333495-YTG-A-0407
50
Unitary Products Group
Heat Pump Unit Dimensions
Note:
For units applied with a roof curb, the minimum clearance may be reduced from 1 inch to 1/2 inch
between combustible roof curb material and this supply air duct.
Heat Pump Unit Dimensions
Unit Size
Dimensions
“A”
024, 036
33-1/2
042
1
, 048, 060
1. BHZ Models.
41-1/2
Heat Pump Unit Clearances
Direction
Distance
(in.)
Direction
Distance
(in.)
Top
1
1. Units must be installed outdoors. Over hanging structure or shrubs should not obscure condenser air
discharge outlet.
36
Right
24
Front
12
Left
24
Rear
0
Bottom
2
3
2. Units may be installed on combustable floors made from wood or class A, B or C roof covering
materials.
3. Minimum Clearance of 1inch all sides of supply air duct for the first 3 foot of duct for 20 & 25 kW., zero
inches there after. For all other heaters, zero inch clearance all sides for entire length of duct.
0