![background image](http://html1.mh-extra.com/html/york/affinity-dnq-series/affinity-dnq-series_technical-manual_912379009.webp)
333491-YTG-D-0409
Johnson Controls Unitary Products
13
DNZ, DNQ and DNX Unit Limitations
Size
(Tons)
Model
Unit Voltage
Unit Limitations
Applied Voltage
Outdoor DB Temp
Min
Max
Max (°F)
024
(2.0)
DNZ
DNQ
208/230-1-60
187
252
125
DNX
208/230-1-60
187
252
115
030
(2.5)
DNZ
208/230-1-60
187
252
125
208/230-3-60
187
252
125
460-3-60
432
504
125
DNQ
208/230-1-60
187
252
115
208/230-3-60
187
252
115
460-3-60
432
504
115
036
(3.0)
DNZ
208/230-1-60
187
252
125
208/230-3-60
187
252
125
460-3-60
432
504
125
DNQ
DNX
208/230-1-60
187
252
115
208/230-3-60
187
252
115
460-3-60
432
504
115
042
(3.5)
DNZ
DNQ
208/230-1-60
187
252
125
208/230-3-60
187
252
125
460-3-60
432
504
125
048
(4.0)
DNZ
DNQ
DNX
208/230-1-60
187
252
115
208/230-3-60
187
252
115
460-3-60
432
504
115
060
(5.0)
DNQ
208/230-1-60
187
252
125
208/230-3-60
187
252
125
460-3-60
432
504
125
DNZ
208/230-1-60
187
252
115
208/230-3-60
187
252
115
460-3-60
432
504
115