333495-YTG-D-0609
Johnson Controls Unitary Products
75
Weights and Dimensions
BHX, BHQ and BHZ Unit Weights
Unit 4 Point Load Weight
Size
(Tons)
Model
Weight (lbs.)
Center of Gravity
4 Point Load Location (lbs.)
Shipping Operating
X
Y
A
B
C
D
024
(2.0)
BHZ
360
355
22.25
25
96
84
81
93
BHQ
360
355
22.25
25
96
84
81
93
BHX
385
380
22.25
25
103
90
87
100
030
(2.5)
BHZ
355
350
22.25
25
96
84
81
93
BHQ
380
375
22.25
25
102
89
86
98
036
(3.0)
BHZ
395
390
22.25
25
106
92
89
102
BHQ
405
400
22.25
25
109
95
92
105
BHX
405
400
21.75
24.25
108
90
92
110
042
(3.5)
BHZ
445
440
22.25
25
120
104
101
115
BHQ
425
420
22.25
25
114
100
96
110
048
(4.0)
BHZ
490
485
22.25
25
132
115
111
127
BHQ
445
440
22.25
25
120
104
101
115
BHX
445
440
22
26
126
107
95
112
060
(5.0)
BHZ
500
495
22.25
25
135
117
113
130
BHQ
495
490
22.25
26
137
122
109
122
BHX
465
460
22
26.25
133
113
99
116
X
CENTER OF
GRAVITY
49-1/8
FRONT
OF
UNIT
Y
47-1/4
"D"
"C"
"B"
"A"
Unit Accessory Weights
Unit Accessory
Model
Weight (lbs.)
Shipping
Operating
Add Economizer
All
45
40
Add Electric Heat
1
BHX, BHQ and BHZ
13
12
1. Weight given is for the maximum heater size available (25 kW).