Johnson Controls Unitary Products

5

Anti Short Cycle Timer (BHZ Units Only)

 - 

Automatically prevents the compressor from restarting for 
5 minutes after cycled off.Not required if Thermostat 
2ET07700224 and 2ET04700224 are used. Standard in 
all BHX units.

Filter/Frame Kit (Single Phase Only)

 - Kit contains the 

necessary hardware to field install return air filters into the 
base unit. Pre-cut filter racks and appropriate cleanable 
standard size filters are shipped in one kit. The filter rack 
is suitable for either 1" or 2" filters. (1" filter is supplied) 
This kit is available for single phase horizontal or vertical 
duct application only. Standard in all 3 Phase models.

Motorized Fresh Air Damper

 - Designed for duct 

mounted side supply/return and unit mounted down 
supply/return applications. Damper capable of providing 
0% through 50% of outdoor air (field supplied). Closes on 
power loss, includes hood and screen assembly.

Rectangle To Round Adapters

 - Kit includes one supply 

and one return air rectangle to round duct adapter. 
Adapters are preformed and designed to fit over current 
duct openings on the base unit. Transition is from side 
square duct opening to 14" round duct opening.

Roof Curbs

 - NRCA approved curbs provide proper fit to 

base unit for rooftop installations. Curbs are designed to 
be assembled through hinge pins in each corner. Kit also 
provides seal strip to assure a water tight seal. 8 and 14 
inch high roof curbs are available.

Manual Outdoor Damper

 - Provides 0% through 50% 

outdoor air capability (field adjustable). Designed for duct 
mounted side supply/return applications. Includes hood 
and screen assembly.

Wall Thermostat

 - The units are designed to operate with 

24-volt electronic and electro-mechanical thermostats. All 
units can operate with single stage heat/single stage cool 
thermostats - with or without the economizer.

Low Ambient Kit

 - Kit provides necessary hardware to 

convert unit to operate in cooling cycle down to 0º F. 
Standard unit operation 45º F.

Transformer Kit

 - Kit provides necessary hardware to 

provide single phase models from factory furnished 40 VA 
transformer capability to 75 VA transformer capability. 
(Required on installations with economizer or motorized 
damper.)

Guide Specifications

General

Units shall be manufactured by York International Unitary 
Products Group in an ISO 9001 certified facility. YORK’s 
Affinity™ package units give you the flexibility and choices you 
need in today’s market. These packaged heat pumps are 
designed for outdoor installation. Only utility and duct 
connections are required at the point of installation.

Description

Units shall be factory-assembled, single packaged, heat pump 
units, designed for outdoor mounted installation. For SEER 
ratings, refer to technical literature. They shall have built in, 
equal size, field convertible duct connections for down 
discharge supply/return or horizontal discharge supply/return. 
The units shall be factory wired, piped, charged with R-410A 
Refrigerant and factory tested prior to shipment. All unit wiring 
shall be both numbered and color coded. All units shall be 
manufactured in a facility certified to ISO 9001 standards, and 
the cooling performance shall be rated in accordance with DOE 
and ARI test procedures. The heating performance shall be 
rated to DOE and GAMA test procedures. Units shall be CSA 
listed and classified to ANSI Z21.47/CAN/CSA 2.3 standards 
and UL 1995/CAN/CSA No. 236-M90 conditions.

Unit Cabinet

Unit cabinet shall be constructed of galvanized steel, with 
exterior surfaces coated with a non-chalking, powdered paint 
finish, certified at 1000 hours salt spray test per ASTM-B117 
standards. The unit top shall be a single piece “Water Shed” 
design, with drip edges and no-seam corners to provide 
optimum water integrity. Unit shall have a rigidly mounted 
condenser coil guard to provide protection from objects and 
personnel after installation. Indoor blower section shall be 
insulated with up to 3/4” thick, aluminum, foil faced insulation, 
fastened to prevent insulation from entering the air stream. 
Cabinet panels shall be “large” size, easily removable for 
servicing and maintenance, with built-in lift handles. Unit shall 
be built on a formed, “Super-Structure” design base pan, with 
embossments at critical points to add strength, rigidity and aid 
in minimizing sound. Full perimeter base rails shall be provided 
to assure reliable transit of equipment, overhead rigging, for 
truck access and proper sealing on roof curb applications. Base 
rails shall be removable, when required, to lower unit height. 
Filters shall be furnished and be accessible through a 
removable access door, sealed airtight. Units vertical discharge 
and return duct configuration shall be designed to fit between 
standard 24” O.C. beams without modification to building 
structure, duct work and base unit. Condensate pan shall be 
internally sloped and conform to ASHRAE 62-89 self-draining 
standards, with 3/4” NPTI copper, ridged mount connection.

Indoor (Evaporator) Fan Assembly

Fan shall be direct drive design. Fan wheel shall be double-inlet 
type with forward-curved blades, dynamically balanced to 
operate smoothly throughout the entire range of operation. 
Airflow design shall be constant air volume. Bearings shall be 
sealed and permanently lubricated for longer life and no 
maintenance. Fan assembly shall be “Slip Track” (slide-out) 
design for easy removal and cleaning.

Outdoor (Condenser) Fan Assembly

The outdoor fan shall be of the direct-driven propeller type, 
discharge air vertically, have aluminum blades riveted to 
corrosion resistant steel spider bracket and shall be statically 
balanced for smooth operation. The outdoor fan motor shall be 

Summary of Contents for Affinity BHZ024

Page 1: ...pumps are designed for outdoor installation Only utility and duct connections are required at the point of installation Field installed electric heater accessories are available to provide electric heat if required R 410A AFFINITY SERIES BHX BHQ AND BHZ MODELS 2 5 TON 60 Hertz Tested in accordance with ISO 9001 Certified Quality Management System ...

Page 2: ...s 75 Component Location Heat Pump Direct Drive Condenser Fan Motor Highly Efficient Enhanced Copper Tube Aluminum Fin Indoor Coil Highly Efficient Enhanced Copper Tube Aluminum Fin Outdoor Coil Decorative Protective Coil Guard See Features for details Direct Drive Blower Motor With Slide Out Blower Assembly Heavy Gauge Removable Base Rails High Efficiency Compressor Rigidly Mounted Long Lasting Po...

Page 3: ...turn application If a bottom supply bottom return application is desired you simply remove the two panels from the bottom of the unit and place them in the side supply side return duct openings No panel cutting is required and no accessory panel is necessary Convertible airflow design allows maximum field flexibility and minimum inventory Condensate Pan A non corrosive long lasting water tight pan...

Page 4: ...ssor The compressor is internally protected against high pressure and temperature This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protect the compressor if undesirable operating conditions occur Pressure Switches High pressure and low pressure loss of charge switches standard in all units When abnormal conditions are sensed through th...

Page 5: ...gs refer to technical literature They shall have built in equal size field convertible duct connections for down discharge supply return or horizontal discharge supply return The units shall be factory wired piped charged with R 410A Refrigerant and factory tested prior to shipment All unit wiring shall be both numbered and color coded All units shall be manufactured in a facility certified to ISO...

Page 6: ...ternally enhanced copper tubes with all joints brazed b Evaporator coil shall be of the direct expansion blow through design while condenser coil shall be draw through design Refrigerant Circuit and Refrigerant Safety Components shall include a Shall include independent fixed orifice expansion devices b Shall include filter strainer to eliminate any foreign matter Electric Heating Section Field In...

Page 7: ...croll 1 spd Scroll 1 spd Scroll 1 spd Scroll 1 spd Quantity 1 1 1 1 1 1 CONDENSER COIL DATA Face area Sq Ft 12 9 12 9 12 9 16 4 16 4 16 4 Rows 1 1 2 2 2 2 Fins per inch 20 20 20 20 20 20 Tube diameter in 3 8 3 8 3 8 3 8 3 8 3 8 Refrigerant control Orifice Orifice Orifice Orifice Orifice TXV EVAPORATOR COIL DATA Face area Sq Ft 4 38 4 38 4 38 5 63 5 63 5 63 Rows 2 3 3 3 3 3 Fins per inch 15 13 15 1...

Page 8: ...30 1 60 187 252 125 208 230 3 60 187 252 125 460 3 60 432 504 125 BHX BHQ 208 230 1 60 187 252 115 208 230 3 60 187 252 115 460 3 60 432 504 115 042 3 5 BHZ BHQ 208 230 1 60 187 252 125 208 230 3 60 187 252 125 460 3 60 432 504 125 048 4 0 BHZ 208 230 1 60 187 252 125 208 230 3 60 187 252 125 460 3 60 432 504 125 BHX BHQ 208 230 1 60 187 252 115 208 230 3 60 187 252 115 460 3 60 432 504 115 060 5 ...

Page 9: ...4 14 0 9 5 1000 72 28 3 1 7 26 6 21 6 16 7 11 7 26 2 1 9 24 7 19 7 14 8 9 8 67 26 1 1 7 26 1 24 1 19 0 14 0 9 0 24 8 1 9 24 8 23 8 18 9 13 9 8 9 62 24 2 1 7 24 2 24 2 24 0 19 1 14 1 9 1 23 0 1 9 23 0 23 0 22 9 18 0 13 0 8 0 57 23 3 1 7 23 3 23 3 23 3 18 3 13 4 8 4 22 7 1 9 22 7 22 7 22 7 17 8 12 8 7 8 95 F 105 F 600 77 23 0 1 8 11 5 8 7 5 8 22 8 2 1 11 8 9 0 6 1 72 22 5 1 8 16 5 13 7 10 8 8 0 21 6...

Page 10: ...17 4 2 5 17 4 17 4 17 7 13 8 9 9 6 0 15 6 2 7 15 6 15 6 15 6 12 4 8 6 4 7 57 18 0 2 5 18 0 18 0 17 2 13 3 9 4 5 5 16 3 2 8 16 3 16 3 15 5 11 6 7 7 3 8 900 72 20 7 2 6 20 0 16 2 11 8 7 3 19 3 2 9 19 3 15 9 11 5 7 0 67 18 7 2 6 18 7 18 7 16 2 11 8 7 3 16 5 2 8 16 5 16 5 15 3 10 8 6 4 62 17 5 2 6 17 5 17 5 17 7 13 2 8 8 4 4 15 6 2 8 15 6 15 6 15 6 11 5 7 1 2 7 57 18 1 2 6 18 1 18 1 17 7 13 3 8 9 4 4 ...

Page 11: ...8 21 5 15 3 34 3 2 8 32 5 26 3 20 1 13 9 67 34 6 2 6 34 6 34 6 26 2 20 0 13 8 31 5 2 7 31 5 31 5 25 5 19 3 13 1 62 32 6 2 3 32 6 32 6 32 6 26 4 20 2 13 9 28 6 2 6 28 6 28 6 28 6 22 4 16 1 9 9 57 30 7 2 4 30 7 30 7 30 7 24 5 18 3 12 1 28 1 2 6 28 1 28 1 28 1 21 9 15 7 9 5 95 F 105 F 750 77 35 7 2 6 16 4 12 9 9 3 32 5 2 8 15 1 11 5 8 0 72 32 6 2 6 20 9 17 3 13 7 10 2 29 5 2 8 19 7 16 2 12 6 9 1 67 2...

Page 12: ... 2 22 2 22 2 22 0 17 1 12 3 7 4 20 7 3 5 20 7 20 7 20 5 15 6 10 8 5 9 57 20 3 3 3 20 3 20 3 20 1 15 3 10 4 5 6 17 4 3 6 17 4 17 4 17 2 12 4 7 5 2 6 1125 72 28 6 3 3 26 5 21 0 15 4 9 9 26 9 3 6 25 5 20 0 14 4 8 9 67 25 6 3 4 25 6 25 6 21 9 16 4 10 9 24 0 3 7 24 0 24 0 21 3 15 8 10 3 62 23 9 3 3 23 9 23 9 23 8 18 3 12 7 7 2 23 5 3 6 23 5 23 5 23 3 17 8 12 3 6 7 57 21 9 3 3 21 9 21 9 21 8 16 2 10 7 5...

Page 13: ...6 40 1 3 0 39 0 31 5 24 1 16 6 67 40 8 2 5 40 8 40 8 33 9 26 5 19 0 37 9 2 9 37 9 37 9 32 5 25 1 17 6 62 37 7 2 5 37 7 37 7 37 7 30 3 22 8 15 4 35 4 2 8 35 4 35 4 35 4 28 0 20 5 13 1 57 37 3 2 5 37 3 37 3 37 3 29 9 22 4 15 0 35 2 2 9 35 2 35 2 35 2 27 7 20 2 12 8 95 F 105 F 900 77 40 0 2 9 21 7 17 5 13 2 37 1 3 4 20 1 15 8 11 6 72 36 7 2 9 27 1 22 8 18 6 14 3 33 6 3 4 25 5 21 3 17 0 12 7 67 33 4 2...

Page 14: ...0 62 26 3 3 8 26 3 26 3 27 4 21 6 15 8 9 9 23 5 4 2 23 5 23 5 23 5 18 7 12 9 7 0 57 26 4 3 8 26 4 26 4 27 5 21 7 15 9 10 0 23 7 4 2 23 7 23 7 23 7 18 9 13 1 7 3 1350 72 31 3 4 0 30 7 25 2 18 6 12 0 28 1 4 4 28 1 23 3 16 6 10 0 67 27 5 3 9 27 5 27 5 25 2 18 6 11 9 24 1 4 3 24 1 24 1 23 3 16 6 10 0 62 26 4 3 9 26 4 26 4 27 0 20 3 13 7 7 1 23 4 4 3 23 4 23 4 23 4 17 2 10 6 4 0 57 26 5 3 9 26 5 26 5 2...

Page 15: ...8 47 5 3 5 42 8 34 1 25 4 16 7 67 44 4 3 3 44 4 43 6 34 9 26 2 17 5 44 1 3 5 44 1 43 0 34 3 25 6 16 9 62 43 6 3 2 43 6 43 6 43 6 34 9 26 2 17 5 41 6 3 4 41 6 41 6 41 6 32 9 24 2 15 5 57 43 1 3 2 43 1 43 1 43 6 34 9 26 2 17 5 42 2 3 4 42 2 42 2 42 2 33 5 24 8 16 1 95 F 105 F 1050 77 42 5 3 5 22 9 17 9 12 9 39 6 3 8 22 3 17 3 12 3 72 39 9 3 5 31 0 26 0 21 0 16 0 36 3 3 7 29 9 24 9 19 9 14 9 67 37 3 ...

Page 16: ... 0 62 29 4 4 3 29 4 29 4 31 2 24 4 17 6 10 8 25 8 4 7 25 8 25 8 27 3 20 5 13 7 6 9 57 30 6 4 3 30 6 30 6 31 3 24 5 17 7 10 9 26 7 4 8 26 7 26 7 27 9 21 1 14 3 7 5 1575 72 36 2 4 4 35 5 28 5 20 7 13 0 31 7 4 8 33 8 27 1 19 4 11 6 67 31 8 4 3 31 8 31 8 28 5 20 7 13 0 26 6 4 7 26 6 27 5 26 4 18 7 10 9 62 30 4 4 3 30 4 30 4 31 3 23 5 15 8 8 0 26 5 4 6 26 5 26 5 27 3 19 6 11 8 4 1 57 31 6 4 3 31 6 31 6...

Page 17: ... 54 0 4 2 50 0 40 5 31 0 21 5 67 54 3 3 8 54 3 54 3 43 7 34 2 24 7 49 7 4 1 49 7 49 7 41 0 31 5 22 0 62 47 9 3 8 47 9 47 9 47 9 38 4 28 9 19 4 45 4 4 0 45 4 45 4 45 4 35 9 26 4 16 9 57 49 1 3 8 49 1 49 1 49 1 39 6 30 1 20 6 45 9 3 8 45 9 45 9 45 9 36 4 26 9 17 4 95 F 105 F 1200 77 56 5 3 4 28 5 22 8 17 1 51 7 3 8 27 8 22 1 16 4 72 51 3 3 6 36 5 30 8 25 1 19 4 46 4 3 8 35 7 30 0 24 3 18 6 67 46 1 3...

Page 18: ...4 1 62 35 7 4 7 35 7 35 7 35 2 27 5 19 7 11 9 31 9 5 1 31 9 31 9 31 5 23 8 16 0 8 2 57 35 7 4 7 35 7 35 7 35 3 27 6 19 8 12 0 32 1 5 2 32 1 32 1 31 7 23 9 16 1 8 3 1800 72 42 1 5 0 40 8 33 3 24 4 15 6 37 9 5 4 37 9 31 6 22 6 13 7 67 36 5 4 9 36 5 36 5 32 6 23 8 14 9 32 1 5 2 32 1 32 1 30 4 21 5 12 5 62 35 9 4 8 35 9 35 9 35 7 26 8 18 0 9 1 32 4 5 2 32 4 32 4 32 2 23 2 14 2 5 3 57 36 0 4 8 36 0 36 ...

Page 19: ... 69 2 5 1 63 0 50 6 38 2 25 8 67 66 9 4 6 66 9 66 2 51 4 39 0 26 5 62 3 5 0 62 3 62 0 49 6 37 1 24 7 62 65 2 4 1 65 2 65 2 65 2 52 8 40 4 28 0 59 0 4 7 59 0 59 0 59 0 46 6 34 2 21 7 57 64 5 4 1 64 5 64 5 64 5 52 1 39 7 27 3 58 5 4 7 58 5 58 5 58 5 46 1 33 7 21 2 95 F 105 F 1500 77 63 3 5 5 31 1 24 0 16 9 57 8 5 8 29 5 22 4 15 3 72 59 7 5 2 43 2 36 1 29 0 21 9 53 8 5 6 40 0 32 9 25 8 18 7 67 56 1 4...

Page 20: ... 62 41 3 6 1 41 3 41 3 45 1 35 4 25 6 15 9 36 3 6 6 36 3 36 3 36 3 33 3 23 5 13 8 57 43 2 6 1 43 2 43 2 41 8 32 1 22 4 12 7 39 4 6 6 39 4 39 4 38 2 28 5 18 8 9 1 2250 72 50 7 6 5 48 8 38 3 27 2 16 2 45 8 7 0 45 8 36 0 25 0 13 9 67 46 1 6 3 46 1 46 1 37 9 26 9 15 8 40 7 6 9 40 7 40 7 34 4 23 3 12 3 62 42 6 6 2 42 6 42 6 44 5 33 4 22 3 11 3 37 9 6 7 37 9 37 9 37 9 30 1 19 1 8 0 57 44 6 6 2 44 6 44 6...

Page 21: ...00 10 92 13 40 16 61 20 73 26 06 32 93 KW 1 49 1 57 1 64 1 72 1 79 1 87 1 94 2 02 80 MBH 6 33 7 83 9 75 12 23 15 43 19 56 24 88 31 75 KW 1 67 1 74 1 82 1 89 1 97 2 04 2 12 2 19 030 2 5 750 55 MBH 12 14 13 95 16 07 18 55 21 46 24 87 28 85 33 52 KW 1 68 1 73 1 79 1 85 1 91 1 97 2 03 2 09 70 MBH 9 98 11 80 13 92 16 40 19 31 22 71 26 70 31 36 KW 1 95 2 01 2 07 2 13 2 19 2 25 2 31 2 36 80 MBH 9 05 10 8...

Page 22: ... 28 03 33 69 40 46 KW 2 44 2 61 2 77 2 94 3 11 3 28 3 45 3 62 042 3 5 1050 55 MBH 14 34 17 01 20 13 23 79 28 08 33 09 38 97 45 85 KW 2 20 2 43 2 66 2 89 3 12 3 34 3 57 3 80 70 MBH 14 60 17 27 20 39 24 05 28 34 33 36 39 23 46 11 KW 2 72 2 95 3 18 3 41 3 63 3 86 4 09 4 32 80 MBH 13 11 15 77 18 90 22 56 26 84 31 86 37 74 44 62 KW 3 13 3 35 3 58 3 81 4 04 4 27 4 49 4 72 1225 55 MBH 14 84 17 51 20 63 2...

Page 23: ... MBH 24 54 28 20 32 46 37 44 43 23 49 98 57 85 67 02 KW 3 12 3 34 3 56 3 79 4 01 4 23 4 45 4 67 70 MBH 22 90 26 57 30 83 35 80 41 60 48 35 56 21 65 38 KW 3 56 3 78 4 00 4 22 4 44 4 66 4 89 5 11 80 MBH 21 74 25 40 29 67 34 64 40 43 47 18 55 05 64 22 KW 4 07 4 30 4 52 4 74 4 96 5 18 5 40 5 62 1750 55 MBH 24 18 27 84 32 11 37 08 42 87 49 62 57 49 66 66 KW 3 20 3 42 3 64 3 86 4 08 4 31 4 53 4 75 70 MB...

Page 24: ...78 377 981 971 397 1048 Medium High 4 1416 413 872 1314 436 932 1206 454 993 1083 460 1051 High 5 1441 530 970 1326 538 1022 1182 521 1070 042 3 5 BHZ Low 1 1241 221 702 1151 245 778 1058 268 853 Low Medium 2 1406 299 759 1325 324 826 1242 349 893 1158 373 959 1072 396 1025 Medium 3 1536 376 808 1461 403 869 1384 427 928 1305 449 988 1223 468 1046 Medium High 4 1656 466 858 1584 492 912 1509 515 9...

Page 25: ...78 377 981 971 397 1048 Medium High 4 1416 413 872 1314 436 932 1206 454 993 1083 460 1051 High 5 1441 530 970 1326 538 1022 1182 521 1070 042 3 5 BHZ Low 1 1241 221 702 1151 245 778 1058 268 853 Low Medium 2 1406 299 759 1325 324 826 1242 349 893 1158 373 959 1072 396 1025 Medium 3 1536 376 808 1461 403 869 1384 427 928 1305 449 988 1223 468 1046 Medium High 4 1656 466 858 1584 492 912 1509 515 9...

Page 26: ...02 0 03 0 06 1300 0 07 0 03 0 17 036 3 0 BHZ BHX BHQ 700 0 01 0 00 0 02 0 03 800 0 01 0 01 0 02 0 03 900 0 01 0 01 0 02 0 04 1000 0 02 0 01 0 02 0 04 1100 0 03 0 01 0 03 0 05 1200 0 04 0 02 0 03 0 06 1300 0 04 0 03 0 03 0 07 1400 0 04 0 04 0 03 0 08 042 3 5 BHZ BHQ 1100 0 03 0 01 0 03 0 05 1200 0 04 0 02 0 03 0 06 1300 0 04 0 03 0 03 0 07 1400 0 04 0 04 0 03 0 08 1500 0 05 0 05 0 04 0 09 1600 0 06...

Page 27: ...1600 1600 208 230 3 60 1600 1600 1600 1600 460 3 60 1600 1600 1600 1600 BHX BHQ 208 230 1 60 1440 1440 1440 1440 208 230 3 60 1440 1440 1440 1440 460 3 60 1440 1440 1440 1440 060 5 0 BHZ 208 230 1 60 1750 1750 1750 1750 208 230 3 60 1750 1750 1750 1750 460 3 60 1750 1750 1750 1750 BHX BHQ 208 230 1 60 1900 1900 1900 1900 208 230 3 60 1900 1900 1900 1900 460 3 60 1900 1900 1900 1900 Indoor Blower S...

Page 28: ...500 1000 2000 4000 8000 024 2 0 BHZ 77 64 74 71 69 65 5 58 46 BHX BHQ 75 65 5 66 5 69 69 5 64 62 57 030 2 5 BHZ BHQ 77 65 66 5 72 71 5 68 5 65 5 64 5 036 3 0 BHZ 78 67 5 67 73 73 69 64 5 61 5 BHX BHQ 79 73 71 5 72 71 67 64 5 60 042 3 5 BHZ BHQ 77 64 5 67 71 5 72 5 69 5 64 5 59 048 4 0 BHZ 78 65 67 72 72 69 67 5 63 BHX BHQ 80 70 71 75 74 70 66 67 060 5 0 BHZ 85 70 72 5 79 79 5 76 73 5 73 BHX BHQ 80...

Page 29: ...46 15 1 18 32 7 35 042 3 5 208 230 1 60 18 6 105 29 1 2 6 0 None 30 5 40 2NP04501006 7 5 10 2 36 1 41 7 75 6 82 5 80 90 2NP04501506 11 3 15 2 54 2 62 5 98 2 108 6 100 110 2ND04501506 3 8 5 1 18 1 20 8 53 56 5 60 60 7 5 10 1 36 1 41 7 75 6 82 5 80 90 208 230 3 60 13 4 88 21 1 2 6 0 None 24 30 2NP04501025 7 5 10 1 20 8 24 1 50 54 60 60 2NP04501525 11 3 15 1 31 3 36 1 63 69 1 70 70 460 3 60 6 4 39 10...

Page 30: ...333495 YTG D 0609 Johnson Controls Unitary Products 63 Typical BHX BHQ BHZ024 060 Wiring Diagrams Typical BHX024 048 and 060 Heat Pump 208 230 1 60 volt Wiring Diagram ...

Page 31: ...333495 YTG D 0609 66 Johnson Controls Unitary Products Typical BHZ024 060 Heat Pump 208 230 1 60 volt Wiring Diagram ...

Page 32: ...333495 YTG D 0609 70 Johnson Controls Unitary Products Typical BHZ030 060 Heat Pump 230 3 60 volt Wiring Diagram ...

Page 33: ...333495 YTG D 0609 74 Johnson Controls Unitary Products Typical BHZ030 060 Heat Pump 460 3 60 volt Wiring Diagram ...

Page 34: ... 89 102 BHQ 405 400 22 25 25 109 95 92 105 BHX 405 400 21 75 24 25 108 90 92 110 042 3 5 BHZ 445 440 22 25 25 120 104 101 115 BHQ 425 420 22 25 25 114 100 96 110 048 4 0 BHZ 490 485 22 25 25 132 115 111 127 BHQ 445 440 22 25 25 120 104 101 115 BHX 445 440 22 26 126 107 95 112 060 5 0 BHZ 500 495 22 25 25 135 117 113 130 BHQ 495 490 22 25 26 137 122 109 122 BHX 465 460 22 26 25 133 113 99 116 X CEN...

Page 35: ...2 3 2 Units may be installed on combustable floors made from wood or class A B or C roof covering materials 3 Minimum Clearance of 1inch all sides of supply air duct for the first 3 foot of duct for 20 25 kW zero inches there after For all other heaters zero inch clearance all sides for entire length of duct 0 FRONT OVERALL OVERALL OVERALL COMPRESSOR SERVICE ACCESS COMPARTMENT PANEL REFRIGERANT CO...

Page 36: ...NECTION LOW VOLTAGE CONN 7 8 DIA KNOCKOUT 4 5 8 26 3 4 CONDENSATE DRAIN 3 4 NPTF HIGH VOLTAGE CONN 1 3 32 DIA KNOCKOUT LOW VOLTAGE CONN 7 8 DIA KNOCKOUT HIGH VOLTAGE CONN 1 31 32 x 7 8 KNOCKOUT 22 1 2 43 1 2 40 1 2 4 14 1 2 28 3 8 14 1 2 BACK 3 3 8 SIDE RETURN AIR OPENING 14 1 2 4 1 4 3 1 2 15 1 3 4 1 3 4 BOTTOM RETURN AIR OPENING 15 28 9 16 15 1 3 4 BOTTOM SUPPLY AIR OPENING CONDENSER COIL SIDE S...

Page 37: ...ions Unit Typical Slab on Ground Installation ROOF CURB INSTALLATION REAR DUCT ROOF CURB INSTALLATION BOTTOM DUCT SLAB ON GROUND INSTALLATION TO POWER SUPPLY SUPPLY AIR DUCT RETURN AIR DUCT FIELD SUPPLIED DISCONNECT SWITCH LOCATED TO REAR OF UNIT CONTROL WIRING TO INDOOR THERMOSTAT ...

Reviews: