background image

4

2.1 - New Installation

Run cable to a hole at the selected wall location for the thermo-
stat and pull about 75 mm of wire through the opening. Color-
coded thermostat cable with at least one conductor for each
wiring terminal is recommended. Good service practice recom-
mends selecting a cable with one or two extra conductors than
the immediate application requires.

If using remote temperature sensor(s), refer to the mounting ins-
tructions included with the device for wiring cable requirements.
Route cable away from sources of electrical interference.

2.2 - Mount subbase or wallplate

The subbase or wallplate can be mounted on a horizontal outlet
box or directly on the wall.

For a wall installation, hold subbase or wallplate in position and
mark holes for the screws. See figure 1. Screws and wall plugs
must be obtained locally. Be careful that the wires do not fall
back into the wall opening. Set aside subbase or wallplate.

2.3 - Set subbase DIP switches

The Subbase provides the Thermostat with an interface to the
single zone HVAC system.  See Table 1 for DIP switch settings.
The subbase DIP switches are located on the front and to the
right of the wiring terminals. See Fig.2. Set the DIP switches for
the system being controlled.

Table 1 - Subbase DIP switch settings

a. No effect on 2 heat/1 cool Thermostats/ 2ET04700324.
b. Factory setting.
c. No effect on heat pump subbases : 2ET04700324/424.

2.4 - Set thermostat mini-jumper

Note : This operation must be done prior to installing the

batteries. If batteries are installed prior to this operation,
remove battery for 15 minutes and begin.

The thermostat is factory-set for conventional system control. If
using with a heat pump 2ET04700324 or 424, locate the mini-
jumper on the back of the display. See Fig. 3. Pull the mini-jum-
per off the two CONV pins and move to the two HEAT PUMP
pins. This changes the thermostat to the heat pump algorithm.

If you wish to change the control of the thermostat because a
new subbase has been purchased, remove battery for 15
minutes, change mini-jumper position, and re-install battery.

2.5 - Set display DIP switches

The thermostat DIP switches provide the thermostat with an
interface to the single zone HVAC system. See Table 2 for DIP
switch settings. The display DIP switches are located on the
back of the thermostat. See Fig. 4. Set the DIP switches for the
desired thermostat features and the system being controlled.

CA1

CA2

CA3 CA4

CA5

LED1 LED2 COM

Y1

G

RC

RH

B

A3

A2

A1

W2

Y2

T

T

Switch

Setting

Function

1a

ONb

2 stages heat

OFF

1 stage heat

2a

ONb

2 stages cool

OFF

1 stage cool

ONb

Proportional plus integral (P+I)

3

control (droopless)

OFF

Proportional control (allows droop)

4c

ONb

Energizes fan on cool only

OFF

Energizes fan on heat and cool

5

ONb

Use internal sensor

OFF

Use remote sensor

2 - Installation

CA1

CA2

CA3

CA4 CA5

LED1 LED2 COM

Y1

G

RC

RH

B

A3

A2

A1

W2

Y2

T

T

0

N

1

2

3

4

5

4

1

T7300 ONLY

HEAT PUMP

CONV

0

N

1

2

3

4

5

°

C

24

CON

OFF

°

F - TEMP

12 HR. TIME

INT - FAN

ON - KEYBD

0

N

°

F - TEMP

12 HR. TIME

INT - F

A

N

ON - KEYBD

1

2

T7300 ONLY

HEAT PUMP

CONV

0

N

1

2

3

4

5

°

C

24

CON

OFF

°

F - TEMP

12 HR. TIME

INT - FAN

ON - KEYBD

0

N

1

2

3

4

5

°

C

24

CON

OFF

°

F - 

TEMP

12 HR. 

TIME

INT

 - F

A

N

ON - KEYBD

Fig. 1

Fig. 2 - Subbase DIP switches

Fig. 3 - Setting thermostat mini-jumper

Fig. 4 - Display DIP switches

Summary of Contents for 2ET04700224

Page 1: ...USER GUIDE Programmable Thermostat 2ET04700224 324 424 Roof Top units THERMOSTATS...

Page 2: ...battery 5 3 Wiring 6 3 1 Connections between thermostat and equipment terminals 2ET04700224 6 3 2 Connections between thermostat and equipment terminals 2ET04700324 6 3 3 Connections between thermosta...

Page 3: ...per hour rather than jumping from the energy savings setting to the comfort setting all at once This provides additional energy savings When the Intelligent RecoveryTM is used in the heating mode the...

Page 4: ...this operation remove battery for 15 minutes and begin The thermostat is factory set for conventional system control If using with a heat pump 2ET04700324 or 424 locate the mini jumper on the back of...

Page 5: ...ored the system will resume normal operation Without the battery the system will adopt the default setpoints Refer to the technical data Use the following steps to install a battery 1 Locate the batte...

Page 6: ...from terminals 8 and 10 on jumper plug connector P7 4 Only required on units with supplemental electric heat 3 3 Connections between thermostat and equipment terminals 2ET04700424 Note Use copper con...

Page 7: ...start time for the selected day repeat Step 5 until four dashes are displayed or the second start time if previously programmed is displayed Then repeat Step 6 9 Repeat Steps l through 8 for each rema...

Page 8: ...eassigned key value see Set or Key Value section 1 Press the 3 HOUR OCCUPIED key to change the unoccupied temperature setting to the occupied setpoint for three hours 2 Press the key to increase or pr...

Page 9: ......

Page 10: ...Europe Simplified Diagram Notes CUSTOMER INSTALLATION UNITARY equipment...

Page 11: ......

Page 12: ...Printed in France Manufacturer reserves the right to change specifications without prior notice E UG R9702 Europe...

Reviews: