background image

GENERAL

YORK Model B1HA units are factory assembled heat pumps
designed for outdoor installation on a rooftop or a slab. Field-
installed electric heater accessories are available to provide
supplemental electric heat combined with electric cooling and
heating.

The units are completely assembled on rigid, removable
base rails. All piping, refrigerant charge, and electrical wiring
is factory installed and tested. The units require only electric
power and duct connections at the point of installation.

The electric heaters have nickel-chrome resistance wire ele-
ments and utilize single point power connection.

INSPECTION

As soon as a unit is received, it should be inspected for pos-
sible damage during transit. If damage is evident, the extent
of the damage should be noted on the carrier's freight bill. A
separate request for inspection by the carrier's agent should
be made in writing. Refer to Form 50.15-NM for additional in-
formation.

REFERENCE

Additional information on the design, installation, operation
and service of this equipment is available in the following refer-
ence forms:

55.70-N1        -General Installation

55.70-N2        -Pre-start & Post-start Check List

511.26-N1.1V -Electric Heater Accessory

RENEWAL PARTS

Refer to Replacement Parts Manual for complete listing of
replacement parts on this equipment.

All forms referenced in this instruction may be ordered from:

Standard Register

2101 West Techumseh Road

Norman, OK 73069

Toll Free: Tel. 877-318-9675/Fax. 877-379-7920

CHAMPION

®

SERIES

SINGLE PACKAGE HEAT PUMPS

Supersedes:  035-16004-000  (0801)

035-16004-001-A-0202

INSTALLATION INSTRUCTION

MODELS B1HA018 THRU 060

1.5 THRU 5 TON

(10 SEER)

Installer should pay particular attention to the words: NOTE, CAUTION and WARNING. Notes are intended to clarify or
make the installation easier. Cautions are given to prevent equipment damage. Warnings are given to alert installer that per-
sonal injury and/or equipment damage may result if installation procedure is not handled properly.

CAUTION

THE ENCLOSED INSTALLATION INSTRUCTIONS AND ANY APPLICABLE

LOCAL, STATE, AND NATIONAL CODES INCLUDING, BUT NOT LIMITED

TO, BUILDING, ELECTRICAL, AND MECHANICAL CODES.

THIS PRO DUCT M UST BE INSTALLED IN STRICT COMPLIANCE W ITH

WARNING

OPERATION OF THE  PRODUCT COULD CAUSE  PERSONAL  INJURY

O R   P R O P E R T Y   D A M A G E .

INCORRECT INSTALLATION MAY CREATE A CONDITION W HERE THE

Summary of Contents for B1HA018A06

Page 1: ...refer ence forms 55 70 N1 General Installation 55 70 N2 Pre start Post start Check List 511 26 N1 1V Electric Heater Accessory RENEWAL PARTS Refer to Replacement Parts Manual for complete listing of...

Page 2: ...with slings placed under the unit Spreader bars of sufficient length should be used across the top of the unit BEFORE LIFTING A UNIT MAKE SURE THAT ITS WEIGHT IS DISTRIBUTED EQUALLY ON THE CABLES SO T...

Page 3: ...Refer to Figure 3 for information concerning rear and bottom supply and return air duct openings FILTERS Single phase units are shipped without a filter and is the responsi bility of the installer to...

Page 4: ...shipped with compressor mountings factory adjusted for shipping Caution Loosen compressor bolts half turn before operating unit 035 16004 001 A 0202 4 Unitary Products Group TABLE 2 PHYSICAL DATA MOD...

Page 5: ...wances for a dry indoor coil and no filters For additional pressure drops refer to the Additional Static Pressure Resistance table 208 volts MODEL NO BHA MOTOR SPEED EXTERNAL STATIC PRESSURE IWG 10 20...

Page 6: ...1 103 7 114 1 126 3 140 2 148 8 166 2 90 100 110 125 150 150 150 175 90 100 110 125 150 150 150 175 060 208 230 1 60 28 9 165 0 1 5 7 0 2NH04501006 2NH04501506 2NH04502006 2NH04502506 2 2 2 2 7 5 10 0...

Page 7: ...04501558 2NH04502058 2NH04502558 1 1 2 2 10 0 15 0 20 0 25 0 9 6 14 4 19 2 24 1 21 3 27 3 33 3 39 3 25 30 35 40 25 30 35 40 060 575 3 60 6 4 50 0 0 6 2 8 2NH04501058 2NH04501558 2NH04502058 2NH0450255...

Page 8: ...4 0 36 0 50 50 96 40 060 208 230 1 60 187 253 28 9 165 0 1 5 7 0 44 6 60 60 96 40 036 208 230 3 60 187 253 10 9 78 0 1 1 3 5 18 2 25 25 96 75 042 208 230 3 60 187 253 14 1 110 0 1 1 3 5 22 2 30 30 96...

Page 9: ...test is being run 4 Knowing the pressure drop across a dry coil the actual CFM through the unit can be determined from the curve in Coil Delta P vs Supply Air CFM figure WARNING Failure to properly ad...

Page 10: ...14 2 18 8 23 4 28 0 32 5 37 1 37 3 37 5 37 7 37 9 75 10 1 14 0 17 9 21 8 25 7 29 5 33 4 34 3 35 2 36 1 37 0 80 10 5 13 7 17 0 20 2 23 4 26 6 29 8 31 4 33 0 34 6 36 2 85 11 0 13 5 16 0 18 5 21 1 23 6 2...

Page 11: ...5 19 4 23 9 28 3 95 5 5 6 6 7 8 12 5 17 3 22 1 26 8 100 5 4 6 3 10 4 14 6 18 7 22 9 105 8 3 11 8 15 4 19 0 110 6 2 9 1 12 1 15 0 115 6 4 8 8 11 1 OUTDOOR TEMPERATURE F INDOOR WB TEMPERATURE F 55 57 5...

Page 12: ...105 5 6 6 2 8 7 11 3 13 9 16 4 110 5 8 7 9 10 0 12 2 115 6 2 7 9 OUTDOOR TEMPERATURE F INDOOR WB TEMPERATURE F 55 57 59 61 63 65 67 69 71 73 75 65 34 0 34 2 34 4 34 6 34 8 35 0 35 2 36 2 37 3 38 4 39...

Page 13: ...1 6 8 7 5 8 2 9 1 10 1 11 0 11 9 110 5 5 6 3 7 2 8 0 8 9 9 8 10 7 11 6 115 5 9 6 9 7 8 8 7 9 5 10 4 11 2 OUTDOOR TEMPERATURE F INDOOR WB TEMPERATURE F 55 57 59 61 63 65 67 69 71 73 75 65 26 7 27 6 28...

Page 14: ...PENING SIDE SUPPLY AIR OPENING BOTTOM RETURN AIR OPENING 15 14 1 2 283 8 33 8 31 2 289 16 23 8 13 4 13 4 13 4 31 2 15 14 1 2 14 1 2 BOTTOM SUPPLY AIR OPENING 23 8 33 4 471 4 LOW VOLTAGE CONN 7 8 DIA K...

Page 15: ...n the indoor blower will continue to run If the fan switch is in the AUTO position the K1 relay will open and de energize the indoor blower motor after the appropriate time delay Please refer to Table...

Page 16: ...TER BANK 3 ELEC HEAT INSTANT OFF HEATER BANK 2 ELEC HEAT 1 2 SEC DELAY OFF HEATER BANK 1 ELEC HEAT 1 SEC DELAY OFF FAN 10 SEC DELAY OFF G Y W ON FAN INSTANT ON COMPRESSOR AND OUTDOOR FAN INSTANT ON SY...

Page 17: ...LE 22 THERMOSTAT SIGNALS THREE PHASE UNITS SIGNAL STATE BOARD FUNCTION G ON FAN INSTANT ON OFF FAN INSTANT OFF G Y O ON FAN INSTANT ON COMPRESSOR AND OUTDOOR FAN INSTANT ON AFTER ANTI SHORT CYCLE DELA...

Page 18: ...08 PR 708 PR 716 PR 716 PR 713 PR 713 PR 710 PR 710 PR F6 F6 F4 F4 F2 F2 K6 K6 K4 K4 K5 K5 K3 K3 M1 M1 714 BK 714 BK 706 BK 706 BK 711 BK 711 BK 703 BK 703 BK 709 BK 709 BK F1 F1 F3 F3 F5 F5 DUAL POIN...

Page 19: ...Group 19 035 16004 001 A 0202 FIG 5 TYPICAL WIRING DIAGRAM 230 3 60 POWER SUPPLY M R C COMPR RELAY DFST STAT M1 DETAIL A 222 Y BLU BLU DS DEFROST CONTROL 031 01268 000B FOR DEFROST CONTROL 031 09104 0...

Page 20: ...0 2 1 4 B R 8 D 7 E A B K 3 8 1 3 B R 8 1 4 Y L 2 L 2 L 2 1 2 3 H 1 L 1 L 1 L 1 K 1 2 0 9 R K 2 F A N C O N T R O L B O A R D T L H F L H 4 1 2 3 4 P 2 S 2 8 0 9 O 8 0 8 B R 2 0 4 B R S E E N O T E 8...

Page 21: ...ELEC HEAT 20 25 ALL KW ELEC HEAT 20 25 KW ELEC HEAT PTCR START ASSIST OPTIONAL DEVICE 20 25 20 25 20 25 CB CIRCUIT BREAKER 24V 3 AMP F7 F8 F9 TB2 TERMINAL BLOCK ECM MOTOR SPEED CONNECTIONS M2 CONTACT...

Page 22: ...22 Unitary Products Group 035 16004 001 A 0202...

Page 23: ...Unitary Products Group 23 035 16004 001 A 0202...

Page 24: ...ry Products Group 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright by York International Corporation 2000 All Rights Reserved Supersedes 035 16004 000...

Reviews: