GUIDE SPECIFICATIONS

GENERAL

Units shall be manufactured by York International Unitary 
Products Group in an ISO 9001 certified facility.

York's Sunline 2000

TM

 units are convertible single package 

heat pumps. Although the units are primarily designed for 
curb mounting on a roof, they can also be slab-mounted at 
ground level or set on steel beams above a finished roof. 
Models are available with a wide variety of factory-mounted 
options and field-installed accessories to make them suitable 
for almost every application. All units are self-contained and 
assembled on full perimeter base rails with holes in the four 
corners for overhead rigging. Every unit is completely piped, 
wired, charged and tested at the factory to simplify the field 
installation and to provide years of dependable operation. All 
models (including those with an economizer) are suitable for 
either bottom or horizontal duct connections. Models with 
power exhaust are suitable for bottom duct connections only. 
For bottom duct, remove the sheet metal panels from the 
supply and return air openings through the base of the unit. 
For horizontal duct, remove the supply and return air panels 
on the rear of the unit. 

All non-Scroll compressors include crankcase heaters and all 
compressors have internal pressure relief. Every refrigerant 
circuit includes a liquid line filter-drier, a discharge line high 
pressure switch and a suction line with a freezestat and low 
pressure/loss of charge switch.The unit control circuit 

includes a 75 VA transformer, a 24-volt circuit breaker and a 
relay board with a compressor lockout circuit, a terminal strip 
for thermostat wiring, plus an additional set of pin connectors 
to simplify the interface of additional field controls. All units 
have long lasting powder paint cabinets with 750 hour salt 
spray test approval under ASTMB117 procedures. All models 
are CSA listed. All models include a 1-year limited warranty 
on the complete unit. Compressors and electric heater ele-
ments carry a 5-year warranty. 

DESCRIPTION

Units shall be factory-assembled, single packaged heat 
pumps designed for outdoor mounted installation.

The units shall have minimum EER ratings of 10.2. They shall 
have built-in field convertible duct connections for down dis-
charge supply/return or horizontal discharge supply/return, 
and be available with factory installed options or field installed 
accessories. The units shall be factory wired, piped, charged 
with R-22 refrigerant and factory tested prior to shipment. All 
unit wiring shall be both numbered and color coded. All units 
the cooling performance shall be rated in accordance with 
DOE and ARI test procedures. Units shall be CSA listed, 
classified to ANSI Z21.47, UL 1995/CSA No. 236 standards.

UNIT CABINET

Unit cabinet shall be constructed of G90 galvanized steel,
with exterior surfaces coated with a non-chalking, powdered 
paint finish, certified at 750 hours salt spray test per 
ASTMB117 standards. Indoor blower section shall be insu-

FIGURE 10 - ROOF CURB DIMENSIONS

Summary of Contents for BP 072

Page 1: ...or frame All units include Powder Paint finish that meets ASTM B 117 750 hour salt spray standards Permanently lubricated motors Bottom or side air discharge configuration capability field convertibl...

Page 2: ...B DIMENSIONS 29 Tbl Pg LIST OF TABLES 1 SOUND POWER RATING 15 2 CAPACITY RATINGS 15 3 BP072 COOLING CAPACITIES 6 TON 16 4 BP072 HEATING CAPACITIES 18 5 SUPPLY AIR BLOWER PERFORMANCE 6 TON BELT DRIVE S...

Page 3: ...L Options 1 3 4 M Options 1 2 3 4 N Options 2 3 P Options 2 4 Q Options 2 3 4 R Options 3 4 S Option 5 T Options 1 5 U Options 1 3 5 V Options 1 4 5 W Options 1 3 4 5 X Options 3 5 Y Options 4 5 Z Op...

Page 4: ...se Monitor CQ CPC Controller DFS APS Technicoat Evap Cond Coils Coil Guard CR CPC Controller DFS APS Technicoat Evap Cond Coils Phase Monitor Coil Guard CS CPC Controller DFS APS SS Drain Pan CT CPC C...

Page 5: ...Controller DFS APS SS Drain Pan Phase Monitor Coil Guard HU Honeywell Excel 10 Controller DFS APS SS Drain Pan Technicoat Cond Coils HV Honeywell Excel 10 Controller DFS APS SS Drain Pan Technicoat Ev...

Page 6: ...ty Intelli Comfort Controller LB Simplicity Intelli Comfort Controller Phase Monitor LC Simplicity Intelli Comfort Controller Coil Guard LD Simplicity Intelli Comfort Controller Phase Monitor Coil Gua...

Page 7: ...Pan Dirty Filter Switch Hinged Filter Door Toolless Access Panels BN SS Drain Pan Phase Monitor Coil Guard Dirty Filter Switch Hinged Filter Door Toolless Access Panels BS Bottom Drain Connection Hing...

Page 8: ...FS APS SS Drain Pan Phase Monitor Coil Guard Technicoat Evap and Cond Coils Hinged Filter Door Toolless Access Panels GA Honeywell Excel 10 Controller with Dirty Filter Switch Air Proving Switch Hinge...

Page 9: ...Guard Dirty Filter Switch Hinged Filter Door Toolless Access Panels UH Technicoat Condenser Coil Phase Monitor Coil Guard Dirty Filter Switch Hinged Filter Door Toolless Access Panels UJ Technicoat E...

Page 10: ...LINC Controller Hinged Filter Door Toolless Access Panels XB Intelli Comfort w ModLINC Controller Phase Monitor Hinged Filter Door Toolless Access Panels XC Intelli Comfort w ModLINC Controller Coil G...

Page 11: ...es For testing the anti short cycle delay can be temporarily overridden with the push of a button Fan Delays Fan on and fan off delays are fully pro grammable and are independent of one another All un...

Page 12: ...e complete coil for maximum protection ELECTRIC HEATERS Wired for single point power supply These nickel chromium heater elements are pro vided with limit and automatic reset capability to prevent ope...

Page 13: ...operation of the unit by interrupting power to the control board if smoke is detected within the air compartment STAINLESS STEEL DRAIN PAN An optional rust proof stainless steel drain pan is availabl...

Page 14: ...without power exhaust This accessory includes a rain hood a bird screen and a fully assembled damper With bottom duct connections the damper should be mounted over the opening in the return air panel...

Page 15: ...MBH ARI RATINGS1 HEATING CAPACITY 47 F 17 F COOLING PERFORMANCE SOUND RATING2 bels NOTES 1 Certified in accordance with the Unitary Large Equipment certification program which is based on ARI Standar...

Page 16: ...OOR AMBIENT TEMPERATURE 105 F 115 F GROSS CAP 1 MBH INPUT2 POWER kW GROSS SENSIBLE CAPACITY1 MBH GROSS CAP 1 MBH INPUT2 POWER kW GROSS SENSIBLE CAPACITY1 MBH RETURN AIR DRY BULB TEMP F RETURN AIR DRY...

Page 17: ...47 9 40 9 33 9 26 9 19 9 67 57 2 7 76 57 2 53 8 46 8 39 8 32 8 25 8 18 8 62 53 8 7 75 53 8 53 8 53 8 47 0 40 0 33 1 26 1 57 52 7 7 70 52 7 52 7 52 5 45 5 38 5 31 5 24 5 2700 72 63 8 7 94 50 4 42 4 34...

Page 18: ...R MOTOR HEAT MBH 3 415 X KW TABLE 5 SUPPLY AIR BLOWER PERFORMANCE 6 TON BELT DRIVE SIDE DUCT APPLICATION RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 3200 1150 2325 1182 2425...

