background image

036-21137-004 Rev. C (0505)

Unitary Products Group

5

PROCEDURES:

1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and for 15 feet of interconnecting line tubing.

2. Verify the orifice size and additional charge required for specific evaporator coil in the system using the above table.

3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.

4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evap adder 

for line set.

5. If the orifice in the evaporator was changed, verify the evaporator nameplate has been marked with the correct orifice size.

Additional R-22 Charge / Orifice Size for Various Matched Systems - 3 Phase

Outdoor Unit 

H1RC036S

H1RC048S

H1RC060S

Unit Orifice (s) 

1

Factory R-22 Charge, lbs-oz

6 - 2

7 - 10

9 - 3

Indoor Coil

Coil Orifice 

TVX Kit

2

 = Additional Charge, Oz

3

G2FD035(S,H)14

65

702 + 0

G2FD036(S,H)17,21

75

702 + 3

G2FD042(S,H)21

78

702 + 0

G2FD046(S,H)17

78

702 + 9

703 + 0

G2FD048(S,H)21,24

84

702 + 17

703 + 9

G2FD060(S,H)24

90

703 + 0

703 + 20

G2FD061H24

90

703 + 6

703 + 25

G1FA/G1UA036S14

73

702 + 1

G1FA/G1UA036S17,21

73

702 + 0

G1FA/G1UA048S17

84

703 + 2

G1FA/G1UA048S21

84

702 + 9

703 + 7

G1FA/G1UA060S21,24

90

703 + 14

703 + 20

G1NA036S17L

71

702 + 0

G1NA048S21D

78

702 + 0

703 + 0

G1NA048S24P

78

702 + 0

703 + 0

G1NA060S24T

87

703 + 0

G1NF036SOF

67

702 + 0

G1NF048SOF

78

702 + 0

G1NF060SOF

87

703 + 0

G1HD036

69

702 + 5

G1HD048

81

702 + 11

703 + 0

G1HD060

93

703 + 0

703 + 20

FOOTNOTES:

1. These orifices are factory mounted in the flow control device of each indoor coil and must be removed for TXV installation.

2. A TXV kit must be used with these coils to obtain system performance. (701,702,703 indicates 1TV07 ...series).

3. Systems matched with furnaces or air handlers not equipped with blower-off delays, may require blower Time Delay Kit #6918A5011.

Summary of Contents for 12 SEER H*RC018 THRU 060

Page 1: ...ssure and temperature This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protects the compressor if undesirable operating condi tions occur...

Page 2: ...S46 H1RC048S46 H1RC060S46 Unit Supply Voltage 208 230 3 60 460 3 60 Normal Voltage Range 1 187 to 252 432 to 504 Minimum Circuit Ampacity 13 3 18 9 22 9 7 6 9 6 12 0 Max Overcurrent Device Amps 2 20 3...

Page 3: ...0 S H 24 90 87 15 703 15 703 5 G2FD061H24 90 87 19 703 19 703 11 G1HA024H14 61 053 03 059 03 G1HA024H14 T TXV 701 03 03 G1HA036H14 75 59 12 63 11 73 08 G1HA036H14 T TXV 702 11 08 G1HA036H17 78 63 14 7...

Page 4: ...2 3 RP024N H06 T 61 53 4 59 4 701 4 701 4 F 2 3 RP030N06 T 65 59 6 63 4 701 6 701 4 F 2 3 RP036N06 T 75 63 4 73 8 701 4 702 8 F 2 3 RP042N06 T 78 73 13 78 0 702 13 702 0 F 2 3 FP048N06 T 84 73 16 78...

Page 5: ...RC060S Unit Orifice s 1 Factory R 22 Charge lbs oz 6 2 7 10 9 3 Indoor Coil Coil Orifice TVX Kit2 Additional Charge Oz3 G2FD035 S H 14 65 702 0 G2FD036 S H 17 21 75 702 3 G2FD042 S H 21 78 702 0 G2FD0...

Page 6: ...5 18 21 G2FD048 S H 21 1400 43 0 30 6 13 00 11 55 N1VSC16 10 15 18 21 G2FD048 S H 21 1590 47 0 30 6 12 80 11 40 H2RC048S06 N1VSC16 10 15 18 21 G2FD048 S H 21 1590 47 0 34 9 12 80 12 80 11 40 N1VSD20 1...

Page 7: ...16 9 12 00 12 00 11 00 14 G1UA036S14 750 24 2 17 6 12 00 12 00 11 25 17 21 G1UA036S17 21 750 24 0 17 3 12 00 12 00 11 10 14 17 G2FD024 S H 14 17 750 23 6 16 9 12 00 12 00 11 00 17 G2FD030 S H 17 750 2...

Page 8: ...G1FA036S14 1235 33 4 25 0 11 50 10 65 17 21 G1FA036S17 21 1235 33 0 24 4 11 50 10 55 21 G1FA048S21 1235 35 0 25 9 12 00 10 70 G1HD036 1235 33 4 24 7 11 80 10 70 G1HD048 1235 35 0 25 8 12 00 11 05 17 G...

Page 9: ...G1FA060S21 24 1600 47 0 34 8 12 50 11 45 G1HD048 1600 45 0 33 3 12 00 11 15 G1HD060 1600 46 5 36 1 12 40 11 40 21 G1NA048S21D 1400 46 0 34 0 12 00 11 20 17 G1UA048S17 1500 44 5 32 9 12 00 10 50 21 G1...

Page 10: ...12 00 11 15 P1DUB16V G2FD036 S H 17 17 1200 34 4 24 2 12 25 11 40 P1DUC20V PV8C20 UH G1FA036S21 21 1200 33 6 23 6 12 00 11 30 P1DUC20V PV8C20 UH G2FD036 S H 21 21 1200 34 8 24 4 13 00 11 60 P1XDB12V...

Page 11: ...1 T 21 1640 56 0 41 8 12 10 10 10 P1XUC20V G2FD060 S H 24 T 24 1640 56 0 41 8 12 10 10 10 P1XUC20V G2FD061H24 24 1640 56 5 42 0 12 10 10 25 P1XUD20V G1FA G1UA060S24 T 24 1620 56 0 41 6 12 10 10 30 P1X...

Page 12: ...at Add sub base for 1H 1C 1H 1C manual change over electronic non programmable thermostat 1H 1C auto manual changeover electronic programmable deluxe 7 day thermostat 1H 1C auto manual changeover elec...

Page 13: ...30 1 60 CONTACTOR TERMINALS COIL GND LUG C Y R G W Y R G W POWER WIRING CONTROL WIRING FACTORY WIRING 24 VOLT CONTROL WIRING MINIMUM 18 GA WIRE NEC CLASS 2 FURNACE OR AIR HANDLER TERMINAL BLOCK ROOM T...

Page 14: ...14 2 13 6 KW 1 47 1 45 1 43 1 48 1 47 1 45 1 49 1 48 1 46 105 T C 18 1 16 3 14 2 18 7 17 1 15 0 19 4 17 8 15 8 S C 11 3 10 6 9 7 13 0 12 2 11 3 14 7 13 8 12 9 KW 1 58 1 55 1 52 1 59 1 57 2 53 1 61 1 5...

Page 15: ...6 2 07 2 02 1 98 2 09 2 04 2 00 115 T C 21 3 18 6 16 2 22 0 19 5 17 0 22 8 20 5 17 7 S C 14 0 12 9 12 0 16 3 15 3 14 2 18 6 17 8 16 4 KW 2 19 2 13 2 08 2 22 2 16 2 10 2 25 2 18 2 12 125 T C 19 8 16 4...

Page 16: ...3 19 5 KW 2 70 2 61 2 55 2 74 2 64 2 57 2 77 2 68 2 59 125 T C 24 0 20 4 17 0 26 7 21 7 16 8 29 4 23 2 16 7 S C 17 1 15 6 14 1 20 2 17 9 16 0 23 3 20 5 17 8 KW 2 88 2 76 2 70 2 94 2 79 2 70 3 00 2 84...

Page 17: ...2 22 6 28 4 25 5 22 9 S C 21 4 20 0 19 0 23 8 22 3 21 1 26 2 24 6 23 2 KW 3 36 3 29 3 19 3 38 3 31 3 23 3 39 3 33 3 26 NOTE ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH 10...

Page 18: ...33 4 30 8 27 2 33 6 31 3 27 7 S C 23 7 22 5 20 7 24 5 23 6 21 9 25 4 24 6 23 0 KW 4 01 3 88 3 75 4 02 3 91 3 77 4 03 3 93 3 78 125 T C 31 0 27 6 23 5 31 1 28 1 24 1 31 3 28 5 24 4 S C 23 1 21 3 19 6 2...

Page 19: ...37 4 43 9 41 5 38 1 44 2 42 0 38 9 S C 28 4 27 6 25 9 30 0 29 7 28 2 31 6 31 8 30 5 KW 3 39 3 38 3 36 3 39 3 38 3 36 3 40 3 39 3 37 115 T C 41 2 38 1 34 1 41 6 38 7 34 9 42 0 39 3 35 7 S C 27 8 26 7...

Page 20: ...2 6 41 9 37 2 33 1 S C 30 5 28 3 26 3 33 1 30 5 28 4 35 7 32 8 30 5 KW 4 28 4 15 4 02 4 32 4 17 4 05 4 35 4 19 4 08 125 T C 36 3 31 3 28 5 36 9 31 9 28 8 37 6 32 5 29 1 S C 29 2 26 8 24 8 31 8 28 9 26...

Page 21: ...6 2 42 5 39 3 36 2 S C 30 5 30 6 29 5 30 9 32 6 32 8 31 5 32 8 34 1 34 2 32 7 34 5 KW 4 67 4 45 4 25 4 03 4 72 4 49 4 30 4 09 4 74 7 53 4 34 4 18 115 T C 41 8 38 3 35 3 31 7 42 3 38 8 35 8 33 0 42 5 3...

Page 22: ...50 0 53 4 57 6 45 7 50 4 53 7 57 9 S C 40 6 38 6 39 8 39 6 43 1 40 6 41 9 41 6 44 6 42 4 43 5 43 2 KW 7 5 8 1 8 6 9 3 7 5 8 1 8 6 9 2 7 4 8 1 8 5 9 1 115 T C 42 3 46 7 50 1 53 9 42 9 47 4 50 4 54 4 4...

Page 23: ...43 1 42 6 41 6 KW 5 24 5 10 5 06 5 25 5 11 5 07 5 26 5 12 5 08 105 T C 58 1 54 6 50 0 58 9 55 7 51 3 59 7 56 8 52 7 S C 36 9 36 0 34 4 39 8 39 0 37 3 42 7 41 9 40 2 KW 5 86 5 72 5 63 5 87 5 74 5 64 5...

Page 24: ...ING INDOOR COMPONENTS G1UA 1 2 CASED UPFLOW G1HD HORIZONTAL DUCT G2FD MULTI POSITION UPFLOW HORIZONTAL AND DOWNFLOW Available with factory installed horizontal drain pan ADD ON COILS FOR FURNACE APPLI...

Reviews: