background image

5

2 - Installation (cont’d)

Table 2 - Display DIP switch settings

a : Factory settings.

2.6 - Mount thermostat

Caution

Always disconnect power supply and remove battery from the
thermostat before connecting the ribbon cables to prevent elec-
trical shock and equipment damage.

Use the Following procedure to connect the display ribbon
cables to the subbase.

1. Check that the 24 Vac power supply is disconnected.

2. Check that the 9 Vdc battery is not installed in the display.

Important : First be sure to connect the 12 pin ribbon cable to

the base.

3. Connect the 12 pin (larger) ribbon cable to the display. See

Fig. 4.

4. Connect the 9 pin (smaller) ribbon cable to the display.

5. If using a 9 Vdc battery, go to the Install Battery backup sec-

tion for installation instructions.

2.7 - Install battery

The 9 volts battery is not necessary for the operation of the ther-
mostat, but holds the program during power outages. When the
power is restored, the system will resume normal operation.
Without the battery, the system will adopt the default setpoints.
Refer to the "technical data". Use the following steps to install a
battery :

1. Locate the battery holder on the back of the display.

2. Slide the battery up to the connector until it is firmly seated.

Notes : Observe the polarity when snapping a 9 volt alkaline bat-

tery into the holder.
The plugs must be firmly seated on the connectors for
the thermostat to work properly

3. Hang the top edge of the display on the subbase hooks. See

Fig. 5.

4. Swing down and press on the lower edge until the thermostat

snaps in place.

5. Insert and tighten three Allen head screws on the bottom of

the thermostat. See Fig. 5.

Switch

Setting

Function 

1

ONa

°

F display

OFF

°

C display

2

ONa

12 hour clock display 

OFF

24 hour clock display

ONa

Continuous fan operation in occupied 

3

period

OFF

Intermittent fan operation in occupied 
period

4

Non functional switch

ONa

Keyboard is used for programming

5

OFF

Keyboard disabled, but can be used  
to review program, perform overrides 
and make clock changes.

1

Fig. 5 - Ribbon cable and display monting

Summary of Contents for 2ET04700224

Page 1: ...USER GUIDE Programmable Thermostat 2ET04700224 324 424 Roof Top units THERMOSTATS...

Page 2: ...battery 5 3 Wiring 6 3 1 Connections between thermostat and equipment terminals 2ET04700224 6 3 2 Connections between thermostat and equipment terminals 2ET04700324 6 3 3 Connections between thermosta...

Page 3: ...per hour rather than jumping from the energy savings setting to the comfort setting all at once This provides additional energy savings When the Intelligent RecoveryTM is used in the heating mode the...

Page 4: ...this operation remove battery for 15 minutes and begin The thermostat is factory set for conventional system control If using with a heat pump 2ET04700324 or 424 locate the mini jumper on the back of...

Page 5: ...ored the system will resume normal operation Without the battery the system will adopt the default setpoints Refer to the technical data Use the following steps to install a battery 1 Locate the batte...

Page 6: ...from terminals 8 and 10 on jumper plug connector P7 4 Only required on units with supplemental electric heat 3 3 Connections between thermostat and equipment terminals 2ET04700424 Note Use copper con...

Page 7: ...start time for the selected day repeat Step 5 until four dashes are displayed or the second start time if previously programmed is displayed Then repeat Step 6 9 Repeat Steps l through 8 for each rema...

Page 8: ...eassigned key value see Set or Key Value section 1 Press the 3 HOUR OCCUPIED key to change the unoccupied temperature setting to the occupied setpoint for three hours 2 Press the key to increase or pr...

Page 9: ......

Page 10: ...Europe Simplified Diagram Notes CUSTOMER INSTALLATION UNITARY equipment...

Page 11: ......

Page 12: ...Printed in France Manufacturer reserves the right to change specifications without prior notice E UG R9702 Europe...

Reviews: