background image

279550-YIM-A-0207

24

Unitary Products Group

Welded Gas Valve Relay Response.

If either or both Pilot and Main Gas valve outputs are sensed to 
be off for more than 1 seconds when commanded to be on the 
control board shuts off all outputs and enters a hard lockout 

If the Pilot valve or Main valve output is sensed to be energized 
for more than 1 second when commanded to be off, the control 
de-energizes the induced draft motor (if flame is not present) to 
attempt to open the pressure switch to de-energize the gas 
valve. If the pilot or main gas valve is still sensed as energized 
after the inducer has been off for 5 seconds, the control re-
energizes the inducer to attempt to vent the unburned gas. In 
either case, the control enters a hard lockout. If the pilot or main 
valve becomes Un-Welded the inducer will de-energize, but the 
control will remain in a hard lockout.

During a hard lockout, the control board LED will remain off and 
the control will not respond to any thermostat demands.

The only way to recover from a hard lockout is to remove and 
then reapply 24VAC power to the control board.

Safety Controls

The control circuit includes the following safety controls:

1.

Limit Switch (LS) 

- This control is located inside the heat 

exchanger compartment and is set to open at the 
temperature indicated in the Temperature Controls Table 
of the unit wiring diagram. It resets automatically. The limit 
switch operates when a high temperature condition caused 
by inadequate supply air flow occurs, thus shutting down 
the ignition control and closing the main gas valve and 
energizing the blower.

2.

Pressure Switch (PS)

 - If the draft motor should fail, the 

pressure switch prevents the ignition controls and gas 
valves from being energized.

3.

Flame Sensor 

- The flame sensor and controls are located 

per Proper Flame Adjustment Figure 19. If an ignition 
control fails to detect a signal from the flame sensor 
indicating the pilot flame is properly ignited, then the main 
gas valve will not open.

4.

Rollout Switch (RS)

 - This switch is located in the burner 

vestibule. In the event of a sustained main burner flame 
rollout, it shuts off the ignition control and closes the main 
gas valve.

NOTE: 

The manual reset 

Rollout Switch (RS)

 must be reset 

before allowing furnace operation.

5.

Auxiliary Limit Switch (ALS)

 - This control is located 

inside the heat exchanger compartment and is set to open 
at 160°F. It is a manual reset switch. If ALS trips, then the 
primary limit (LS) has not functioned correctly. Replace the 
primary limit LS.

Cooling Sequence Of Operations

When the thermostat calls for first-stage cooling, the thermostat 
terminals G and Y1 energize, signaling the compressor, indoor 
blower and outdoor fan to operate. The indoor blower will operate 
according to the fan delay profile selected using Table 17.

When the thermostat calls for second-stage cooling the 
thermostat terminal Y2 energizes, signaling the compressor 
bypass ports to close and the indoor blower to increase speed. 
If the outdoor fan motor has an ECM controller, Y2 will also 
signal the motor to increase speed.

When the thermostat is satisfied, terminals G, Y1 and Y2 are 
de-energized, thus stopping operation of the compressor and 
outdoor fan. The indoor blower will remain on according to the 
fan delay profile selected using Table 17.

Safety Controls

The control circuit includes the following safety controls:

1.

 

High Pressure Switch (HP)-

 This switch protects against 

excessive discharge pressures due to a blocked 
condenser coil or a condenser motor failure (opens at 625 
± 25 psig and resets at 500 ± 25 psig).

2.

Low Pressure Switch (LP)-

 This switch protects against 

loss of refrigerant charge (opens at 7 ± 3 psig and resets at 
22 ± 5 psig).

The above pressure switches are specifically designed to 
operate with R-410A systems. R-22 pressure switches 

must not 

be used as replacements for the R-410A pressure switches.

Table 18: Ignition Control Board FLASH CODES

Flash Code

Description

On Steady

Control Failure - Replace Control

Heart Beat

Normal Operation

1 Flash

Not Applicable

2 Flashes

Pressure / Centrifugal Switch Open with Inducer On

3 Flashes

Pressure / Centrifugal Switch Closed with Inducer Off

4 Flashes

Not Applicable

5 Flashes

Lock Out From Too Many Flame Losses

6 Flashes

High Temperature Switch Open (Primary or Aux.)

7 Flashes

Rollout Switch Open

8 Flashes

Flame Present With Gas OFF

The ability to properly perform maintenance on this 
equipment requires certain expertise, mechanical 
skills, tools and equipment. If you do not possess 
these, do not attempt to perform any maintenance 
other than those procedures recommended in this 
Installation Manual. Failure to heed this warning could 
result in serious injury and possible damage to this 
equipment.

Summary of Contents for AFFINITY DNX024

Page 1: ...e Gas Heat 10 8 Typical Field Control Wiring Diagram Single Stage Thermostat Two Stage Gas Heat 11 9 Typical Field Control Wiring Diagram Two Stage Thermostat Single Stage Gas Heat 11 10 Typical Field...

Page 2: ...chanical codes Before performing service or maintenance operations on unit turn off main power switch to unit Electrical shock could cause personal injury Improper installation adjustment alteration s...

Page 3: ...lectrical Code ANSI NFPA No 70 Latest Edition 2 National Fuel Gas Code ANSI Z223 1 Latest Edition 3 Gas Fired Central Furnace Standard ANSI Z21 47a Latest Edition 4 Local building codes and 5 Local ga...

Page 4: ...ent Location Direct Drive Condenser Fan Motor Highly Efficient Enhanced Copper Tube Aluminum Fin Evaporator Coil Highly Efficient Enhanced Copper Tube Aluminum Fin Condenser Coil Decorative Protective...

Page 5: ...d proper unit operation Rigging And Handling Exercise care when moving the unit Do not remove any packaging until the unit is near the place of installation Rig the unit by attaching chain or cable sl...

Page 6: ...ensions Size Tons Weight lbs Center of Gravity 4 Point Load Location lbs Shipping Operating X Y A B C D 024 2 0 445 440 20 24 5 127 93 93 127 036 3 0 445 440 20 24 25 126 91 93 129 048 4 0 505 500 20...

Page 7: ...A B 024 33 1 2 18 1 4 036 048 41 1 2 23 1 8 Table 5 Unit Clearances1 2 1 A 1 clearance must be provided between any combustible material and the supply air duct work 2 The products of combustion must...

Page 8: ...Figure 4 Dimensions Front and Bottom Figure 5 Dimensions Back and Bottom 5217 6 6833 12 287 137 211 7 21 2 92 7 211 12 287 21 16 7 5 1 137 92 7 211 12 287 6 5 7851 5 23 1 1 27720 5 7851 5 23 1 1 2772...

Page 9: ...r information concerning rear and bottom supply and return air duct openings Roof Curb On applications when a roof curb is used the unit must be positioned on the curb so the front of the unit is tigh...

Page 10: ...6 The wiring entering the cabinet must be provided with mechanical strain relief A fused disconnect switch should be field provided for the unit If any of the wire supplied with the unit must be repl...

Page 11: ...WG wire should be used for all field installed 24 volt wire PROGRAMMABLE THERMOSTAT ONLY SINGLE STAGE THERMOSTAT UNIT CONTROL BOARD TERMINAL STRIP 24 VOLT TRANSFORMER NOTE HEAT ANTICIPATOR SHOULD BE S...

Page 12: ...T AT 0 35 AMPS FOR ALL MODELS Table 6 Electrical Data Size Tons Volt Compressors each OD Fan Motors each Supply Blower Motor MCA1 Amps 1 Minimum Circuit Ampacity Max Fuse2 Breaker3 Size Amps 2 Maximum...

Page 13: ...IMENSIONS inches Length 49 1 8 49 1 8 49 1 8 Width 47 1 4 47 1 4 47 1 4 Height 33 1 2 41 1 2 41 1 2 OPERATING WT lbs 440 480 500 COMPRESSORS Type Scroll 2 spd Scroll 2 spd Scroll 2 spd Quantity 1 1 1...

Page 14: ...8 49 1 8 49 1 8 Width 47 1 4 47 1 4 47 1 4 Height 33 1 2 41 1 2 41 1 2 OPERATING WT lbs 440 480 500 COMPRESSORS Type Scroll 2 spd Scroll 2 spd Scroll 2 spd Quantity 1 1 1 CONDENSER COIL DATA Face are...

Page 15: ...ld be followed in all cases unless superseded by local codes or gas company requirements Refer to Tables 7 and 8 The heating value of the gas may differ with locality The value should be checked with...

Page 16: ...80 370 80 43 90 170 350 90 40 84 160 320 100 38 79 150 305 Table 8 Propane LP Gas Pipe Sizing Chart1 1 Maximum capacity of pipe in thousands of BTU per hour based upon a pressure drop of 0 5 inch wate...

Page 17: ...a Propane Conversion Accessory Model 1NP0807 for 2 Ton unit with 33 1 2 tall cabinet and Model 1NP0808 for 3 and 4 Ton units with 41 1 2 tall cabinets Available On Models Input Capacity Mbh 2 2 Heati...

Page 18: ...Y1 COOL A 900 198 233 272 313 358 406 458 512 569 Y1 COOL B 760 166 190 222 262 310 366 431 503 584 Y1 COOL C 830 180 210 245 286 332 384 441 503 571 Y1 COOL D 970 221 260 302 344 388 434 481 530 579...

Page 19: ...xternal Static Pressure Inch Water Gauge 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 Watts Watts Watts Watts Watts Watts Watts Watts Watts 024 2 0 Cool Low Y1 COOL A 600 100 122 145 169 194 221 249 279 310 Y1...

Page 20: ...332 375 419 463 509 555 602 649 High Y1 Y2 COOL A 1550 586 640 696 752 810 869 929 991 1053 Y1 Y2 COOL B 1400 466 513 561 611 663 715 770 826 882 Y1 Y2 COOL C 1600 630 687 745 804 864 926 988 1052 11...

Page 21: ...l climate in your area Place the DELAY jumper tap on the CFM selection board on the appropriate pin setting Factory Set Gas Heat CFM The blower speed required for gas heat is different than for coolin...

Page 22: ...r heat ends Pre purge The control board monitors the low pressure switch and ensures it remains closed during pre purge If the pressure switch opens the control goes back to pressure switch proving mo...

Page 23: ...the inducer If a call for heat occurs during post purge the control finishes the post purge drops inducer out to re prove open pressure switch before continuing with the heat cycle Heat Blower Off Del...

Page 24: ...e operation 5 Auxiliary Limit Switch ALS This control is located inside the heat exchanger compartment and is set to open at 160 F It is a manual reset switch If ALS trips then the primary limit LS ha...

Page 25: ...sition 9 Replace the control access panel 10 Turn on all electric power to the unit 11 Set the thermostat to the desired setting 12 If the unit will not operate follow the instructions To Turn Off Gas...

Page 26: ...forward turn at an angle and pull back 3 Burners are now accessible for service Pilot Instruction To adjust the pilot flame Figure 19 Proper Flame Adjustment 1 Remove the pilot adjustment cover screw...

Page 27: ...of the furnace rating with allowance being made for the permissible range of the regulator setting replace the orifice spuds with spuds of the proper size NOTE To find the BTU input multiply the numb...

Page 28: ...279550 YIM A 0207 28 Unitary Products Group Typical Wiring Diagrams Typical DNX024 Cooling Unit with Single Stage Gas Heat 208 230 1 60 volt Wiring Diagram...

Page 29: ...279550 YIM A 0207 Unitary Products Group 29 Typical DNX024 Cooling Unit with Two Stage Gas Heat 208 230 1 60 volt Wiring Diagram...

Page 30: ...279550 YIM A 0207 30 Unitary Products Group Typical DNX036 048 Cooling Unit with Single Stage Gas Heat 208 230 1 60 volt Wiring Diagram...

Page 31: ...279550 YIM A 0207 Unitary Products Group 31 Typical DNX036 048 Cooling Unit with Two Stage Gas Heat 208 230 1 60 volt Wiring Diagram...

Page 32: ...279550 YIM A 0207 32 Unitary Products Group Typical DNX036 048 Cooling Unit with Single Stage Gas Heat 208 230 3 60 volt Wiring Diagram...

Page 33: ...279550 YIM A 0207 Unitary Products Group 33 Typical DNX036 048 Cooling Unit with Two Stage Gas Heat 208 230 3 60 volt Wiring Diagram...

Page 34: ...279550 YIM A 0207 34 Unitary Products Group Typical DNX036 048 Cooling Unit with Single Stage Gas Heat 460 3 60 volt Wiring Diagram...

Page 35: ...279550 YIM A 0207 Unitary Products Group 35 Typical DNX036 048 Cooling Unit with Two Stage Gas Heat 460 3 60 volt Wiring Diagram...

Page 36: ...g cylinders and recovery equipment must be dedicated for use on R 410A systems only Manifold sets must be at least 700 psig high side and 180 psig low side with 550 psig retard All hoses must have a s...

Reviews: