036-21106-005 Rev. B (0505)
Unitary Products Group
13
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
AC036X1222
INDOOR COIL MODEL NO.
G1FA048S21
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM
1000
1200
1400
ID DB (°F)
85
80
75
85
80
75
85
80
75
ID WB (°F)
72
67
63
72
67
63
72
67
63
75
T.C.
36.7
34.3
32.3
36.9
34.9
32.8
37.2
35.4
33.2
S.C.
23.2
22.8
22.5
24.3
24.2
23.9
25.4
25.6
25.4
KW
2.31
2.30
2.27
2.33
2.30
2.28
2.34
2.31
2.30
85
T.C.
35.3
33.1
30.9
35.7
33.7
31.4
36.2
34.2
31.9
S.C.
23.2
22.6
21.9
24.8
24.3
23.6
26.3
26.0
25.3
KW
2.51
2.48
2.45
2.53
2.50
2.47
2.54
2.51
2.48
95
T.C.
34.0
31.9
29.6
34.5
33.6
30.0
35.1
33.0
30.5
S.C.
23.3
22.4
21.3
25.3
23.4
23.3
27.3
26.4
25.2
KW
2.71
2.67
2.64
2.73
2.73
2.66
2.74
2.71
2.67
105
T.C.
31.8
29.5
27.2
32.3
30.0
27.6
32.9
30.5
28.0
S.C.
22.6
21.6
20.5
24.8
23.7
22.5
26.9
25.8
24.5
KW
2.93
2.88
2.82
2.94
2.90
2.85
2.96
2.92
2.87
115
T.C.
29.6
27.2
24.8
30.1
27.6
25.1
30.6
28.0
25.4
S.C.
22.0
20.8
19.7
24.3
23.0
21.8
26.6
25.2
23.9
KW
3.15
3.09
3.01
3.16
3.11
3.04
3.18
3.13
3.07
125
T.C.
27.3
24.8
22.4
27.8
25.2
22.6
28.4
25.5
22.9
S.C.
21.4
20.0
19.0
23.8
22.3
21.1
26.2
24.6
23.2
KW
3.36
3.29
3.19
3.38
3.31
3.23
3.39
3.33
3.26
NOTE:
ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C.
S.C.
KW
F2RC/F2FC036
1.02
1.04
1.00
F2RP/F2FP036
1.02
1.03
1.00
F2RP/F2FP042
1.02
1.04
1.02
F2FP048
1.04
1.06
1.02
N1AHB1206
G2FD036(S,H)17
0.99
0.94
0.99
N1AHB1206
G2FD046(S,H)17
1.03
0.97
1.01
G1FA036S17,21
0.97
0.91
0.99
G1FA036S14
0.99
0.93
1.00
G1FA048S17
1.03
0.97
1.01
G1HD036
1.00
0.94
1.00
G1HD048
1.04
0.98
1.01
G1NA048S21D
1.03
0.99
1.01
G1NA036S17L
1.03
0.99
1.01
G1UA036S17,21
0.97
0.91
0.99
G1UA036S14
0.99
0.93
1.00
G1UA048S17
1.03
0.97
1.01
G1UA048S21
1.00
1.00
1.00
G2FD035(S,H)14
0.97
0.91
0.99
G2FD036(S,H)17
0.99
0.94
0.99
G2FD036(S,H)21
1.01
0.95
1.00
G2FD042(S,H)21
1.02
0.96
1.01
G2FD046(S,H)17
1.03
0.97
1.01
G2FD048(S,H)21,24
1.06
1.00
1.02