333491-YTG-D-0409

Johnson Controls Unitary Products

5

units with natural gas/propane for installations above 2000 
feet. Burner orifices must be obtained from Source 1 Parts. 
Propane Conversion Kit must be obtained separately.

Economizer Down Discharge/Supply Kit

 - Modulating 

integrated economizer provides simultaneous operation 
between the mechanical cooling and economizer 
operation. Independent blade design insures proper 
control and less than 1% leak rate. Includes hood and 
mesh bird screen filter integrated into the hood, dry bulb 
sensor and relief damper. Separate field accessories of 
single enthalpy and dual enthalpy are also available. A 
built-in barometric relief of 25% is provided.

Single Enthalpy Sensor

 - Sensor replaces dry bulb 

sensor standard in economizer kit. Provides improved 
economizer operation by sensing the dry bulb 
temperature from outdoors plus the enthalpy content of 
the outdoor air.

Dual Enthalpy Sensor

 - Additional sensor to single 

enthalpy sensor. Sensor senses both the return air 
temperature dry bulb and humidity in conjunction with the 
single enthalpy to determine the most economical mix. 
Single Enthalpy sensor also required.

Hail Guard Kit

 - Kit contains protective grilles made of 

expanded aluminum with full perimeter frame. Sloped 
hoods are also included to assure maximum protection.

Anti Short Cycle Timer (DNZ Units Only)

 - Automatically 

prevents the compressor from restarting for 5 minutes after 
cycled off.Not required if Thermostat 2ET07700224 and 
2ET04700224 are used. Standard in all DNX and DNQ 
units.

Filter/Frame Kit (Single Phase Only)

 - Kit contains the 

necessary hardware to field install return air filters into the 
base unit. Pre-cut filter racks and appropriate cleanable 
standard size filters are shipped in one kit. The filter rack 
is suitable for either 1" or 2" filters. (1" filter is supplied) 
This kit is available for single phase horizontal or vertical 
duct application only. Standard in all 3 Phase models.

Motorized Fresh Air Damper

 - Designed for duct 

mounted side supply/return and unit mounted down 
supply/return applications. Damper capable of providing 
0% through 50% of outdoor air (field supplied). Closes on 
power loss, includes hood and screen assembly.

Rectangle To Round Adapters

 - Kit includes one supply 

and one return air rectangle to round duct adapter. 
Adapters are preformed and designed to fit over current 
duct openings on the base unit. Transition is from side 
square duct opening to 14" round duct opening.

Roof Curbs

 - NRCA approved curbs provide proper fit to 

base unit for rooftop installations. Curbs are designed to 
be assembled through hinge pins in each corner. Kit also 
provides seal strip to assure a water tight seal. 8 and 14 
inch high roof curbs are available.

Manual Outdoor Damper

 - Provides 0% through 50% 

outdoor air capability (field adjustable). Designed for duct 
mounted side supply/return applications. Includes hood 
and screen assembly.

Wall Thermostat

 - The units are designed to operate with 

24-volt electronic and electro-mechanical thermostats. All 
units can operate with single stage heat/single stage cool 
thermostats - with or without the economizer.

Low Ambient Kit

 - Kit provides necessary hardware to 

convert unit to operate in cooling cycle down to 0º F. 
Standard unit operation 45º F.

Transformer Kit

 - Kit provides necessary hardware to 

provide single phase models from factory furnished 40 VA 
transformer capability to 75 VA transformer capability. 
(Required on installations with economizer or motorized 
damper.)

Guide Specifications

General

Units shall be manufactured by Unitary Products in an ISO 
9001 certified facility. YORK’s Affinity™ package units give you 
the flexibility and choices you need in today’s market. These 
packaged cooling/heating air conditioners are designed for 
outdoor installation. Only utility and duct connections are 
required at the point of installation. The single or two stage gas 
fired heaters have aluminized steel tubular heat exchangers 
and spark to pilot ignition. They are available in natural gas with 
field conversion to propane.

Description

Units shall be factory-assembled, single packaged, Electric 
Cooling/Gas Heating units, designed for outdoor mounted 
installation. For SEER ratings, refer to technical literature. They 
shall have built in, equal size, field convertible duct connections 
for down discharge supply/return or horizontal discharge 
supply/return. The units shall be factory wired, piped, charged 
with R-410A Refrigerant and factory tested prior to shipment. All 
unit wiring shall be both numbered and color coded. All units 
shall be manufactured in a facility certified to ISO 9001 
standards, and the cooling performance shall be rated in 
accordance with DOE and ARI test procedures. The heating 
performance shall be rated to DOE and GAMA test procedures. 
Units shall be CSA listed and classified to ANSI Z21.47/CAN/
CSA 2.3 standards and UL 1995/CAN/CSA No. 236-M90 
conditions.

Unit Cabinet

Unit cabinet shall be constructed of galvanized steel, with 
exterior surfaces coated with a non-chalking, powdered paint 
finish, certified at 1000 hours salt spray test per ASTM-B117 
standards. The unit top shall be a single piece “Water Shed” 
design, with drip edges and no-seam corners to provide 
optimum water integrity. Unit shall have a rigidly mounted 
condenser coil guard to provide protection from objects and 
personnel after installation. Indoor blower section shall be 
insulated with up to 3/4” thick, aluminum, foil faced insulation, 
fastened to prevent insulation from entering the air stream. 
Cabinet panels shall be “large” size, easily removable for 
servicing and maintenance, with built-in lift handles. Unit shall 
be built on a formed, “Super-Structure” design base pan, with 

Summary of Contents for AFFINITY DNQ Series

Page 1: ...nstallation Only utility and duct connections are required at the point of installation The single or two stage gas fired heaters have aluminized steel tubular heat exchangers and spark to pilot ignit...

Page 2: ...minum Fin Evaporator Coil Highly Efficient Enhanced Copper Tube Enhanced Aluminum Fin OR Micro Channel Aluminum Tube Aluminum Fin Condenser Decorative Protective Coil Guard See Features for Details Hi...

Page 3: ...gn allows maximum field flexibility and minimum inventory Condensate Pan A non corrosive long lasting water tight pan is positioned below the evaporator coil to collect and drain all condensate Less c...

Page 4: ...witches standard in all units When abnormal conditions are sensed through the pressure switches the unit will lock out preventing any further operation until reset or problem is corrected Exclusive Co...

Page 5: ...Damper Provides 0 through 50 outdoor air capability field adjustable Designed for duct mounted side supply return applications Includes hood and screen assembly Wall Thermostat The units are designed...

Page 6: ...with internal high pressure relief and over temperature protection The hermetic motor shall be suction gas cooled and have a voltage range of 10 of the unit nameplate voltage b Shall have internal iso...

Page 7: ...9 1 8 49 1 8 49 1 8 49 1 8 49 1 8 Width 47 1 4 47 1 4 47 1 4 47 1 4 47 1 4 47 1 4 Height 33 1 2 33 1 2 33 1 2 41 1 2 41 1 2 41 1 2 OPERATING WT lbs 378 398 402 460 465 480 COMPRESSORS Type Recip 1 spd...

Page 8: ...1 4 47 1 4 47 1 4 Height 33 1 2 33 1 2 33 1 2 41 1 2 41 1 2 41 1 2 OPERATING WT lbs 378 398 402 460 465 480 COMPRESSORS Type Recip 1 spd Recip 1 spd Recip 1 spd Recip 1 spd Scroll 1 spd Scroll 1 spd...

Page 9: ...252 115 208 230 3 60 187 252 115 460 3 60 432 504 115 036 3 0 DNZ 208 230 1 60 187 252 125 208 230 3 60 187 252 125 460 3 60 432 504 125 DNQ DNX 208 230 1 60 187 252 115 208 230 3 60 187 252 115 460...

Page 10: ...28 8 1 6 17 6 15 1 12 5 10 0 26 9 1 8 18 0 15 4 12 8 10 2 67 27 2 1 6 25 2 23 2 20 7 18 1 15 6 25 3 1 8 23 3 21 0 18 4 15 8 13 2 62 25 6 1 6 25 2 22 9 19 8 17 2 14 7 12 1 23 1 1 7 22 9 21 7 19 9 17 3...

Page 11: ...7 27 8 2 0 16 4 13 5 10 6 26 3 2 1 17 7 13 0 9 5 72 26 2 1 9 19 8 16 8 13 9 10 9 23 9 2 1 19 2 16 2 13 1 10 0 67 24 6 1 9 23 1 20 1 17 2 14 3 11 3 21 5 2 1 20 8 19 3 16 6 13 5 10 5 62 21 5 1 9 21 5 21...

Page 12: ...8 7 15 5 12 3 9 1 19 3 2 4 18 2 14 8 11 5 8 1 67 18 5 2 2 18 5 18 5 16 0 12 8 9 6 15 5 2 3 15 5 15 5 15 5 12 1 8 8 62 17 6 2 2 17 6 17 6 17 6 14 3 11 1 7 9 15 6 2 3 15 6 15 6 15 6 12 3 9 0 5 6 57 18 8...

Page 13: ...37 7 2 4 28 2 24 1 20 0 15 9 67 37 6 2 1 36 1 30 4 26 6 22 8 19 0 35 1 2 3 34 4 30 3 26 2 22 0 17 9 62 35 3 2 1 35 3 35 3 33 8 30 0 26 2 22 4 32 5 2 3 32 5 32 5 31 8 27 7 23 6 19 5 57 33 8 2 1 33 8 3...

Page 14: ...23 7 19 7 15 7 11 7 25 5 3 2 22 9 18 8 14 7 10 7 67 24 9 2 9 24 9 24 6 20 6 16 6 12 6 21 5 3 0 21 5 21 5 19 6 15 5 11 5 62 23 3 2 8 23 3 23 3 23 3 19 3 15 3 11 3 20 5 3 0 20 5 20 5 20 5 17 0 12 9 8 9...

Page 15: ...40 5 2 5 34 1 28 3 22 5 16 7 67 39 6 2 1 39 6 36 1 30 2 24 4 18 5 37 0 2 5 37 0 34 7 28 9 23 0 17 2 62 37 1 2 0 37 1 37 1 37 1 31 3 25 4 19 5 34 1 2 5 34 1 34 1 34 1 28 3 22 5 16 6 57 37 4 2 0 37 4 37...

Page 16: ...72 31 8 3 8 27 8 23 1 18 5 13 8 28 2 4 3 26 4 21 8 17 3 12 7 67 28 7 3 9 28 7 28 7 24 3 19 7 15 0 25 7 4 4 25 7 25 7 22 9 18 3 13 8 62 27 1 3 9 27 1 27 1 27 1 22 5 17 8 13 2 24 9 4 4 24 9 24 9 24 9 2...

Page 17: ...49 6 3 0 40 3 33 9 27 5 21 2 67 49 6 2 7 49 6 43 4 37 4 31 3 25 3 46 2 2 9 46 2 42 9 36 5 30 1 23 8 62 45 4 2 6 45 4 45 4 45 4 39 3 33 3 27 3 42 3 2 9 42 3 42 3 42 3 35 9 29 6 23 2 57 44 2 2 6 44 2 44...

Page 18: ...72 38 6 3 7 34 7 28 6 22 4 16 2 34 4 4 0 33 6 27 3 21 1 14 8 67 33 2 3 6 33 2 33 2 29 4 23 3 17 1 28 7 3 8 28 7 28 7 27 8 21 6 15 3 62 34 8 3 6 34 8 34 8 34 8 28 7 22 5 16 3 32 9 3 8 32 9 32 9 32 9 26...

Page 19: ...56 4 3 4 47 1 39 7 32 3 24 9 67 55 4 2 9 55 4 50 7 43 3 35 9 28 5 51 3 3 3 51 3 48 9 41 5 34 1 26 7 62 48 8 2 9 48 8 48 8 48 8 41 4 34 0 26 6 46 4 3 3 46 4 46 4 46 4 39 0 31 6 24 2 57 47 8 3 0 47 8 47...

Page 20: ...46 3 4 8 39 6 33 1 26 6 20 0 42 6 5 3 38 3 31 8 25 3 18 9 67 41 7 4 7 41 7 41 3 34 8 28 3 21 7 38 7 5 2 38 7 38 7 33 8 27 3 20 9 62 35 5 4 6 35 5 35 5 35 5 29 0 22 4 15 9 31 0 5 0 31 0 31 0 31 0 24 7...

Page 21: ...70 9 4 4 57 1 49 2 41 3 33 5 67 68 7 3 7 68 7 63 5 55 8 48 1 40 4 65 0 4 3 65 0 62 0 54 1 46 3 38 4 62 61 2 3 7 61 2 61 2 61 2 53 5 45 8 38 1 59 8 4 2 59 8 59 8 59 8 52 0 44 1 36 2 57 62 3 3 7 62 3 62...

Page 22: ...72 55 7 6 2 47 6 39 6 31 7 23 7 51 5 6 9 45 9 38 1 30 2 22 3 67 51 0 6 2 51 0 50 3 42 3 34 4 26 4 47 6 6 8 47 6 47 6 42 9 35 0 27 1 62 47 9 6 0 47 9 47 9 47 9 39 9 31 9 23 9 44 4 6 7 44 4 44 4 44 4 37...

Page 23: ...3 1304 395 913 1214 424 978 1114 448 1040 994 462 1098 Medium High 4 1445 515 976 1357 532 1041 1252 542 1097 1117 537 1140 High 5 1498 708 1108 1363 665 1157 1179 599 1178 042 3 5 DNZ Low 1 1114 176...

Page 24: ...3 1304 395 913 1214 424 978 1114 448 1040 994 462 1098 Medium High 4 1445 515 976 1357 532 1041 1252 542 1097 1117 537 1140 High 5 1498 708 1108 1363 665 1157 1179 599 1178 042 3 5 DNZ Low 1 1114 176...

Page 25: ...13 1200 0 06 0 02 0 16 1300 0 07 0 03 0 17 036 3 0 DNZ DNQ DNX 700 0 01 0 00 0 04 800 0 02 0 01 0 06 900 0 03 0 01 0 08 1000 0 04 0 01 0 10 1100 0 05 0 01 0 13 1200 0 06 0 02 0 16 1300 0 07 0 03 0 17...

Page 26: ...350 1110 2220 D072 700 1350 1110 2220 DNX N065 685 1350 1080 2370 N090 685 1350 1070 1780 D090 685 1350 1070 1780 042 3 5 DNZ DNQ N065 1050 1750 1080 2370 N090 1050 1750 1070 1780 D090 1050 1750 1070...

Page 27: ...applied at lower voltages Nominal Applied 240 208 0 75 230 0 92 480 460 0 92 600 575 0 92 Outdoor Sound Power Levels Size Tons Model Sound Rating1 dB A 1 Rated in accordance with ARI 270 standard Octa...

Page 28: ...14 4 20 060 5 0 208 230 1 60 26 2 150 41 2 3 7 6 42 7 60 208 230 3 60 17 9 120 28 2 3 7 6 32 3 40 460 3 60 9 6 70 15 1 3 3 8 17 1 25 DNQ024 060 Gas Heat Size Tons DNQ Volt Compressors each OD Fan Mot...

Page 29: ...333491 YTG D 0409 Johnson Controls Unitary Products 57 Typical DNX DNQ DNZ024 060 Wiring Diagrams Typical DNZ024 060 Cooling Unit with Single Stage Gas Heat 208 230 1 60 volt Wiring Diagram...

Page 30: ...333491 YTG D 0409 58 Johnson Controls Unitary Products Typical DNZ024 060 Cooling Unit with Two Stage Gas Heat 208 230 1 60 volt Wiring Diagram...

Page 31: ...333491 YTG D 0409 Johnson Controls Unitary Products 67 Typical DNZ030 060 Cooling Unit with Single Stage Gas Heat 208 230 3 60 volt Wiring Diagram...

Page 32: ...333491 YTG D 0409 68 Johnson Controls Unitary Products Typical DNZ030 060 Cooling Unit with Two Stage Gas Heat 208 230 3 60 volt Wiring Diagram...

Page 33: ...333491 YTG D 0409 Johnson Controls Unitary Products 75 Typical DNZ030 060 Cooling Unit with Single Stage Gas Heat 460 3 60 volt Wiring Diagram...

Page 34: ...333491 YTG D 0409 76 Johnson Controls Unitary Products Typical DNZ030 060 Cooling Unit with Two Stage Gas Heat 460 3 60 volt Wiring Diagram...

Page 35: ...24 5 127 93 93 127 030 2 5 DNZ 403 398 24 20 81 81 119 117 DNQ 430 425 20 24 25 122 88 90 125 036 3 0 DNZ 407 402 24 20 81 82 120 119 DNQ 435 430 20 24 25 123 89 91 127 DNX 485 480 20 24 136 98 103 14...