Johnson Controls Unitary Products
9
5151060-YTG-F-1116
ELECTRICAL DATA FOR MULTI-SOURCE POWER SUPPLY: 208/230-1-60
Air Handlers
Models
Heater
Models
Heater
Amps
@240V
Min. Circuit Ampacity
MOP
1
208V
230V
208V
230V
Circuit
Circuit
1st
3
2nd
3rd
1st
3
2nd
3rd
1st
3
2nd
3rd
1st
3
2nd
3rd
24B
6HK16501306
52
22.5
37.6
–
24.4
41.5
–
25
40
-
25
45
–
30B
6HK16501306
52
22.5
37.6
–
24.4
41.5
–
25
40
-
25
45
–
6HK16501506
60
25.4
43.3
–
27.6
47.9
–
30
45
-
30
50
–
36B
6HK16501306
52
25.0
37.6
–
26.4
41.5
–
25
40
–
30
45
–
6HK16501506
60
27.9
43.3
–
29.6
47.9
–
30
45
–
30
50
–
6HK16501806
72
45.3
39.0
–
48.8
43.1
–
50
40
–
50
45
–
6HK16502006
80
49.6
43.3
–
53.5
47.9
–
50
45
–
60
50
–
36C
6HK16501306
52
25.0
37.6
–
26.4
41.5
–
25
40
–
30
45
–
6HK16501506
60
27.9
43.3
–
29.6
47.9
–
30
45
–
30
50
–
6HK16501806
72
45.3
39.0
–
48.8
43.1
–
50
40
–
50
45
–
6HK16502006
80
49.6
43.3
–
53.5
47.9
–
50
45
–
60
50
–
42C
6HK16501306
52
25.0
37.6
–
26.4
41.5
–
25
40
–
30
45
–
6HK16501506
60
27.9
43.3
–
29.6
47.9
–
30
45
–
30
50
–
6HK16501806
72
45.3
39.0
–
48.8
43.1
–
50
40
–
50
45
–
6HK16502006
80
49.6
43.3
–
53.5
47.9
–
50
45
–
60
50
–
48C
6HK16501306
52
27.9
37.6
–
29.5
41.5
–
30
40
–
30
45
–
6HK16501506
60
30.8
43.3
–
32.7
47.9
–
35
45
–
35
50
–
6HK16501806
72
48.1
39.0
–
51.9
43.1
–
50
40
–
60
45
–
6HK16502006
80
52.5
43.3
–
56.7
47.9
–
60
45
–
60
50
–
48D
6HK16501306
52
27.9
37.6
–
29.5
41.5
–
30
40
–
30
45
–
6HK16501506
60
30.8
43.3
–
32.7
47.9
–
35
45
–
35
50
–
6HK16501806
72
48.1
39.0
–
51.9
43.1
–
50
40
–
60
45
–
6HK16502006
80
52.5
43.3
–
56.7
47.9
–
60
45
–
60
50
–
6HK16502506
100
52.5
43.3
21.7
56.7
47.9
24.0
60
45
25
60
50
25
60C
6HK16501306
52
27.9
37.6
–
29.5
41.5
–
30
40
–
30
45
–
6HK16501506
60
30.8
43.3
–
32.7
47.9
–
35
45
–
35
50
–
6HK16501806
72
48.1
39.0
–
51.9
43.1
–
50
40
–
60
45
–
6HK16502006
80
52.5
43.3
–
56.7
47.9
–
60
45
–
60
50
–
60D
6HK16501306
52
27.9
37.6
–
29.5
41.5
–
30
40
–
30
45
–
6HK16501506
60
30.8
43.3
–
32.7
47.9
–
35
45
–
35
50
–
6HK16501806
72
48.1
39.0
–
51.9
43.1
–
50
40
–
60
45
–
6HK16502006
80
52.5
43.3
–
56.7
47.9
–
60
45
–
60
50
–
6HK16502506
100
52.5
43.3
21.7
56.7
47.9
24.0
60
45
25
60
50
25
1. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. The 1st circuit includes blower motor amps.
Refer to the latest edition of the National Electric Code or in Canada the Canadian electrical Code and local codes to determine correct wire sizing.