background image

7

4 - Program the thermostat

4.1 - Overview

The keyboard is located behind the thermostat flip-up cover. See
Fig. 6.  There are 16 keys to set, review and modify programmed
times and temperatures.  The liquid crystal display (LCD) shows
day, time or temperature and which programming period
is operating.

The thermostat can be set for two occupied and two unoccupied
time and temperatures for each day of the week (28 independent
settings). The two override keys provide quick temporary pro-
gramming changes for increased occupant comfort.

Important : To program the thermostat, 24 Vac is required (turn

on System power) and the keyboard lockout swit-
ch (see Fig. 4) must be in the ON-KEYBD position.

4.2 - Set current time/day

1. Set the current time by pressing and releasing the CLOCK

key once.

2. Press the + or - key until the current time appears on the LCD.

3. Set the current day by pressing and releasing the DAY key once.

4. Press the + or - key until the current day appears on the LCD.

Note : Su = Sunday; Mo = Monday; Tu = Tuesday; We =

Wednesday; Th = Thursday; Fr = Friday; Sa = Saturday.

4.3 - Set program times

Important : The thermostat will remain in occupied mode from

the point of initial programming until it encounters
the first unoccupied start time. To avoid the unne-
cessary occupied period following initial program-
ming, set a 12:00 AM unoccupied start time on the
thermostat when programmed.

Note : The programming times are in intervals of ten minutes;

i.e., 8:00, 8:10, 8:20...

1. Press the SELECT DAY key. The display shows the abbre-

viation for a day.

2. Press and hold the + or - key until the desired day appears.

3. Press the OCCUPIED START TIME key. The program indi-

cator will point to OCCUPIED.

4. Press and hold the + or - key until the desired start time

appears.

Note : If a start time is not required, press the CLEAR START

TIME key.

5. Press the UNOC START TIME key. The program indicator

will point to UNOCCUPIED.

6. Press and hold the + or - key until the desired start time

appears.

7. To program a second occupied start time for the selected day,

repeat Step 3 until four dashes ( ---- ) are displayed or the
second start time (if previously programmed) is displayed.
Then repeat Step 4.

8. To program a second unoccupied start time for the selected

day, repeat Step 5 until four dashes ( ---- ) are displayed or the
second start time (if previously programmed) is displayed.
Then repeat Step 6.

9. Repeat Steps l through 8 for each remaining day of the week

or refer to the following section, COPY A DAY.

4.4 - Copy a day

1. Press the SELECT DAY key. The display shows the abbre-

viation for a day.

2. Press and hold the + or - key until the day to be copied from

appears.

3. Press the COPY key.

4. Press and hold the + or - key until the day to be copied to

appears.

Note : The day to be copied from will remain on the display.

5. Press the COPY key a second time to perform the copy. 

6. Repeat Steps 3 to 5 to copy to another day.

4.5 - Set program temperature setpoints

Note : The setpoint temperature range is 7

°

C (unoccupied heat)

to 35

°

C (unoccupied cool). The occupied heat setpoint

must be at least 1

°

C less than the occupied cool setpoint

1. Press the SET TEMPERATURE key (OCCUPIED HEAT,

OCCUPIED COOL, UNOC HEAT, or UNOC COOL).  The
program indicator will point to OCCUPIED or UNOCCUPIED
and the LCD will indicate HEAT or COOL.

2. Press and hold the + or - key until the desired temperaure

appears.

3. Repeat Steps 1 and 2 until all four temperatures are set.

4.6 - Set operating display

The LCD can show time or temperature. To change the current
display, press the DISPLAY key until the desired operating dis-
play appears.

4.7 - Clear start time

1. Press the SELECT DAY key.

2. Press and hold the + or - key until the desired day appears.

3. Press and hold the OCCUPIED START TIME or the UNOC

START TIME key until the time to clear appears.

4. Press and hold the CLEAR START TIME key until the display

shows four dashes ( ---- ).

Note : If there is a second OCCUPIED setting, the start for time

this setting will appear instead of four dashes.

4.8 - Temporarily override program

There are three overrides available. The 3 hour occupied over-
rides can be initiated from the thermostat.

3 hour occupied

The 3 HOUR OCCUPIED key is used to override the unoccupied
program when people need to use the area temporarily (working
late, weekends or holidays).

SET START TIME

SET

SET TEMPERATURE

DATA CHANGE

OVERRIDE

CLOCK

SELECT

DAY

OCCUPIED

START TIME

OCCUPIED

HEAT

OCCUPIED

COOL

DISPLAY

+

3 HOUR

OCCUPIED

DAY

COPY

UNOC

START TIME

UNOC

HEAT

UNOC
COOL

CLEAR

START TIME

-

CONT
UNOC

OCCUPIED

UNOCCUPIED

CONT UNOC

3 HR OCCUPIED

HEAT

AM

11:32

Fig. 6 - Programming keys and LCD

Summary of Contents for 2ET04700224

Page 1: ...USER GUIDE Programmable Thermostat 2ET04700224 324 424 Roof Top units THERMOSTATS...

Page 2: ...battery 5 3 Wiring 6 3 1 Connections between thermostat and equipment terminals 2ET04700224 6 3 2 Connections between thermostat and equipment terminals 2ET04700324 6 3 3 Connections between thermosta...

Page 3: ...per hour rather than jumping from the energy savings setting to the comfort setting all at once This provides additional energy savings When the Intelligent RecoveryTM is used in the heating mode the...

Page 4: ...this operation remove battery for 15 minutes and begin The thermostat is factory set for conventional system control If using with a heat pump 2ET04700324 or 424 locate the mini jumper on the back of...

Page 5: ...ored the system will resume normal operation Without the battery the system will adopt the default setpoints Refer to the technical data Use the following steps to install a battery 1 Locate the batte...

Page 6: ...from terminals 8 and 10 on jumper plug connector P7 4 Only required on units with supplemental electric heat 3 3 Connections between thermostat and equipment terminals 2ET04700424 Note Use copper con...

Page 7: ...start time for the selected day repeat Step 5 until four dashes are displayed or the second start time if previously programmed is displayed Then repeat Step 6 9 Repeat Steps l through 8 for each rema...

Page 8: ...eassigned key value see Set or Key Value section 1 Press the 3 HOUR OCCUPIED key to change the unoccupied temperature setting to the occupied setpoint for three hours 2 Press the key to increase or pr...

Page 9: ......

Page 10: ...Europe Simplified Diagram Notes CUSTOMER INSTALLATION UNITARY equipment...

Page 11: ......

Page 12: ...Printed in France Manufacturer reserves the right to change specifications without prior notice E UG R9702 Europe...

Reviews: