background image

66901 / 035-20393-001 Rev. C (1204)

Unitary Products Group

7

DEHUMIDIFICATION CONTROL

A dehumidification control accessory 2HU06700124 may be used with
variable speed air handlers or furnaces in high humidity areas. This
control works with the variable speed indoor unit to provide cooling at a
reduced air flow, lowering evaporator temperature and increasing latent
capacity. The humidistat in this control opens the humidistat contacts on
humidity rise. To install, refer to instructions packaged with the acces-
sory and Figures 7-9. Prior to the installation of the dehumidification
control, the jumper across the HUMIDISTAT terminals on the indoor
variable speed air handler or furnace CFM selection board must be
removed.

During cooling, if the relative humidity in the space is higher than the
desired set point of the dehumidification control, the variable speed
blower motor will operate at lower speed until the dehumidification con-
trol is satisfied. A 40-60% relative humidity level is recommended to
achieve optimum comfort.

If a dehumidification control is installed, it is recommended that a mini-
mum air flow of 325 cfm/ton be supplied at all times.

SECTION VI: EVACUATION

It will be necessary to evacuate the system to 500 microns or less. If a
leak is suspected, leak test with dry nitrogen to locate the leak. Repair
the leak and test again. 

To verify that the system has no leaks, simply close the valve to the vac-
uum pump suction to isolate the pump and hold the system under vac-
uum. Watch the micron gauge for a few minutes. If the micron gauge
indicates a steady and continuous rise, it’s an indication of a leak. If the
gauge shows a rise, then levels off after a few minutes and remains
fairly constant, it’s an indication that the system is leak free but still con-
tains moisture and may require further evacuation if the reading is
above 500 microns.

SECTION VII: SYSTEM CHARGE

The factory charge in the outdoor unit includes enough charge for the
unit and the highest sales volume evaporator. Some indoor coil
matches may require additional charge. See tabular data sheet pro-
vided in unit literature packet for charge requirements.

The “TOTAL SYSTEM CHARGE” must be permanently stamped on the
unit data plate.

Total system charge is determined as follows:

1.

Determine outdoor unit charge from tabular data sheet.

2.

Determine indoor coil adjustment from tabular data sheet.

3.

Calculate the line charge using the tabular data sheet if line length
is greater than 15 feet.

4.

Total system charge = item 1 + item 2 + item 3.

5.

Permanently stamp the unit data plate with the total amount of
refrigerant in the system.

Use the following subcooling charging method whenever additional
refrigerant is required for the system charge. A superheat charging
method is not suitable for TXV equipped systems.

Measurement Method

If a calibrated charging cylinder or accurate weighing device is avail-
able, add refrigerant accordingly.

Check flare caps on service ports to be sure they are leak tight. DO
NOT OVERTIGHTEN (between 40 and 60 inch - lbs. maximum).

Subcooling Charging Method

This condensing unit must only be used with the matching thermostatic
expansion valve kit listed in the Tabular Data Sheet. This unit 

must

 be

charged during 

second-stage (Y1  & Y2) 

operation only

See Tables 2-

7 for unit specific subcooling charts.

For mix matched systems, the recommended subcooling is 10°F

1.

Set the system running in the 

Second-Stage (Y1 + Y2) 

cooling

mode by setting the thermostat at least 6°F below the room tem-
perature.

2.

Operate the system for a minimum of 15-20 minutes.

3.

Refer to the tabular data sheet for the recommended airflow and
verify this indoor airflow (it should be about 400 SCFM per ton).

4.

Measure the liquid refrigerant pressure P and temperature T at the
service valve.

5.

Calculate the saturated liquid temperature ST from Table 1.

6.

Subcooling temperature TC = Saturated Temperature (ST) - Liquid
Temp (T).

Add charge if the calculated subcooling temperature TC in Step 6 is
lower than the recommended level. Remove and recover the refrigerant
if the subcooling TC is higher than the recommended level. See Table 1
for R-410A saturation temperatures. 

R-410A refrigerant cylinders are rose colored, and have a dip tube
which allows liquid to flow out of the cylinder in the Upright Posi-
tion.
 Always charge the system slowly with the tank in the upright
position.

Do not leave the system open to the atmosphere.  Unit damage
could occur due to moisture being absorbed by the POE oil in the
system.  This type of oil is highly susceptible to moisture absorp-
tion.

Refrigerant charging should only be carried out by a qualified air
conditioning contractor.

Compressor damage will occur if system is improperly charged. On
new system installations, charge system per tabular data sheet for
the matched coil and follow guidelines in this instruction.

Example: The pressure P and temperature T measured at the liquid 
service port is 360 Psig and 93°F. From Table 1, the saturated tem-
perature for 360 Psig is 109°. The subcooling temperature TC = 
109°-93°=16°F

Summary of Contents for 15 SEER - CZE

Page 1: ...h if not avoided may result in minor or moderate injury It is also used to alert against unsafe practices and hazards involving only property dam age INSPECTION As soon as a unit is received it should...

Page 2: ...nches apart coil face to coil face If the unit is to be installed on a hot sun exposed roof or a black topped ground area the unit should be raised sufficiently above the roof or ground to avoid takin...

Page 3: ...d care must be taken to avoid sharp bends which may cause a restriction 2 The lines should be installed so that they will not obstruct service access to the coil air handling system or filter 3 Care m...

Page 4: ...er cap and with an allen wrench back out counter clockwise until valve stem just touches the chamfered retaining wall See Page 4 PRECAU TIONS DURING BRAZING SERVICE VALVE 13 Replace plunger cap finger...

Page 5: ...er supply connections FIELD CONNECTIONS CONTROL WIRING 1 Route low voltage wiring into bottom of control box Make low volt age wiring connections inside the junction box per Figures 7 9 2 The complete...

Page 6: ...HERMOSTAT E Y2 Y2 HUM BLU YEL YEL BLK RED 1 VARIABLE SPEED FURNACE 2 STAGE AIR CONDITIONER C Y1 R W O HUMIDISTAT CONTACTS OPEN ON HUMIDITY RISE JUMPER MUST BE IN POSITION HUMIDISTAT INSTALLED YES G C...

Page 7: ...the tabular data sheet if line length is greater than 15 feet 4 Total system charge item 1 item 2 item 3 5 Permanently stamp the unit data plate with the total amount of refrigerant in the system Use...

Page 8: ...lclean mix one part Coilclean to seven parts water Allow solution to remain on coil for 30 minutes before rinsing with clean water Solution should not be permitted to come in contact with painted surf...

Page 9: ...12 110 449 11 451 11 454 11 457 12 115 478 11 480 11 483 11 486 12 120 507 10 509 10 512 11 515 11 125 537 10 539 10 542 10 545 10 TABLE 4 15Z48AC Subcooling Charging Chart Outdoor Ambient Indoor Wet...

Page 10: ...LED Status LED Description Status LED Troubleshooting Information Green POWER Module has power Supply voltage is present at module terminals Red TRIP Thermostat demand signal Y1 is present but the com...

Page 11: ...66901 035 20393 001 Rev C 1204 Unitary Products Group 11 SECTION IX WIRING DIAGRAM FIGURE 10 Wiring Diagram...

Page 12: ...e without notice Printed in U S A 66901 035 20393 001 Rev C 1204 Copyright by York International Corp 2004 All rights reserved Supersedes 035 20393 001 Rev A 0704 Unitary 5005 Norman Product York OK G...

Reviews: