unitary 5005 Norman Products York OK Group Dr...