Johnson Controls Unitary Products

5

256819-YTG-J-1208

APPLICATION FACTORS - RATED CFM VS. ACTUAL CFM

% Of Rated Airflow

80%

90%

Rated CFM

110%

120%

Capacity Factor

0.96

0.98

1.00

1.02

1.03

PHYSICAL & ELECTRICAL DATA - COOLING ONLY (60 Hz)

Models 

AVY24B**H21

AVY36C**H21

AVY48D**H21
SVY48D**N21

AVY60D**H21
SVY60D**N21

Blower - Diameter x Width

10 x 7

10 x 7

10 x 10

10 x 10

Motor

HP

1/3

1/2

3/4

1

Nominal RPM

1200

1200

1200

1200

Voltage

230

Amps

Full Load (230)

2.8

4.3

5.5

7.0

Filter

1

Type

DISPOSABLE OR PERMANENT

Size

16 x 20 x1

20 x 20 x1

22 x 20 x1

22 x 20 x1

Permanent Type Kit

1PF0601BK

1PF0602BK

1PF0603BK

1PF0603BK

Shipping / Operating Weight (lbs.)

140/134

170/164

AV - 196/185

SV - 194/181

AV - 199/188

SV - 195/184

1.Field supplied.

ELECTRICAL DATA - COOLING ONLY (60 Hz)

Models

Total Motor Amps

Minimum Circuit Ampacity

Max. O.C.P. 

Amps/Type

1

Minimum Wire 

Size A.W.G.

60 Hertz

60 Hertz

208V

230V

208V

230V

AVY24B**H21

3.2

2.8

4.0

3.5

15

14

AVY36C**H21

4.7

4.3

5.9

5.4

15

14

AVY48D**H21

6.1

5.0

7.6

6.9

15

14

SVY48D**N21

6.1

5.0

7.6

6.9

15

14

AVY60D**H21

7.8

7.0

9.7

8.8

15

14

SVY60D**N21

7.8

7.0

9.7

8.8

15

14

1. OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.

Summary of Contents for AVY24 THRU 60

Page 1: ...ovides easy installation to convert the air handler to the required refrigerant which is a true bolt on design that does not require brazing to replace or install MicroBlueTM Coated Fins All air handl...

Page 2: ...6 17 5 21 5 w o cladding 22 5 with cladding 12 3 8 13 29 32 14 19 32 7 8 1 2 1 3 8 1 1 23 32 1 1 4 7 8 1 2 3 8 3 4 AVY36C H21 52 21 17 1 8 17 13 32 18 3 32 7 8 AVY48D H21 57 24 5 22 1 8 20 29 32 21 19...

Page 3: ...1 Cooling Heat Pump Sweat 5 83 3 11 2 24 x 17 5 1 x 0 866 3 8 Enhanced None AVY60D2CH2 2C AVY60D4HH21 4H AVY60D4JH21 4J AVY60D4KH21 4K SVY60D3XN21 None SVY60D2CN21 2C Note H models are available with...

Page 4: ...0 840 1387 823 D N A 1 Airflow at nominal voltage bottom return at 0 5 external static pressure tested without filter installed dry coil conditions 2 These units have variable speed motors that automa...

Page 5: ...PERMANENT Size 16 x 20 x1 20 x 20 x1 22 x 20 x1 22 x 20 x1 Permanent Type Kit 1PF0601BK 1PF0602BK 1PF0603BK 1PF0603BK Shipping Operating Weight lbs 140 134 170 164 AV 196 185 SV 194 181 AV 199 188 SV...

Page 6: ...3 6 4 8 12 3 16 4 3 6 4 8 3 6 4 8 3 6 4 8 4HK 6500806 0 5 Heat C 5 6 7 5 19 2 25 6 2 8 3 75 5 6 7 5 5 6 7 5 4HK 6501006 0 5 Heat C 7 2 9 6 24 6 32 8 3 6 4 8 7 2 9 6 7 2 9 6 4HK16501506 0 5 Heat C 10 8...

Page 7: ...0 0 53 08 58 75 60 60 6 6 4HK16501506 60 0 74 75 83 75 90 90 3 3 4HK16501806 73 3 89 19 100 38 90 110 3 2 4HK16502006 80 0 96 42 108 75 100 125 3 1 4HK16502506 100 0 118 08 133 75 125 150 1 1 0 1 O C...

Page 8: ...rsion table on Page 5 ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY COPPER WIRE 208 230 3 60 Models Heat Kit Three Phase Heater Amps 240V Field Wiring Min Circuit Ampacity Max O C P 1 Amps Type 75 C...

Page 9: ...national and local safety codes Voltage limits are as follows Airflow must be within the minimum and maximum limits approved for electric heat evaporator coils and outdoor units COOLING MODELS WITH EL...

Page 10: ...SEER enhancement 2 Remove humidistat jumper on air handler control board 3 For heat pump applications set MODE jumper on air handler control board to the HP position 4 To change quantity of heat duri...

Reviews: