1.5 Operation

In normal operation contact 1 (COM) of the thermostat is on standby and 2 (NC) is closed. When a

temperature higher than the set value (100 °C) is detected the contact opens.
The temperature/smoke control board detects the open contact at the inlet of terminals J4, triggering

output relay K1 through terminals J5 (contact not live).
The YKN2Open board (A1) indicates high temperature faults with a 4-5 flashing sequences of the red

LED. If thermostat DPC-1 is fitted, the incident is indicated on the screen where the time is displayed

along with fault code 45.
Once the cause of the increase in temperature has disappeared, the thermostat must be manually reset

and the YKN2Open board (A1) reset to delete the incident.
Where the economiser accessory is fitted, check the position of jumper J20 on the economiser board.

Jumper J20 (outside damper closed with high temperature-smoke alarm) is open by default. If the jumper

is closed, outside damper open with high temperature-smoke alarm is selected.
In units equipped with a supply probe connected to the YKN2Open board, with hot water coil (accessory)

or economiser, if a supply temperature of over 80 °C is detected the equipment will stop and fault code

45 is displayed.

1.6 Installation

  N O T E

Bear in mind the current regulations on electrical installation in the country where the unit is to be installed.

A. Manual thermostat A25CN-9001.
B. Accessories.

1. Disconnect the main switch on the unit.
2. Fit the thermostat using the metal flange supplied

and two screws to the separator panel plate on the

supply air side.

3. Connect  brown  wires,  terminal  1  (COM),  and

terminal 2, (NC).

4. Set the thermostat to 100 ºC.
5. Fit  the  temperature/smoke  control  board  in  the

electrical box.

  N O T E

If the smoke detection accessory is also fitted, only one temperature/smoke control board is fitted

and the two normally closed contacts fitted in series in input J4.

6. Connect the brown wired to connector J4 of board A9. Connect the telephone cable to connector J2

or J8 on board A2.

7. Once all of the connections are made, reconnect the unit main switch.
8. Check that the green LED on board A9 remains lit. Next, search and configure the accessories by

pressing the test button on the YKN2Open board (A1) for more than three seconds, until the red

LED lights up. When the search and configuration process starts, the red LED on the board will light

up and will remain on until the operation is completed. Once it has switched off, check that the green

LED (V1) on board A9 is flashing to indicate that the accessory has been configured.

9. To check the electrical operation, disconnect the wires of terminals 1 and 2 of the thermostat and

check  that  the  YKN2Open  board  (A1)  indicates  the  high  temperature  fault  with  a  4-5  flashing

sequences of the red LED. Reconnect the wires and reset the YKN2Open (A1) board to delete the

fault.