
4
Johnson Controls Unitary Products
5151060-YTG-F-1116
COOLING CAPACITY
1
Models
Rated CFM
2
Entering Air
Dry/Wet Bulb (°F)
MBH@ Evap. Temp. and Corresponding R-410A Pressure (°F/PSIG)
35/107.9
40/118.9
45/130.7
50/143.3
18B
600
85/72
45.7
41.6
36.8
30.5
80/67
38.5
33.9
28.5
22.3
75/62
31.5
26.5
20.5
15.9
70/57
24.4
19.5
15.2
11.5
24B
800
85/72
52.2
47.5
41.8
35.0
80/67
43.6
38.3
31.9
24.5
75/62
35.2
29.5
22.7
16.2
70/57
27.1
20.7
15.5
11.4
30B
1000
85/72
75.3
67.8
56.8
47.1
80/67
62.6
54.6
44.2
34.5
75/62
50.2
41.3
32.0
22.9
70/57
37.8
30.1
21.5
16.2
36B
1200
85/72
91.6
82.4
71.3
59.4
80/67
76.5
65.4
54.6
42.8
75/62
61.3
51.2
40.0
30.5
70/57
47.5
38.1
28.7
22.3
36C
1200
85/72
91.6
82.4
71.3
59.4
80/67
76.5
65.4
54.6
42.8
75/62
61.3
51.2
40.0
30.5
70/57
47.5
38.1
28.7
22.3
42C
1400
85/72
108.0
98.4
88.1
73.8
80/67
93.3
82.1
69.7
57.0
75/62
75.9
64.4
53.1
41.9
70/57
60.7
49.9
39.4
32.4
48C
1600
85/72
115.2
105.0
93.9
79.0
80/67
88.3
78.2
65.5
52.6
75/62
72.7
60.8
50.1
37.6
70/57
57.7
46.9
36.6
29.7
48D
1600
85/72
115.2
105.0
93.9
79.0
80/67
88.3
78.2
65.5
52.6
75/62
72.7
60.8
50.1
37.6
70/57
57.7
46.9
36.6
29.7
60C
1800
85/72
115.1
103.0
91.7
78.6
80/67
96.8
85.9
73.7
60.5
75/62
80.7
69.4
57.5
43.5
70/57
58.7
48.9
37.7
32.7
60D
1800
85/72
133.6
118.5
103.2
86.6
80/67
111.4
96.2
80.3
62.8
75/62
90.7
75.1
60.0
43.5
70/57
70.6
56.9
42.5
32.8
1. Actual capacity varies with the outdoor AC or HP that is used with the system.
2. Airflow is calculated for each system tonnage.