Page 19: ...0 0 12 0 14 0 16 0 19 0 22 20 30KW 0 06 0 07 0 08 0 09 0 11 0 13 0 15 0 17 0 20 0 23 0 26 0 06 0 07 0 08 0 09 0 10 0 11 0 12 0 14 0 16 0 19 0 22 0 08 0 10 0 12 0 14 0 16 0 18 0 20 0 23 0 26 0 29 0 32...

Page 20: ...462 13 6 16 4 34 7 35 2CE045120462 19 5 23 5 43 6 45 2CE045130462 28 8 34 6 57 6 60 NONE 0 0 11 9 15 2CE04511058 10 6 10 2 24 7 25 2CE04511558 15 9 15 3 31 0 35 2CE04512058 21 2 20 4 37 4 40 2CE045130...

Page 21: ...62 13 6 16 4 39 7 40 2CE045120462 19 5 23 5 48 6 50 2CE045130462 28 8 34 6 62 6 70 NONE 0 0 15 9 20 2CE04511058 10 6 10 2 28 7 30 2CE04511558 15 9 15 3 35 0 40 2CE04512058 21 2 20 4 41 4 45 2CE0451305...

Page 22: ...ins Per Inch 18 Face Area Sq Ft 17 1 COMPRESSOR Qty Per Unit Scroll Type 1 AIR FILTERS Quantity Per Unit 15 X 20 X 1 or 2 2 Quantity Per Unit 14 X 25 X 1 or 2 1 Total Face Area sq ft 6 6 CHARGE Refrig...

Page 23: ...TRANSFORMER TO REMOTE SENSOR 2TH040702224 IF USED NOT USED ADD JUMPER ADD JUMPER 4 4 3 2 1 ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET04700224 INCLUDES SUBBASE 2 SECOND STAGE COOLING IS NOT REQUIRED ON UN...

Page 24: ...036 21630 001 B 0904 24 Unitary Products Group FIGURE 3 UNIT DIMENSIONS FRONT VIEW FIGURE 4 UNIT WITH ECONOMIZER RAINHOOD DETAIL A...

Page 25: ...036 21630 001 B 0904 Unitary Products Group 25 FIGURE 5 UNIT WITH FIXED OUTDOOR AIR MOTORIZED DAMPER RAINHOOD DETAIL B FIGURE 6 UNIT DIMENSIONS REAR VIEW...

Page 26: ...Wiring Side Bottom C 1 5 8 KO Gas Piping Front D 1 1 2 KO Gas Piping Bottom 1 Opening in the bottom to the unit can be located by the side in the insulation 2 Do not remove the 2 knockout ring TABLE 1...

Page 27: ...036 21630 001 B 0904 Unitary Products Group 27 FIGURE 8 TYPICAL APPLICATIONS...

Page 28: ...GRAVITY BACK OF UNIT TABLE 16 BP 4 POINT LOADS WEIGHT DISTRIBUTION UNIT TOTAL A B C D BP072 612 136 133 170 173 TABLE 17 BP 6 POINT LOADS WEIGHT DISTRIBUTION UNIT TOTAL A B C D E F BP072 612 91 90 89...

Page 29: ...ure switch and a suction line with a freezestat and low pressure loss of charge switch The unit control circuit includes a 75 VA transformer a 24 volt circuit breaker and a relay board with a compress...

Page 30: ...l spring isolation and sound muf fling to minimize vibration and noise and be exter nally isolated on a dedicated independent mounting Coils a Evaporator and condenser coils shall have alumi num plate...

Page 31: ...nd return air damper assembly to prevent the supply air temperature from dropping below 55 F Changeover from compressor to economizer oper ation shall be provided by an integral electronic enthalpy co...

Page 32: ...tary 5005 Norman Products York OK Group Drive 73069 BAS CONTROLS Simplicity INTELLI Comfort CPC JOHNSON HONEYWELL NOVAR BAS READY ECONOMIZER BELIMO ACTUATOR WITHOUT A CONTROLLER HINGED FILTER DOOR ACC...

Reviews: