Johnson Controls Unitary Products
47
505591-YTG-A-0909
Multipliers for determining the performance with other indoor sections.
NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
LOW CFM
Continued on next page.
HEATING PERFORMANCE DATA - LOW CFM 1-STAGE OPERATION
OUTDOOR UNIT MODEL NO.
YZH04811(C)
INDOOR COIL MODEL NO.
FC/MC62D + MV20D
AIR TEMP.
ENTERING
OUTDOOR
UNIT
AIR TEMP.
ENTERING
INDOOR
COIL
ID CFM
973
1023
1073
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
60
60
41.4 2.5 4.9 41.6 2.5 5.0 41.8 2.4 5.1
70
40.7 2.8 4.3 40.8 2.7 4.3 40.9 2.7 4.4
80
40.0 3.1 3.8 40.0 3.0 3.8 40.0 3.0 3.9
47
60
33.7 2.4 4.0 33.8 2.4 4.1 34.0 2.4 4.2
70
33.2 2.7 3.6 33.3 2.7 3.7 33.4 2.6 3.7
80
32.8 3.0 3.2 32.8 2.9 3.3 32.8 2.9 3.3
40
60
29.7 2.4 3.7 29.8 2.3 3.7 29.9 2.3 3.8
70
29.4 2.6 3.3 29.4 2.6 3.3 29.4 2.6 3.4
80
29.1 2.9 2.9 29.0 2.9 3.0 28.9 2.8 3.0
30
60
24.4 2.3 3.1 24.4 2.3 3.2 24.5 2.2 3.2
70
24.2 2.6 2.8 24.1 2.5 2.8 24.1 2.5 2.8
80
23.9 2.8 2.5 23.8 2.8 2.5 23.7 2.7 2.5
17
60
18.1 2.2 2.4 18.2 2.2 2.5 18.2 2.1 2.5
70
18.0 2.5 2.1 18.0 2.4 2.2 18.1 2.4 2.2
80
17.8 2.7 1.9 17.9 2.7 2.0 18.0 2.6 2.0
10
60
15.0 2.2 2.0 15.0 2.1 2.1 15.0 2.1 2.1
70
14.8 2.4 1.8 14.9 2.4 1.8 14.9 2.4 1.9
80
14.6 2.7 1.6 14.7 2.6 1.6 14.9 2.6 1.7
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler
Coil
MBH
KW
COP
AHX48
–
1.01
0.99
1.03
AHX60
–
1.01
0.99
1.02
AV/SV*48 –
1.00
0.98
1.02
AV/SV*60 –
1.00
0.98
1.02
MV16C FC/MC48C
1.00
0.98
1.02
MV20D FC/MC48D
1.00
0.98
1.02
MV20D FC/MC60D
1.00
0.98
1.02
MV20D
FC64D
0.99
1.05
0.94
–
FC64
1.04
0.98
1.06