Electrical connection
24
Module No.:
The setting of the DIP address has been set at the delivery of the unit. If module’s centralized control shall be
adopted on the site, it is required to reset the address of each module (the addresses set at the delivery are all the 1
#). See specifics in the followings:
Model Address DIP301-1 DIP301-2 DIP301-3 DIP301-4
1#
ON
OFF
OFF
OFF
2#
OFF
ON
OFF
OFF
3#
ON
ON
OFF
OFF
4#
OFF
OFF
ON
OFF
5#
ON
OFF
ON
OFF
6#
OFF
ON
ON
OFF
7#
ON
ON
ON
OFF
8#
OFF
OFF
OFF6
ON
DIP301's
dialing code 5/6/7/8 shall be reserved.
Note:
When the main board is energized, the dialing switch is prohibited to be set.
The wire controller and the 7-inch touch screen shall be used as the controller, and only 8 modules
can be controlled at most
Model setting:
Model
DIP302-1 DIP302-2 DIP302-3
20TR
ON
OFF
30TR
OFF
ON
40/50TR
ON
ON
China
OFF
North America
ON
DIP302's
dialing code 4/5/6/7/8 shall be reserved.
Settings for Mode:
0-refrigeration; 1-heating; 2-heat recovery; 8-water pump cycle
Only 1# module is valid, which is set by HMI
If the condition of unmatched setting occurs, the fault of unmatched setting will be reported.