York 12 SEER H*RC018 THRU 060 Technical Manual Download Page 7

036-21137-004 Rev. C (0505)

Unitary Products Group

7

COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils

UNIT MODEL

FURNACE**

COIL

MODEL

COOLING

CFM RANGE

(Min.-max.)

W

RATED  CFM

NET MBH

SEER

W/O TXV

SEER + TXV

1

EER

TOTAL

SENS.

H2RC018S06

525
675

14,17

G1FA024S14,17

600

19.2

13.0

12.00*

12.00

11.35

14

G1HA024H14

600

19.2

13.6

12.00*

11.50

14

G1HA024H14T

600

19.2

13.6

12.00*

11.60

-

G1HD024

600

20.0

13.5

12.50*

12.50

11.70

17

G1NA030S17K

600

20.0

13.5

12.75*

12.75

11.75

21

G1NA030S21M

600

20.0

13.5

12.50*

12.50

11.75

14,17

G1UA024S14,17

600

19.2

13.0

12.00*

12.00

11.35

14,17

G2FD024(S,H)14,17

600

19.6

13.2

12.50*

12.50

11.60

17

G2FD030(S,H)17

600

20.0

13.5

12.60*

12.60

11.75

14

G2FD035(S,H)14

600

20.0

13.5

12.60*

12.60

11.75

H2RC024S06

650
850

14,17

G1FA024S14,17

750

23.0

16.4

11.80*

11.80

10.70

14

G1FA030S14

750

23.6

16.9

12.00*

12.00

11.00

14

G1FA036S14

750

24.2

17.6

12.00*

12.00

11.25

17,21

G1FA036S17,21

750

24.0

17.3

12.00*

12.00

11.10

14

G1HA024H14

750

19.2

13.6

12.00*

10.90

14

G1HA024H14T

800

23.5

16.7

12.00*

10.90

14

G1HA036H14

800

24.6

17.5

12.00

11.35

-

G1HD024

750

24.0

17.2

12.00*

12.00

11.05

-

G1HD036

750

24.6

17.6

12.10*

12.10

11.35

17

G1NA030S17K

750

24.0

17.2

12.00*

12.00

11.15

21

G1NA030S21M

750

24.0

17.2

12.00*

12.00

11.15

14,17

G1UA024S14,17

750

23.0

16.4

11.80*

11.80

10.70

14

G1UA030S14

750

23.6

16.9

12.00*

12.00

11.00

14

G1UA036S14

750

24.2

17.6

12.00*

12.00

11.25

17,21

G1UA036S17,21

750

24.0

17.3

12.00*

12.00

11.10

14,17

G2FD024(S,H)14,17

750

23.6

16.9

12.00*

12.00

11.00

17

G2FD030(S,H)17

750

24.0

17.3

12.00*

12.00

11.10

14

G2FD035(S,H)14

750

24.0

17.3

12.10*

12.10

11.10

17

G2FD036(S,H)17

750

24.6

17.8

12.15*

12.15

11.35

H2RC030S06

875

1125

14

G1FA030S14

1000

29.2

20.7

11.85*

11.85

10.80

14

G1FA036S14

1000

30.4

21.6

12.00*

12.00

11.10

17,21

G1FA036S17,21

1000

30.0

21.3

12.00*

12.00

11.00

17

G1FA048S17

1000

31.2

22.3

12.50*

12.50

11.45

21

G1FA048S21

1000

31.2

22.3

12.50*

12.50

11.35

14

G1HA036H14

1000

30.3

21.5

12.00*

11.25

14

G1HA036H14

1000

30.2

21.4

12.00*

11.25

17

G1HA036H17

1000

30.4

21.9

12.00*

11.35

17

G1HA036H17T

1000

30.5

22.0

12.00*

11.35

-

G1HD036

1000

30.8

21.9

12.75*

12.75

11.25

17

G1NA030S17K

1000

30.2

21.4

12.00*

12.00

11.05

21

G1NA030S21M

1000

30.2

21.4

12.00*

12.00

11.05

17

G1NA036S17L

1000

31.4

22.3

12.50*

12.50

11.45

14

G1UA030S14

1000

29.2

20.7

11.85*

11.85

10.80

14

G1UA036S14

1000

30.4

21.6

12.00*

12.00

11.10

17,21

G1UA036S17,21

1000

30.0

21.3

12.00*

12.00

11.00

17

G1UA048S17

1000

31.2

22.3

12.50*

12.50

11.45

21

G1UA048S21

1000

31.2

22.3

12.50*

12.50

11.35

17

G2FD030(S,H)17

1000

30.0

21.3

12.00*

12.00

11.00

14

G2FD035(S,H)14

1000

30.0

21.3

12.00*

12.00

11.00

17

G2FD036(S,H)17

1000

30.6

21.8

12.25*

12.25

11.20

21

G2FD036(S,H)21

1000

30.8

21.9

12.25*

12.25

11.25

21

G2FD042(S,H)21

1000

31.0

22.1

12.50*

12.50

11.35

17

G2FD046(S,H)17

1000

31.4

22.3

12.50*

12.50

11.45

For Notes See Page 9.

Summary of Contents for 12 SEER H*RC018 THRU 060

Page 1: ...ssure and temperature This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protects the compressor if undesirable operating condi tions occur...

Page 2: ...S46 H1RC048S46 H1RC060S46 Unit Supply Voltage 208 230 3 60 460 3 60 Normal Voltage Range 1 187 to 252 432 to 504 Minimum Circuit Ampacity 13 3 18 9 22 9 7 6 9 6 12 0 Max Overcurrent Device Amps 2 20 3...

Page 3: ...0 S H 24 90 87 15 703 15 703 5 G2FD061H24 90 87 19 703 19 703 11 G1HA024H14 61 053 03 059 03 G1HA024H14 T TXV 701 03 03 G1HA036H14 75 59 12 63 11 73 08 G1HA036H14 T TXV 702 11 08 G1HA036H17 78 63 14 7...

Page 4: ...2 3 RP024N H06 T 61 53 4 59 4 701 4 701 4 F 2 3 RP030N06 T 65 59 6 63 4 701 6 701 4 F 2 3 RP036N06 T 75 63 4 73 8 701 4 702 8 F 2 3 RP042N06 T 78 73 13 78 0 702 13 702 0 F 2 3 FP048N06 T 84 73 16 78...

Page 5: ...RC060S Unit Orifice s 1 Factory R 22 Charge lbs oz 6 2 7 10 9 3 Indoor Coil Coil Orifice TVX Kit2 Additional Charge Oz3 G2FD035 S H 14 65 702 0 G2FD036 S H 17 21 75 702 3 G2FD042 S H 21 78 702 0 G2FD0...

Page 6: ...5 18 21 G2FD048 S H 21 1400 43 0 30 6 13 00 11 55 N1VSC16 10 15 18 21 G2FD048 S H 21 1590 47 0 30 6 12 80 11 40 H2RC048S06 N1VSC16 10 15 18 21 G2FD048 S H 21 1590 47 0 34 9 12 80 12 80 11 40 N1VSD20 1...

Page 7: ...16 9 12 00 12 00 11 00 14 G1UA036S14 750 24 2 17 6 12 00 12 00 11 25 17 21 G1UA036S17 21 750 24 0 17 3 12 00 12 00 11 10 14 17 G2FD024 S H 14 17 750 23 6 16 9 12 00 12 00 11 00 17 G2FD030 S H 17 750 2...

Page 8: ...G1FA036S14 1235 33 4 25 0 11 50 10 65 17 21 G1FA036S17 21 1235 33 0 24 4 11 50 10 55 21 G1FA048S21 1235 35 0 25 9 12 00 10 70 G1HD036 1235 33 4 24 7 11 80 10 70 G1HD048 1235 35 0 25 8 12 00 11 05 17 G...

Page 9: ...G1FA060S21 24 1600 47 0 34 8 12 50 11 45 G1HD048 1600 45 0 33 3 12 00 11 15 G1HD060 1600 46 5 36 1 12 40 11 40 21 G1NA048S21D 1400 46 0 34 0 12 00 11 20 17 G1UA048S17 1500 44 5 32 9 12 00 10 50 21 G1...

Page 10: ...12 00 11 15 P1DUB16V G2FD036 S H 17 17 1200 34 4 24 2 12 25 11 40 P1DUC20V PV8C20 UH G1FA036S21 21 1200 33 6 23 6 12 00 11 30 P1DUC20V PV8C20 UH G2FD036 S H 21 21 1200 34 8 24 4 13 00 11 60 P1XDB12V...

Page 11: ...1 T 21 1640 56 0 41 8 12 10 10 10 P1XUC20V G2FD060 S H 24 T 24 1640 56 0 41 8 12 10 10 10 P1XUC20V G2FD061H24 24 1640 56 5 42 0 12 10 10 25 P1XUD20V G1FA G1UA060S24 T 24 1620 56 0 41 6 12 10 10 30 P1X...

Page 12: ...at Add sub base for 1H 1C 1H 1C manual change over electronic non programmable thermostat 1H 1C auto manual changeover electronic programmable deluxe 7 day thermostat 1H 1C auto manual changeover elec...

Page 13: ...30 1 60 CONTACTOR TERMINALS COIL GND LUG C Y R G W Y R G W POWER WIRING CONTROL WIRING FACTORY WIRING 24 VOLT CONTROL WIRING MINIMUM 18 GA WIRE NEC CLASS 2 FURNACE OR AIR HANDLER TERMINAL BLOCK ROOM T...

Page 14: ...14 2 13 6 KW 1 47 1 45 1 43 1 48 1 47 1 45 1 49 1 48 1 46 105 T C 18 1 16 3 14 2 18 7 17 1 15 0 19 4 17 8 15 8 S C 11 3 10 6 9 7 13 0 12 2 11 3 14 7 13 8 12 9 KW 1 58 1 55 1 52 1 59 1 57 2 53 1 61 1 5...

Page 15: ...6 2 07 2 02 1 98 2 09 2 04 2 00 115 T C 21 3 18 6 16 2 22 0 19 5 17 0 22 8 20 5 17 7 S C 14 0 12 9 12 0 16 3 15 3 14 2 18 6 17 8 16 4 KW 2 19 2 13 2 08 2 22 2 16 2 10 2 25 2 18 2 12 125 T C 19 8 16 4...

Page 16: ...3 19 5 KW 2 70 2 61 2 55 2 74 2 64 2 57 2 77 2 68 2 59 125 T C 24 0 20 4 17 0 26 7 21 7 16 8 29 4 23 2 16 7 S C 17 1 15 6 14 1 20 2 17 9 16 0 23 3 20 5 17 8 KW 2 88 2 76 2 70 2 94 2 79 2 70 3 00 2 84...

Page 17: ...2 22 6 28 4 25 5 22 9 S C 21 4 20 0 19 0 23 8 22 3 21 1 26 2 24 6 23 2 KW 3 36 3 29 3 19 3 38 3 31 3 23 3 39 3 33 3 26 NOTE ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH 10...

Page 18: ...33 4 30 8 27 2 33 6 31 3 27 7 S C 23 7 22 5 20 7 24 5 23 6 21 9 25 4 24 6 23 0 KW 4 01 3 88 3 75 4 02 3 91 3 77 4 03 3 93 3 78 125 T C 31 0 27 6 23 5 31 1 28 1 24 1 31 3 28 5 24 4 S C 23 1 21 3 19 6 2...

Page 19: ...37 4 43 9 41 5 38 1 44 2 42 0 38 9 S C 28 4 27 6 25 9 30 0 29 7 28 2 31 6 31 8 30 5 KW 3 39 3 38 3 36 3 39 3 38 3 36 3 40 3 39 3 37 115 T C 41 2 38 1 34 1 41 6 38 7 34 9 42 0 39 3 35 7 S C 27 8 26 7...

Page 20: ...2 6 41 9 37 2 33 1 S C 30 5 28 3 26 3 33 1 30 5 28 4 35 7 32 8 30 5 KW 4 28 4 15 4 02 4 32 4 17 4 05 4 35 4 19 4 08 125 T C 36 3 31 3 28 5 36 9 31 9 28 8 37 6 32 5 29 1 S C 29 2 26 8 24 8 31 8 28 9 26...

Page 21: ...6 2 42 5 39 3 36 2 S C 30 5 30 6 29 5 30 9 32 6 32 8 31 5 32 8 34 1 34 2 32 7 34 5 KW 4 67 4 45 4 25 4 03 4 72 4 49 4 30 4 09 4 74 7 53 4 34 4 18 115 T C 41 8 38 3 35 3 31 7 42 3 38 8 35 8 33 0 42 5 3...

Page 22: ...50 0 53 4 57 6 45 7 50 4 53 7 57 9 S C 40 6 38 6 39 8 39 6 43 1 40 6 41 9 41 6 44 6 42 4 43 5 43 2 KW 7 5 8 1 8 6 9 3 7 5 8 1 8 6 9 2 7 4 8 1 8 5 9 1 115 T C 42 3 46 7 50 1 53 9 42 9 47 4 50 4 54 4 4...

Page 23: ...43 1 42 6 41 6 KW 5 24 5 10 5 06 5 25 5 11 5 07 5 26 5 12 5 08 105 T C 58 1 54 6 50 0 58 9 55 7 51 3 59 7 56 8 52 7 S C 36 9 36 0 34 4 39 8 39 0 37 3 42 7 41 9 40 2 KW 5 86 5 72 5 63 5 87 5 74 5 64 5...

Page 24: ...ING INDOOR COMPONENTS G1UA 1 2 CASED UPFLOW G1HD HORIZONTAL DUCT G2FD MULTI POSITION UPFLOW HORIZONTAL AND DOWNFLOW Available with factory installed horizontal drain pan ADD ON COILS FOR FURNACE APPLI...

Reviews: