OPERATION PANEL - COOL ONLY
MODELS
The operation panel will look like one of the following :
ROOM AIR CONDITIONERS
3
IOM # 036 - 3007 TP (0206)
POINTS TO REMEMBER
1. 3 Minute Time Delay
If during the course of
operation, the unit is
turned off or, if the
operation mode is
changed from COOLING
to FAN ensure that the
unit remains in FAN
MODE or remain
switched off for at least three minutes before changing
the mode to COOLING once again.
2. Attach
The
Air
Filter
Before switching on the
air conditioner, make sure
that the air filter is
attached properly. If the
unit has not been used for
a long time, it is
recommended to clean
the air filter before your
using the unit. During continuous use, clean the air filter
at least once every two weeks
.
3. Remove
Obstructions
Before switching the unit
on, make sure that the air
inlet grill and air outlet grill
are unobstructed.
4. Operating
Conditions
This units has been
designed to operate
efficiently in the following conditions :
Outdoor Temperature : 18°C to 45°C (’S’ Models) and
18°C to 56°C (’O’ Models)
Indoor Temperature : 18°C to 32°C
Heating Operation : Indoor Temperature -5°C to 30°C
Note :
If the indoor relative humidity is more than 80%,
condensation may appear on the cabinet, the grills or at
other places on the body of the air conditioner.
Operation of the unit in ambient conditions higher than
the design conditions may cause the unit to trip or the
compressor may burn out.
5. If you need to change the location of the unit, please
contact the York agent or distributor from whom you
have purchased the unit. The York agent or distributor
has trained personnel who can help you.
!
CAUTION
COOLER
THERMOSTAT
HIGH
FAN
LOW
COOL
HIGH
COOL
LOW
FAN
AUTO LOUVER
0
OFF
ON
TEST RUN
SELECTOR
OFF
ON
AUTO SWING
COOLER
1
6
3
9
THERMOSTAT
LOW
COOL
HIGH
FAN
LOW
FAN
HIGH
COOL
MED
COOL
SELECTOR
POWER
OFF
WAIT AT LEAST 3 MINUTES BEFORE RESTARTING
OPERATING INSTRUCTIONS
OPERATING PANEL COVER
Depending on the model
purchased by you, your air
conditioner may not have a
cover on the operating panel.
Note : Do not swing or
press the open operating
panel cover.
OPERATION SELECTOR
To set desired cooling
temperature, simply rotate the
knob to the appropriate
setting. SELECTOR at HIGH
FAN will circulate the air at a
maximum speed without a
cooling effect. At LOW FAN
the unit will circulate the air at
a minimum speed without a
cooling effect. HIGH COOL
provides cooling, automatically with maximum air circulation.
LOW COOL provides cooling, automatically with minimum air
circulation. If the SELECTOR is positioned at ‘0’ the unit will
shut down.
Note : When turning the SELECTOR knob from LOW
COOL to HIGH COOL, keep the speed slow as far as
possible. Do not change the operation mode between
LOW COOL and HIGH COOL too often as the
compressor protection may trip the unit.
SELECTOR
HIGH
FAN
LOW
COOL
HIGH
COOL
LOW
FAN
0
X